Leviton DRCDD-L0 Installation Instructions
Leviton DRCDD-L0 Installation Instructions

Leviton DRCDD-L0 Installation Instructions

Dali distributed room controller gateway

Advertisement

Quick Links

WARNINGS
• TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER AT CIRCUIT BREAKER OR FUSE AND TEST
THAT POWER IS OFF BEFORE WIRING!
• To be installed and/or used in accordance with appropriate electrical codes and regulations.
• If you are unsure about any part of these instructions, consult an electrician.
Introduction
DRCDD-0L0 is the highly integrated LumaCAN gateway device capable of communicating with DALI lighting
systems. It is developed with an innovative approach for all types of commercial and domestic use. Up
to 64 ballasts can be connected to each channel and 16 group addresses can be created per one channel.
Installation
Before installation, consider the items noted below.
Determine power supply strategy and requirements.
Determine LumaCAN device address and channel assignments. This may be
defined on your system submittal drawings.
WARNING: TO AVOID FIRE, SHOCK, OR DEATH;
TURN OFF POWER at circuit breaker or fuse and test that power is off before wiring!
1.
Mount the controller on the DIN rail.
NOTE: To remove the controller from the DIN rail, pull down on the tension spring
and lift off.
2.
Choose the appropriate wiring for your application.
LumaCAN to DALI gateway requires Class 2 (LPS) power which ordinarily will be received over the LumaCAN
network; however, in cases where power isn't available over LumaCAN, an external supply may be used. DALI
networks require power which is typically provided at the controller. If a power supply is provided external to
your gateway, for example if a CN100 is used, then the DALI Power In terminals should remain disconnected. If
however no power supply is provided, it can be provided by the controller.
a.
When to use LumaCAN powered with isolated DALI power
supply:
• When DALI requires a separate isolated power supply.
• When DALI network is wired as Class 1 or 2.
• In this application the total draw from LumaCAN is 60mA for the
gateway.
• In this application the total draw from DALI power supply is 250
mA per DALI channel, 500mA max.
Operation
1.
Reset Switch 1 : to return device Ethernet
settings to factory defaults, press and hold
reset switch for 20 seconds until the status
indicator light begins to blink rapidly.
2.
LED indicator light functions:
LED Indicator Light
Ethernet Link Indicator Light 2
Intermittent Blink
Steady
Ethernet Speed Indicator Light 3
Off
DALI CH1 Indicator Light 4
Intermittent Blink
DALI CH2 Indicator Light 5
Steady
Communication Indicator Light 6
Rapid Blink
Blink once/350ms
Status Indicator Light 7
Rapid Blink
© 2018 Leviton Mfg. Co., Inc.
DALI Distributed Room Controller Gateway

INSTALLATION INSTRUCTIONS

b.
When to use LumaCAN powered:
• When DALI network is wired as Class 2 and all power can be
provided from the LumaCAN network.
• In this application the total draw from LumaCAN is:
1. 250mA or each DALI channel in use
2. 60mA for the gateway
For single channel DALI, 250mA + 60mA = 310mA
For dual channel DALI, 2(250mA) + 60mA = 560mA
Action
Indicates
Rx and Tx Ethernet Traffic
Ethernet Speed is 100Mbps
Ethernet Speed is 10Mbps
Rx and Tx on the DALI channel
Power
Duplicate LumaCAN Node ID
Normal Operation
Indicated Bootloader Mode
Cat. No. DRCDD-L0
CAUTIONS
• Use this device with copper or copper clad wire only.
• For indoor applications only.
• Save these instructions.
The extensive functions of DRCDD-0L0 will enable multiple lighting scenarios. Follow this guide to install and
connect the DRCDD-0L0 gateway to the automation system.
a.
b.
NOTE:
DALI is NOT a PELV/SELV interface. Under some codes, DALI must use an isolated PSU.
DALI Power Supply voltage must NOT exceed the maximum value (Refer to Product Specifications).
8
9
10
2
4
5
14
15
16
DIN rail
To remove
from DIN rail
c.
When to use LumaCAN Data ONLY, isolated DALI power supply,
isolated gateway power supply:
• When DALI requires a separate isolated power supply.
• When DALI network is wired as Class 1 or 2.
• In this application there is no power draw from LumaCAN.
• In this application the total draw from DALI power supply is 250
mA per DALI channel, 500mA max.
• In this application the total draw from the gateway power supply
is 60mA.
3
11
3.
Other features:
• DALI output CH1 and CH2 8
• DALI power input 9
• Not in use 10
• Ethernet jack 11
• Termination resistor switch 12
• LumaCAN address 13
12
• Power input 14
• Device ground 15
13
• QTY 2 LumaCAN jacks RJ45 16
• Micro USB - factory use ONLY - 17
6
7
1
17
PK-A3267-10-00-5A
AR3128
ENGLISH
PK-A3267-10-00-5A
AR3128

Advertisement

loading

Summary of Contents for Leviton DRCDD-L0

  • Page 1: Installation Instructions

    Rx and Tx on the DALI channel DALI CH2 Indicator Light 5 Steady Power Communication Indicator Light 6 Rapid Blink Duplicate LumaCAN Node ID Blink once/350ms Normal Operation Status Indicator Light 7 Rapid Blink Indicated Bootloader Mode PK-A3267-10-00-5A © 2018 Leviton Mfg. Co., Inc. AR3128...
  • Page 2 Leviton warrants to the original consumer purchaser and not for the benefit of anyone else that this product at the time of its sale by Leviton is free of defects in materials and workmanship under normal and proper use for five years from the purchase date. Leviton’s only obligation is to correct such defects by repair or replacement, at its option. For details visit www.leviton.com or call 1-800-824-3005. This warranty excludes and there is disclaimed liability for labor for removal of this product or reinstallation.

This manual is also suitable for:

Drcdd-0l0