Parametrisation and commissioning of ExCos-D (-A) transducers after an ExPro-C... sensor ist connected
Preparation of parametrisation/operation
Operation
Parametrisation, push
If password (PW) protection is active: put PW in, push
Menu
Function
Menu 1
DE, EN, FR
select language: German, English, French
Menu 2
no function - menu skip
Menu 3 no function - menu skip
Menu 4 unit sensor 1
select physical unit
Menu 5 range 1
adjust the measuring range
Menu 6 no function - menu skip
Menu 7 output V, mA
select output signal as VDC or mA
Menu 8 output range 1
adjust the output range
Menu 9 sensor error 1
select signal at sensor error
Menu 10 output 1
select if signal output is increasing or decreasing
Menu 11 unit sensor 2*
select physical unit
Menu 12
range 2*
adjust the measuring range
output range 2*
Menu 13
adjust the output range
Menu 14
sensor error 2*
select signal at sensor error
output 2*
Menu 15
select if signal output is increasing or decreasing
Menu 16 output Ex-i 1 (option, only at ExCos-D-A)
adjust 4...20 mA or 0...20 mA IS output signal
Menu 17
output Ex-i 2 (option, only at ExCos-D-A)*
adjust 4...20 mA or 0...20 mA IS output signal
Menu 18
no function - menu skip
Menu 19 display function
select display on/off, illuminated or backlight off
Menu 20 password
select password protection
Menu 21 save and exit
select save data / factory setting / discard
or back to menu
Menu 22 Set offset 1
Add / subtract from measures value
Menu 23 Set offset 2 *
Add / subtract from measures value
*only available if combination sensor type ExPro-CTF... is connected
Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 (0)9101 9081-0, Fax +49 (0)9101 9081-77, E-Mail info-de@schischek.com
Change operation- / parametrisation mode Example of parameters
To change from operation to parametrisation mode push
E X P L O S I O N P R O O F
"enter button"
for 3 sec.
menu save and exit.
Enter
Indication
DE, EN, FR
english
deutsch, english, francais
unit sensor 1
°C
°C, °F
range 1
0..50 °C
output V/mA
V
mA, V
output range 1
0..10V
sensor error 1
10V / 20 mA
10V / 20 mA or 0V / 0mA
output 1
increasing
increasing, decreasing
unit sensor 2
%rH
%rF, %rH
range 2
0..100 %rH
output range 2
0..10V
sensor error 2
0V / 0 mA
10V / 20 mA or 0V / 0mA
output 2
increasing
increasing, decreasing
output Exi 1
4..20 mA
output Exi 2
4..20 mA
display function
on illuminated
on-illuminated, on, off
new password
yes no
save and exit
save data
set offset 1
0.00°C
sett offset.2
0.00%rH
www.schischek.com
for minimum 3 seconds. Back over the
Select
Enter
adjust lower limit
adjust lower limit
adjust lower limit
adjust lower limit
adjust lower limit
adjust lower limit
E X P L O S I O N P R O O F
Language
English
Range
0...+50 °C, 0...100 % rH
Output
each 0...10 VDC, 0...20 mA
Outputs Ex-i
4...20 mA
Next indication
Next selsction
Enter
range 1
0..50 °C
adjust higher limit
output range 1
0..10V
adjust higher limit
range 2
0..100 %rH
adjust higher limit
output range 2
0..10V
adjust higher limit
output Exi 1
4..20 mA
adjust higher limit
output Exi 2
4..20 mA
adjust higher limit
password
0000
Next menu
D.EC-D-01.05-en
12-July-2012
4 / 4