关于产品 PS 8040-510 E 3U PS 8080-340 E 3U PS 8160-170 E 3U PS 8200-140 E 3U PS 8400-70 E 3U 电源输入 340…460V AC 340…460V AC 340…460V AC 340…460V AC 340…460V AC 输入电压 可选输入电压范围 3Ph, PE 3Ph, PE 3Ph, PE 3Ph, PE 3Ph, PE 要求相数...
Page 8
关于产品 PS 8240-170 E 3U PS 8500-90 E 3U PS 8600-70 E 3U PS 81500-30 E 3U 电源输入 340…460V AC 340…460V AC 340…460V AC 340…460V AC 输入电压 588…796V AC+MP 588…796V AC+MP 588…796V AC+MP 588…796V AC+MP 可选输入电压范围 3Ph, PE 3Ph, PE 3Ph, PE 3Ph, PE 要求相数...
Page 26
Do not connect external voltage sources with reversed polarity to the DC output! The device will be damaged. • Avoid connecting external voltage sources to the DC output, especially those who can generate voltages higher than specified for the device! Instruction Manual Date: 06-05-2014 PS 8000 E 3U Series...
Page 30
Example: a 80V model has min. 0.2% voltage accuracy. This is 160mV. When setting a voltage of 5V and with an allowed maximum deviation of 160mV, the resulting actual value could be between 4.84V and 5.16V. Instruction Manual Date: 06-05-2014 PS 8000 E 3U Series...
Page 32
Example: a 80V model has min. 0.2% voltage accuracy. This is 160mV. When setting a voltage of 5V and with an allowed maximum deviation of 160mV, the resulting actual value could be between 4.84V and 5.16V. Instruction Manual Date: 06-05-2014 PS 8000 E 3U Series...
Also contact your dealer immediately. Input connection (single unit) The unit‘s AC input requires two (3.3kW/5kW models) or three phases (6.6kW/10kW/15kW) models of a three-phase supply, plus ground (PE). The connection is done with cables of proper cross section. See table below for typical input currents when connecting one unit. Instruction Manual Date: 06-05-2014 PS 8000 E 3U Series...
(+) Sense must only be connected to (+) at the load appli- cation and (–) Sense must only be connected to (–)! Else both systems can take damage. For additional information also see section „7.7 Remote sense operation“. Instruction Manual Date: 06-05-2014 PS 8000 E 3U Series...
A second push leaves the preset mode instantly or it ends automatically, if no preset button is pushed or any set value is altered within 5 seconds. The button might be locked by the condition LOCK. See 6.2.8. Instruction Manual Date: 06-05-2014 PS 8000 E 3U Series...
Attention! Permanent input undervoltage or overvoltage must be avoided! Figure 9. Wiring remote sense Instruction Manual Date: 06-05-2014 PS 8000 E 3U Series...
„off“ , except LOCAL mode is active. This mode locks all interface from access to the device. Also see „6.2.7 Pushbutton Local“. • The grounds of the analogue interface are related to minus output. Instruction Manual Date: 06-05-2014 PS 8000 E 3U Series...
>4V Short-circuit-proof against DGND High * AI = Analogue input, AO = Analogue output, DI = Digital input, DO = Digital output, POT = Potential ** Internal Vcc = 13.8 *** Power fail = input failure or PFC (reported only since firmware 6.01) Instruction Manual Date: 06-05-2014 PS 8000 E 3U Series...