Taco SmartPlus-e Instruction Sheet

Taco SmartPlus-e Instruction Sheet

Ecm high-efficiency hot water recirculation system

Advertisement

Quick Links

U.S. Patent # 8,594,853
SUPERSEDES: NEW
Plant ID# 001-5008
APPLICATION:
The Taco SmartPlus-e™ consists of a 006e3™ ECM high-efficiency circu-
lator combined with our SmartPlug Instant Hot Water Control
SmartPlus-e is designed to increase hot water comfort while conserving
water and energy. By recirculating "cooled" hot water back to the water
heater, the wait for hot water is reduced to seconds. A dedicated hot water
recirculation line within the piping system is required.
HIGH QUALITY FEATURES:
The SmartPlus-e System includes a high-efficiency Taco multi-speed
006e3 ECM permanent magnet circulator. The circulator is suitable for
most residential homes with hot water supply lines up to 300 feet.
SmartPlug Instant Hot Water Control learns weekly hot water usage
patterns in the home. It uses that information to run the 006e3 providing
hot water when its needed.
WARNING: All local plumbing and electrical codes should be
followed when installing this product.
CAUTION: To ensure all plumbing system components are
protected from the damaging effects of water hammer, be sure
an approved water hammer arrestor is installed in the system
per locally recognized National plumbing codes.
CAUTION: Do not plug in the 006e3 circulator power cord until
the system is filled with water and purged of air.
WARNING: The 006e3 circulator must be installed and
supported by the circulation piping.
Installing the SmartPlus-e 006e3 Circulator:
Hot Water Return Line (Option No. 1)
1. Install the SmartPlus-e 006e3 circulator in-line on the DHW return line
pumping toward the hot water source as shown in Figure 1. Be sure the
directional arrow on the casing is installed with the arrow pointing toward
the hot water source.
Backflow
Isolation
Preventer
Cold
Hot
Valve
Supply
Supply
Isolation
Thermal
Expansion
Union
Tank
Option No. 1
Figure 1: Installation Diagram (For reference only)
Instruction Sheet
Temperature
Sensor
Valve
SmartPlug
Isolation
006e3
Valve
ECM Circulator
Union
Flow
Drain
Check
Valve
Valve
2. Install all other system components as shown in the piping diagram
in Figure 1.
. The
3. When all components are installed, fill system with water.
®
4. Close the isolation valve on the return line between the water heater
and the flow check valve.
5. Open the drain valve between the
isolation valve and flow check
valve and drain water until all air
is purged from the line.
6. Close drain valve and open
isolation valve.
To change operating speed settings:
Modify the performance of the 006e3 as needed by rotating the
programming dial using a flat screwdriver. A blue LED will illuminate
when the circulator is powered on. The LED will flash each time mode
is changed. The selection of the right performance curve depends on
the characteristics of the system and the actual flow and head
requirements. See 006e3 Performance Curves and Setting Selection
Guide on page 3 to determine best speed setting for the system.
NOTE: If flow velocity noise develops, turn dial counter-clockwise to
reduce pump speed until noise disappears.
Backflow
Isolation
Preventer
Valve
Thermal
Expansion
Tank
Fixtures
Option No. 2
Figure 4: Installation Diagram (For reference only)
Hot Water Supply Line (Option No. 2)
Isolation
Valve
1. Install the SmartPlus-e 006e3 circulator in-line on the DHW supply
line as shown in Figure 4. Be sure the directional arrow on the casing
is installed with the arrow pointing away from the hot water source.
2. Install all other system components as shown in the piping diagram in
Figure 4.
3. Follow steps 3 through 6 listed under the Hot Water Return Line
(Option No. 1) section.
1
EFFECTIVE: February 27, 2018
Temperature
Sensor
Cold
Hot
Supply
Supply
Isolation
Isolation
Valve
Valve
Union
Isolation
Valve
Union
Flow
Drain
Check
Valve
Valve
102-550
Figure 2
Isolation
Valve
Fixtures

Advertisement

loading

Summary of Contents for Taco SmartPlus-e

  • Page 1 Thermal Expansion Union 1. Install the SmartPlus-e 006e3 circulator in-line on the DHW return line Tank pumping toward the hot water source as shown in Figure 1. Be sure the directional arrow on the casing is installed with the arrow pointing toward the hot water source.
  • Page 2 Benefits: require a sensor lead wire in excess of 10'. If the sensor lead length needs to • Easy to Install: Upgrades the SmartPlus-e 006e3 circulator to be increased, standard "18 AWG" “Smart” operation. gage wire and 2 wire nuts can be spliced into the temperature •...
  • Page 3 Union Fitting Selection Guide SmartPlug Specifications: Input: 120VAC, 50/60HZ, single phase, 6A. ."/)0$1#$*% 20*-,)#'3*-" 120VAC, 50/60HZ, single phase, 1/2 hp Output: (limited to 6 FLA, 36LRA). 894:/;<"+</=,&>1 ;?=D.-.= Sensor: NTC Thermistor, 10K ohm @ 77°F, B= 3392. 125V, 6A, Medium Acting 5x20 mm glass, 894:/;<"+</?@AB ;?=D0-.B Fuse:...
  • Page 4 UCTS. assistance on warranty returns, the purchaser may either contact to the defective product or part. Taco reserves the right to make the local Taco stocking distributor or Taco. If the subject product changes in details of design, construction, or arrangement of...