Page 2
Change Control Date Version Author Mod No Reason for change Feb 18 Provi Draft for Review by AP Apr 18 401673 Upd and released following review...
This provides weights including and excluding a full tank of fuel Only commercially available diesel fuel can be used. If a special type of diesel is Fuel: to be used please consult HGI first to discuss its suitability 498-1084 HRD060D Diesel Generator...
200 hours (first oil change at 50 hours) Cylinders: Power: 6.5 kW Engine Speed: 3000 rpm Engine Cooling: Air cooled Starting Method: Electric Start Electrical System: 12V DC system Emissions Level: n/a below threshold. Lowest starting temperature: -10°C without extra aids Other: HRD060D Diesel Generator 498-1084...
Page 10
1014 x 580 x 851mm Operating Clearance: Minimum of 0.6 m all around and above. Access for Servicing: Access of 0.6 m required both sides. Weight – fuel tank empty: 185 kgs Weight – fuel tank full: 210 kgs 498-1084 HRD060D Diesel Generator...
During servicing, follow HSE recommendations NOTICE regarding the handling and disposal of Notice refers to a method or practice which can contaminated oil products. result in product damage, or to draw attention to additional information or explanations. 498-1084 HRD060D Diesel Generator...
Page 13
On end: KEEP FLAMMABLE MATERIAL AWAY FROM THE GENERATOR Part of label No: 499-1081-003 The exhaust and some surfaces are hot and flammable material should not be allowed near the generator. HRD060D Diesel Generator 498-1084...
Page 14
No: 499-1081-003 If the generator is not producing enough power for the application or you suspect a problem do not adjust the engine speed. This may damage the engine, alternator and any power equipment plugged into the generator. HRD060D Diesel Generator...
Page 15
TEST button is located and shown how to use it. An earth spike kit is available as an optional extra. On Control Panel. Qty. 1. ELECTRICITY IS DANGEROUS Label No: 499-1081-004 Warning Label advising safe use of sockets HRD060D Diesel Generator 498-1084...
Page 16
Qty 1 tions of the switch. Label No. 499-945-012 Next to exhaust outlet. CAUTION HOT EXHAUST Qty. 1 The exhaust pipe is shielded as much as is practical but the final outlet is hot. Label No: 499-1081-010 498-1084 HRD060D Diesel Generator...
Page 17
FUEL FILL THIS SIDE the access panel The fuel filler cap is located inside this cover. Label No: 499-1081-017 Remove the cover to access the filler and for refuelling. DO NOT REFUEL WHILE THE SET IS RUNNING OR HOT! HRD060D Diesel Generator 498-1084...
Page 18
If you cannot hold a normal Pt No. 499-325-094 conversation because of background noise your hearing may be in danger. You should move away, wear ear protection or turn off the equipment. 498-1084 HRD060D Diesel Generator...
Page 19
On front panel over battery RECYCLE compartment The battery contains lead and sulphuric acid Part of label and should be recycled at an approved facil- No: 499-081-001 ity only and not put into a dust bin. HRD060D Diesel Generator 498-1084...
Lifting Operations & Lifting Equipment Regula- cations 08/03 tions 1998 (LOLER) SI 1998 No: 2307 For the HRD060D generator, manual lifting (even with The following publication should also be observed:- four people) cannot be recommended as a formal risk •...
Page 21
Lifting by Hooks or Straps The generator can be lifted by hooks or lifting straps passing through the same pods as indicated above.A four point (not two-point) lift is recommended. HRD060D Diesel Generator 498-1084...
Page 23
• Even if the person remains conscious anticipate that they will pass into shock. • Local burns where contact was made should be covered by a sterile dressing. • Obtain medical attention immediately. HRD060D Diesel Generator 498-1084...
A large lift up lid provides access for ease of servicing and maintenance in a tight space. The HRD060D is configured to be operated locally at the set but can be provided with an optional remote start controller.
Page 25
The Icons and the descrip- The DSE module will go into standby when no com- tions of the the alarms they represent be seen mon alarms have been triggered after 1 minute of below: HRD060D Diesel Generator 498-1084...
Page 26
Safety On timer has expired. Contact HGI Sales for further information on the types of remote start panels available for your generator. 498-1084 HRD060D Diesel Generator...
Page 27
230V spike. An earth spike can be supplied as an optional socket and terminals. extra and should be driven at least 600 mm into soil. HRD060D Diesel Generator 498-1084...
Check that the generator is located on level ground and in an open space with free air flow on all sides, at least one metre from other equipment and buildings, and clear of any combustible material. 498-1084 HRD060D Diesel Generator...
Maintenance Section. Stopping 1. Switch off the electrical output and disconnect the load from the generator’s output. 2. Allow the generator to run off load for 2 minutes to cool down. 3. Press the red STOP button. HRD060D Diesel Generator 498-1084...
The control module can be set by a small switch on the back to sound an alarm AND shut down on low fuel or just sound an alarm. 498-1084 HRD060D Diesel Generator...
Smoke seen from exhaust pipe. particularly if the temperature is too low. • Suspect serious fault with the engine. * Care should be taken while working on the fuel system particularly when fuel is under high pressure. HRD060D Diesel Generator 498-1084...
Each 110V/230V output has its own MCB to prevent excessive breaker (MCB). electrical load being taken through that socket. Check if the miniature circuit breaker (MCB) has tripped or 2-pole circuit breakers have been set to OFF. 498-1084 HRD060D Diesel Generator...
Run on ¼, ½, ¾ full load for 30 minutes º º º If you’d like to make an appointment for HGI to service your generator using our in house 26-point health checker guide for your generator then please contact the Service Department. HRD060D Diesel Generator 498-1084...
Drain the oil in the engine while the engine is warm. that the unit trips out when the generator is running. Warm oil drains quickly and completely. 498-1084 HRD060D Diesel Generator...
Page 35
With the front panel removed to reveal the battery check the foam seal is complete all around this compartment and air can only be drawn from outside and cannot re-circulate. HRD060D Diesel Generator 498-1084...
Page 36
• Check all wiring is secure and not damaged. • Check the output voltage and frequency are correct. • Check the earth continuity between the socket earth pins and the generator frame. 498-1084 HRD060D Diesel Generator...
Maintenance Harrington Generators International Maintenance Record Sheet (for use by owner / service agent) Name of Owner: Name of Service Organisation: Address: Address: Maintenance Record Sheet Order No: Job No: Generator Details (from Data Plate) Date of Service: Model: Hours Run meter reading: (hrs) Serial No: Build Code:...
If the generator is to be stored long term it would be beneficial to start and run the generator under electrical load for half an hour every three months and then store as above ( but no need to change the oil). HRD060D Diesel Generator 498-1084...
- http://www.yanmarengines.co.uk/products.php?range_id=1§ion_id=2 Deep Sea 3110 User Guide - http://www.deepseaplc.com/products/dse-genset Mecc Alte ECO / ECP User Manual - http://www.meccalte.com If you are still unsure then please contact HGI Technical Helpline: +44 (0) 1629 821 614 or 821 652 HRD060D Diesel Generator 498-1084...