Overview
The
Vantage
LVOS-0-10-PWM-1
(LVOS) has four PWM and four analog
Low Voltage Outputs along with four
high
voltage
relays.
All
connections are independent from each
other. The station is powered from a
universal
input
of
120-277
50/60Hz source. The high voltage
relays are isolated from the station's high voltage power supply. All
outputs can be manually controlled and monitored from the front of the
station. An Override switch may be connected allowing all the low voltage
loads and high voltage relays to be ON or OFF for fail-safe applications.
The station comes housed in a custom metal enclosure or may be ordered
separately for installation into Vantage's IAUX enclosure. Communication
to the Vantage System is via Ethernet or Station Bus.
Two Ways to Order
Part Number
Station with Single Enclosure:
Low Voltage Output Station (PWM and 0-10) 120v-
LVOS-0-10-PWM-1
277v – comes in a custom Vantage supplied, UL
rated enclosure
LVOS-O-10-PWM station only – for installing in UL
LVOS-0-10-PWM-P-1
rated IAUX-2, IAUX-4, or LCAP series enclosures*.
*WARNING: This is not a DIN station and is not designed for DIN rail.
Vantage's auxiliary enclosures, IAUX-2 / IAUX-4 and LCAP44A-6
enclosures are ordered separately!
Highlight Features
 4 PWM, LV outputs
 4 Analog, 0-10LV outputs
 4 High Voltage Relays – tied to LV outputs in Design Center
 Twelve membrane style actuators and LED status indicators
 High Resolution Performance when Dimming
 Communicates via Vantage Ethernet Bus or Station Bus
 Housed in a custom, UL rated enclosure
o part #LVOS-0-10-PWM-1 includes station and enclosure
 Enclosure configurations
o IAUX-2 – up to six stations per enclosure
o IAUX-4 – up to ten stations per enclosure
o
 Override Switch connections for ON and OFF states of all loads
collectively
Station Specifications
General
Wall Box
Dimensions, HWD
Cover
9.75" x 11.25" x 0.6" (1/16" Thick)
Dimensions, HWT
24.77cm x 28.58cm x 15mm-thick
Station Only
Dimensions, HWD
Weight with box
LED Indicators
Microprocessor Status, Configuration, Loads
Ambient Operating
Temperature
Relative Humidity
Cooling
Firmware
Upgradeable via Ethernet or Station Bus
Manual Control
Overlay with control/status for each output
Real-time scheduling provided by FreeRTOS
FreeRTOS™
AC Input – Power Supply
Type
Input voltage /
frequency
Input power
Connection type
Connection rating
Input / Output Connections (Low Voltage)
RJ45 – Auto Crossover Detection – 10 / 100
Vantage Ethernet
Ferrite clamp included for Ethernet
Bus Port (VEB)
Station Bus
connection
2C, 16AWG / 1.31mm2, twisted, non-
Station Bus Wire
shielded, <30pF per foot. Separate a
Specification
minimum of 12" / 30.5cm from other parallel
communication and/or high voltage runs.
Station Wiring
configuration
Station Equivalent
0.35W on IC-24 / 0.55W on IC-36
InFusion
4 Dry Contacts, (3 and 4 may be for an IR
Auxiliary Inputs
Receiver and Light Sensor respectively)
Override Inputs
©Vantage, 8/12/2016 / IS-0523-B
twelve
VAC
Description
9.0" x 10.5" x 2.75"
22.86cm x 26.67cm x 6.98cm
3.32" x 10.34" x 2.667"
8.43cm x 26.26cm x 6.77cm
5.85lbs -or- 2.65kg
32-104°F / 0-40°C
Maximum 90%, non-condensing
Convection
(www.freertos.org)
Universal Input
120 – 277 VAC 50-60Hz
<16W
0.20" pitch removable plug
300V 10A
connection only (see page 3)
24V / 36V Station Bus
Daisy-chain/Star/Branch
Yes – All ON or All OFF contacts
Low Voltage Output Station, 0-10V & PWM – MODEL: LVOS-0-10-PWM-1
I N S T A L L A T I O N
Low Voltage Output Station, 0-10V & PWM – MODEL: LVOS-0-10-PWM-1
Low Voltage Output: PWM Low
Specification
Number of outputs
Output voltage
Output current
Loads Per Output
Resolution
Duty cycle
Frequency
Connection type
Connection rating
Connection Torque
Low Voltage Output: 0-10V
Specification
Number of outputs
Output
External source
voltage
Loads Per Output
Resolution
Connection type
Connection rating
Connection
Torque
High Voltage Output: Relays
Number of relays
Voltage rating
Type
Load rating,
general purpose
Load rating,
incandescent
Electronic Ballast
Relay input
connected to line
feed
Connection type
Connection rating
Connection
Torque
Protection
High voltage input, over
voltage protection
Low voltage 0-10V output
over current protection
Low voltage PWM output
over current protection
Certifications
UL
Listed
EN55022 Radiated / Conducted emissions
EN55024 61000-4-2 ESD immunity
EN55024 61000-4-3 Radiated immunity
CE,
EN55024 61000-4-4 Fast transient immunity
FCC Part
EN55024 61000-4-5 Surge immunity
15,
EN55024 61000-4-6 Conducted immunity
Sub-Part
EN55024 61000-4-8 Magnetic field immunity
B
EN55024 61000-4-11 Voltage dips/interruption immunity
61000-3-2 Harmonics current emissions
610000-3-3 Flicker emissions
PWM Outputs, 12V (Source)
Low voltage outputs 1-4 may be configured as PWM (Pulse Width
Modulation). PWM Duty Cycles are programmed using Power Profiles
from 0%-Minimum On to 100%- Maximum On (99.9% actual). The load
level is a percentage between the minimum and maximum duty cycle
(Power Profile Minimum On and Maximum On). The output can be
reversed in Design Center through the Power Profile. For example, a
0% duty cycle can either be load ON or load OFF.
Low Voltage Outputs, 0-10V (analog)
Low Voltage Controls 5-8 and Ground are used to control devices
that work with an analog 0-10V signal. Ground provides the negative
reference for the output voltages. All Grounds are connected
internally to each other. Each output, 5-8, can sink or source 0-100mA
at any voltage from 0-10VDC. The load level sets the percentage
between the minimum and maximum voltage that is selected for that
load.
NOTE: Loads 1 – 8, Low Voltage outputs, should be limited to
250 feet / 76.2 meters for each wire run, using a minimum of
18AWG / 0.823mm2 gauge wire. All LV connections use 4.4
inch pound torque. Stranded wire recommended.
V A N T A G E I N S T A L L G U I D E S
IEC 60929 Annex E
4
12V (source only)
100mA per channel, 400mA total
50@ 2.0mA per load (typical)
> 1024 steps
Variable 0% to 99.9%
760Hz
0.20" pitch removable plug
300V 10A
4.4 inch pounds
IEC 60929 Annex E
4
0-10V @ 100mA sink or source
Typical 10V / Maximum 20V
50@ 2.0mA per load (typical)
>1024 steps
0.20" pitch removable plug
300V 10A
4.4 inch pounds
4
120V-277 VAC
Normally open
10A
5A
5A
No
0.20" pitch removable plug
300V 10A
4.4 inch pounds
MOV
PTC Fuse (self resetting)
508
page 1 of 4

Advertisement

loading

Summary of Contents for Vantage Hearth LVOS-0-10-PWM-1

  • Page 1 V A N T A G E I N S T A L L G U I D E S 2168 West Grove Parkway, Suite 300, Pleasant Grove, UT. 84062 USA Low Voltage Output Station, 0-10V & PWM – MODEL: LVOS-0-10-PWM-1 Telephone: 801 229-2800 ● Fax: 801 224-0355...
  • Page 2 I N S T A L L A T I O N Line Voltage Relay Operation Power Connection There are four (4) AC line voltage relays on this LVOS station. They A 120 – 277 VAC 50-60Hz line feed from breaker connects to the Line, are single-pole, single-throw relays (SPST) and are initially Neutral, and Ground connections.
  • Page 3 I N S T A L L A T I O N MULTI-VIEW LINE DRAWING WARNING: This is NOT A DIN station and is not designed for DIN rail. Only mount this station in Vantage’s UL rated box supplied with part number LVOS-0-10-PWM or Vantage’s auxiliary enclosures, IAUX-2/IAUX-4 when ordered separately! WIRING EXAMPLE (See Wiring Terminations table right side)
  • Page 4 I N S T A L L A T I O N AUX ENCLOSURE WITH LVOS STATIONS EXAMPLE LVOS Load Wiring Examples using Vantage auxiliary enclosures; order LVOS-0-10-PWM-P-1 for station only and IAUX-2(4) as needed. Notice all high voltage is through the LEFT or RIGHT sides of the enclosure and all low voltage is through the CENTER of the enclosure. These connections can be through the TOP and/or BOTTOM of the enclosure from the respective sides.