Data and installation

Compatibility

As a Zonal Mimic panel the system control panel must
have the following card software:
Control panel CARD
LPC
New Shorter Card ONLY
³ means equal to or greater than
As a Customised Mimic panel the system control panel
must have the latest card software.

Installation

Fuses on Master Repeat Card
Fuses
Rating
FS4
3.15A AB Ceramic
FS2
3.15A AB Ceramic
FS3
2A
QB
The Mimic Panel set consists of:
Component
by Honeywell
VIGILON FIRE SYSTEM
NOT YET IN SERVICE
AWAITING COMMISSIONING
u
Backbox assembly
v
Inner door assembly
w
Outer cover assembly
x
Key for Outer cover
y
3.15A 20mm x 5mm AB Ceramic
z
2A 20mm x 5mm Quick Blow Fuse
{
Battery lead
|
Link lead
}
6V 7Ah Battery
~
Overlay pack for A3 Mimic panel
1 x pre-printed Zonal sheet
2 x blank A3 sheets for printing
a Mimic or Zonal overlay
1 x LED spacing sheet
The overlays in the pack are high quality UV
protected A3 paper.
A magnetic strip used to hold an overlay in
place is fitted to the top side of the inner door.
2
EN54
BS5839
Control Panel
Control
software
Panel
software
³ V4.19
³ 3.90
20mm x 5mm
20mm x 5mm
20mm x 5mm
Quantity
1
1
1
1
2
1
1
1
2
1 Set

Mounting the backbox

The A3 Customised Mimic panel can be mounted either
landscape or portrait, while an A3 Zonal mimic panel must
only be mounted landscape when using the overlay
supplied.
a.
Locate the package Back box assembly
Landscape orientation
Portrait orientation
Cable entry points
5 - Back and 5 - Top
Earth points
4-off
b.
Knock out the required cable entry points from the
back box.
c.
Mark out the 4-back box fixing positions on the wall to
which the panel is to be mounted and secure it with
suitable fixings.
&
Ensure the mains power is isolated to
from the panel.
d.
Terminate the loop and mains cables at the entry
points and if required connect the cables to the
appropriate terminals.
e.
All the other parts are installed during commissioning.
4188-945_issue 2_05/10_pt1_A3 Mimic
A3 Mimic Panel
u
.
Top cable entry points
Earth points
5-off Back
4-off
5-off Top
by Honeywell
VIGILON FIRE SYSTEM
NOT YET IN SERVICE
AWAITING COMMISSIONING
Back box
380mm
240mm