Content Applications VIBROCONTROL 900 Series Types VIBROCONTROL 950 Accelerometers (CCS) VIBROCONTROL 960 Velocity Sensors Hints for safe operation of VIBROCONTROL 950/960 Setup the VIBROCONTROL 950/960 RS232 interface RS485 interface The Compact Setup Software NOTE! This symbol provides general and useful information for using the product.
Applications Applications The VIBROCONTROL 950/960 Vibration Monitor is a maintenance free device situated mounted in a DIN rail enclosure. It can be used to monitor vibration parameters in applications with machines like pumps, blowers, ventilators, decanters, separators, centrifuges, mills and milling equipment.
Mounting: Mount the VIBROCONTROL 950/960 device on a 35 mm DIN rail inside the control cabinet. Mount the device vertically but make sure to leave enough space between the unit and the top and/or bottom of the control cabinet.
RS485 chain of devices. To use the RS485 interface, connect terminal #17 (marked: “+RS485”) and terminal #18 (marked: “– RS485”) of the VIBROCONTROL 950/960 Vibration Monitor to the RS485 chain of devices using a shielded cable.
The cable must be terminated with a 120 Ω resistor in both ends, i.e. on the PC side and at the last device on the RS485 chain of devices. The VIBROCONTROL 950/960 Vibration Monitor has a built-in 120 Ω resistor, which can be used for this purpose.
Need help?
Do you have a question about the VIBROCONTROL 950 and is the answer not in the manual?