Bus line, cable length and cross-section ....................36 Example ..............................36 Important notes on connecting the CAN bus system ................. 37 Pin assignment of the CAN bus connector and coupling for non pre-wired control cables ............................37 NRG 26-61 - Installation & Operating Manual - 819874-00...
Page 3
Checking installation and function ......................56 Taking out of service ............................ 57 Cleaning the level electrode ......................... 58 Cleaning interval ............................58 Disposal ................................ 58 Returning decontaminated equipment ......................58 EU Declaration of Conformity ........................59 NRG 26-61 - Installation & Operating Manual - 819874-00...
How to use this Manual This Installation & Operating Manual describes the correct use of the NRG 26-61 level electrode. It applies to persons who integrate this equipment in control systems, install, bring into service, operate, maintain and dispose of this equipment. Anyone carrying out the above-mentioned activities must have read this Installation &...
Warning of a dangerous situation that may possibly result in death or serious injury. CAUTION Warning of a situation that may result in minor or moderate injury. ATTENTION Warning of a situation that results in damage to property or the environment. NRG 26-61 - Installation & Operating Manual - 819874-00...
Data transmission standard and interface for connecting electronic equipment, sensors and control systems. Data can be sent and received. NRG .. / URS .. / URB .. / SRL .. / etc. Equipment and type designations of GESTRA AG, see page 10. SELV Safety Extra Low Voltage...
Use as a safety high-level (HW) limiter and low-level (LW) limiter The NRG 26-61 level electrode is used in conjunction with the URS 60 / URS 61 safety control unit as a safety high-level limiter and low-level limiter for pressurised steam and hot-water plants.
Usage for the intended purpose Applicable directives and standards The NRG 26-61 level electrode has been tested and approved for use in the scope governed by the following directives and standards: Directives: Directive 2014/68/EU EU Pressure Equipment Directive ■ ■...
& Operating Manuals for the system components used. You will find the latest Installation & Operating Manuals for the system components named ■ ■ in Fig. 1 on our website: http://www.gestra.com/documents/brochures.html NRG 26-61 - Installation & Operating Manual - 819874-00...
Do not use the equipment in potentially explosive atmospheres. Do not bring any equipment into service that does not have its own specific name plate. The name plate indicates the technical features of the equipment. NRG 26-61 - Installation & Operating Manual - 819874-00...
Check that the plant is not carrying live voltage before commencing work. ■ ■ Danger to life from a faulty NRG 26-61 level electrode due to the sudden escape of hot steam or hot water. Shocks and impacts during transport or installation can result in damage to or leaks in the NRG 26-61 level electrode, causing pressurised hot steam or hot water to escape through the pressure relief hole.
Persons trained by the plant operator to work Retrofit Specialist staff with pressure and temperature. Fig. 2 Notes on product liability We the manufacturer cannot accept any liability for damages resulting from improper use of the equip- ment. NRG 26-61 - Installation & Operating Manual - 819874-00...
Functional safety, safety integrity level (SIL) In combination with the URS 60 / URS 61 safety control unit, the NRG 26-61 level electrode is suitable for safety functions up to SIL 2. It is an element of a safety circuit up to SIL 2 as per EN 61508 in the SPECTOR connect system, and can transmit alarm notifications.
Fraction of undetected dangerous failures that have a beta = 2 % common cause Fraction of detected dangerous failures that have a com- beta d = 1 % mon cause Fig. 4 NRG 26-61 - Installation & Operating Manual - 819874-00...
If the water falls below the set low-level point, the URS 60 or URS 61 safety control unit initiates a safety shutoff. This “Low Water (LW)” switchpoint can be adjusted solely using the rotary knob on the NRG 26-61 level electrode.
Page 17
Display and signals, see page 47 / 51 * The NRG 26-61 level electrode has a green 4-digit, 7-segment display for showing readings, status infor- mation and fault codes. A red and green LED indicate the operating status.
Page 18
Level control functions In addition, the NRG 26-61 level electrode can be used in conjunction with an NRR 2-60 / NRR 2-61 level controller to form a level control system. The controller parameters are set solely on the URB 60 visual display and operating unit.
0.1 % ■ ■ Resolution for internal processing: 15 bits with sign (16 bits) ■ ■ Supply voltage 24 V DC +/-20 % ■ ■ Power consumption Max. 7 VA ■ ■ NRG 26-61 - Installation & Operating Manual - 819874-00...
Page 20
■ ■ Admissible installation positions Vertical ■ ■ Oblique to a maximum inclination of 45°. In this case, the length of the electrode rod is limited ■ ■ to 688 mm maximum. NRG 26-61 - Installation & Operating Manual - 819874-00...
Manufacturer GESTRA AG Protection class Münchener Str. 77 28215 Bremen Disposal information GERMANY Serial number Fig. 5 The date of production is stamped on the screw-in body of every level electrode. NRG 26-61 - Installation & Operating Manual - 819874-00...
Factory settings The NRG 26-61 level electrode is delivered ex-works with the following settings: Parameter values Display in Parameter Unit menu NRG 26-61 Limiter ID Id.Lo 0002 - - - Limiter ID Id.Hi 0005 - - - Controller group 0001...
M12 CAN bus connector, 5-pole, A-coded Sheath (simplified view) Seal seat for sealing ring Sealing ring D 27 x 32, form D, DIN 7603-2.4068, bright annealed Electrode thread Electrode Electrode rod insulation, PTFE Fig. 7 NRG 26-61 - Installation & Operating Manual - 819874-00...
Take further measures to protect the equipment from lightning, insects and animals, and ■ ■ salty air. You will need the following tools: Torque wrench (with size 41 open-ended spanner attachment), see page 24: ■ ■ NRG 26-61 - Installation & Operating Manual - 819874-00...
To prevent current leaks, maintain a minimum distance of 14 mm between the electrode ■ ■ and earth (flange or tank wall). Check the boiler coupling and flange during the preliminary boiler inspection. ■ ■ NRG 26-61 - Installation & Operating Manual - 819874-00...
Screw in the second electrode and tighten the nut in the body to a torque of 25 Nm. Reconnect the electrode wiring to the PCB. Close the rear body panel of the second electrode and screw back on. Installation example with dimensions, see Fig. 13, page 31 NRG 26-61 - Installation & Operating Manual - 819874-00...
Protective tube (provided at the site) for internal installation. Illustration not to scale. Key, see page 34 G ¾ DN 50 ≥ 14 ≤ 90° Ø 20 Fig. 11 All lengths and diameters in mm NRG 26-61 - Installation & Operating Manual - 819874-00...
Page 30
Protective tube (provided at the site) for internal installation. Illustration not to scale. Key, see page 34 G ¾ DN 50 ≥ 14 ≤ 90° Ø 20 Fig. 12 All lengths and diameters in mm NRG 26-61 - Installation & Operating Manual - 819874-00...
Page 31
Illustration not to scale. Key, see page 34 G ¾ G ¾ DN 100 24.5-26.0 24.5-26.0 ≥ 14 " ≤ 90° Ø 20 Fig. 13 All lengths and diameters in mm NRG 26-61 - Installation & Operating Manual - 819874-00...
Page 32
Level pot (≥ DN 80) for mounting externally. Illustration not to scale. Key, see page 34 G ¾ ≥ DN 20 ≥ 14 § ≥ DN 20 ≥ DN 20 All lengths and diameters in mm Fig. 14 NRG 26-61 - Installation & Operating Manual - 819874-00...
Page 33
The level electrode must not be at an incline of more than 45°, and the length of the electrode rod is limited to 688 mm maximum. Illustration not to scale. Tube e.g. 33.7 x 3.2 Fig. 15 All lengths and diameters in mm NRG 26-61 - Installation & Operating Manual - 819874-00...
If necessary, you can orientate the display in the desired direction by rotating the terminal box. ATTENTION Rotating the terminal box ≥ 180° will damage the level electrode’s internal wiring. Never rotate the terminal box more than 180 degrees in either direction. ■ ■ NRG 26-61 - Installation & Operating Manual - 819874-00...
Cover screws M4 x 16 mm Operating panel with 4-digit LED display/alarm and status LEDs and rotary knob, see page 47 M12 CAN bus socket, 5-pole, A-coded M12 CAN bus connector, 5-pole, A-coded NRG 26-61 - Installation & Operating Manual - 819874-00...
- 0 V 120 Ω + 24 V CH = CAN High 24V DC CL = CAN Low Ω S = shield – 100 - 240 V AC Terminating Fig. 17 resistor NRG 26-61 - Installation & Operating Manual - 819874-00...
Fig. 18 diagram. Connector Coupling Fig. 18 Shield (screen) + 24 V Power supply − 0 V Power supply CAN High data line CAN Low data line NRG 26-61 - Installation & Operating Manual - 819874-00...
First, set the “AL.Lo” and “AL.Hi” alarm limits to suitable values for your specific plant,see page 42. Measuring range calibration and the setting of alarm limits are mutually independent. NRG 26-61 - Installation & Operating Manual - 819874-00...
Page 39
Save your set value by pressing the rotary knob for approx. 1 second. The message “donE” is shown and the parameter appears on the display once more. NRG 26-61 - Installation & Operating Manual - 819874-00...
(ConP = oFF) Notes on changing communication parameters “bd.rt, Id.Lo; Id.Hi or GrP” All CAN bus equipment from GESTRA AG has default ex works parameter settings, which enable a standard system to be brought into operation without making any changes.
Press and hold the rotary knob until the current limiter ID flashes on the display. Set the desired ID (off/0001 to 0008). off = the NRG 26-61 level electrode has no effect on the URS 60 / URS 61 safety control unit. Save your setting by pressing the rotary knob for approx. 1 second.
Always check the switchpoint when bringing into service, after changing a limit, and each time the NRG 26-61 level electrode is changed, and do this at the plant’s operating point. Setting the “AL.Hi” (high-level alarm = HW) limit Pay attention to the setting instructions on page 39 and proceed as follows: Select the parameter “AL.Hi”.
Press and hold the rotary knob until the value (e.g. 0025) appears. The last digit flashes. Set the desired reading > 25 % to match the set level. Save your setting by pressing the rotary knob for approx. 1 second. NRG 26-61 - Installation & Operating Manual - 819874-00...
Press and hold the rotary knob until the current time constant flashes on the display. Set the desired time constant (1 to 30 seconds). Save your setting by pressing the rotary knob for approx. 1 second. NRG 26-61 - Installation & Operating Manual - 819874-00...
Press and hold the rotary knob until the current status flashes on the display. Set the required status (off / on). ConP = on: This enables the higher-resolution NRG 26-61 readings to be displayed on the URB 2 operating terminal. (by converting from 16 bit to 10 bit) ConP = oFF: 16-bit resolution of the NRG 26-61 readings.
Never start up any plant without first checking that switchpoints are correct. ■ ■ The NRG 26-61 level electrode may only be repaired by the manufacturer, GESTRA AG. ■ ■ Only replace a faulty device with an identical device from GESTRA AG.
Priority 1 = fault indications as per fault code table, see page 52 ff. Priority 2 = low-level (LW) alarm Priority 3 = high-level (HW) alarm Priority of fault code display Higher priority fault codes overwrite lower ones on the display! NRG 26-61 - Installation & Operating Manual - 819874-00...
Page 48
Displays the current level as % of the calibrated The level electrode measuring range. is immersed within the set LED 2: measuring range Operating LED lights up green See the following pages for more information and tables. NRG 26-61 - Installation & Operating Manual - 819874-00...
Page 49
When the alarm or fault is cancelled the display also goes blank, and the URS 60 / URS 61 safety control unit closes the safety contacts and deactivates the relevant signal outputs once more. NRG 26-61 - Installation & Operating Manual - 819874-00...
Page 50
If the level electrode does not behave as described above, it may be faulty. ■ ■ Perform failure analysis. ■ ■ The NRG 26-61 level electrode may only be repaired by the manufacturer, GESTRA AG. ■ ■ Only replace faulty equipment with identical equipment from GESTRA AG. ■ ■...
Switch off the voltage to the plant and secure so that it cannot be switched back on. ■ ■ Check that the plant is not carrying live voltage before commencing work. ■ ■ NRG 26-61 - Installation & Operating Manual - 819874-00...
Replace the level electrode capacitance (1nF || 47pF) Channel 1 reading with disabled E.010 PWMTSTCh1Err Replace the level electrode measurement signal Channel 2 reading with disabled E.011 PWMTSTCh2Err Replace the level electrode measurement signal NRG 26-61 - Installation & Operating Manual - 819874-00...
Page 53
Virtually all of the aforementioned fault codes can be caused by EMC interference. This is less likely to be the case in the event of permanent faults, but should be considered for sporadic fault messages. NRG 26-61 - Installation & Operating Manual - 819874-00...
The measuring range is incorrectly set. ■ ■ Inspect the electrode and protective tube for soiling and ■ ■ The electrode or protective tube is soiled. ■ ■ clean if necessary. NRG 26-61 - Installation & Operating Manual - 819874-00...
Page 55
Reduce the ambient temperature around the terminal ■ ■ If the temperature rises above 75 °, the fault box, e.g. by cooling. code E.027 (Overtemp Err) appears and a plant shutoff occurs. NRG 26-61 - Installation & Operating Manual - 819874-00...
Check the limiter functions by bringing the level below the set low water (LW) and above the set high ■ ■ water (HW) limits. In this case, the equipment must behave as if there were an alarm. Check the switchpoint when bringing into service and every time the NRG 26-61 level electrode ■ ■ is replaced.
Unplug the connections of the CAN bus control lines and plug them into one another. Next, remove the level electrode. An alarm is triggered when the CAN bus line is interrupted. NRG 26-61 - Installation & Operating Manual - 819874-00...
The term media can refer to solid, liquid or gaseous substances or mixtures, as well as radiation. GESTRA AG can accept returned products only if accompanied by a completed and signed return note and also a completed and signed declaration of decontamination.
EU Declaration of Conformity We hereby declare that the NRG 26-61 level electrode conforms to the following European Directives: Directive 2014/68/EU EU Pressure Equipment Directive ■ ■ Directive 2014/35/EU Low Voltage Directive ■ ■ Directive 2014/30/EU EMC Directive ■ ■...
Page 60
You can find our authorised agents around the world at: www.gestra.com GESTRA AG Münchener Strasse 77 28215 Bremen Germany Phone +49 421 3503-0 +49 421 3503-393 e-mail info@de.gestra.com www.gestra.com 819874-00/08-2019cm (808994-00) · GESTRA AG · Bremen · Printed in Germany...