Vers. 1.6 EN Tel +43 (0)2862 53635 mail@ta.co.at Supplementary instructions for UVR61-3 Building drying with ventilator A special application of the universal controller is the energy-saving and cost-effective drying of basements and other building parts with fan control. The special functionality (measurement of the absolute humidity) of the sensor RFS-DL enables this simple drying out of buildings in connection with the universal controller.
Planning principles Blow direction of the fan always from the outside to the inside! If the fan blows from the inside to the outside, there is a danger of warm and thus humid air following from adjacent building parts thus increasing the problem! A supply air fan is usually sufficient! The “exhaust air”...
The value is saved pressing the arrow key in upward direction. View of the display after the first start of controller UVR61-3 Display after switching on The sensor values initially show 999°C because no sensors are defined as yet.
Page 4
Allocation of the external sensors to sensor values in the menu SENSOR Value blinks Sample setting for the applications 1-4 Access to menu ENTER/Par and definition of the parameters Controller Program number Linking of output version First parameter Second parameter value max1 ...
Page 5
The humidity should be lowered in a humid room. As soon as the absolute exterior humidity is lower than the one inside, a fan is switched on. The fan runs if the absolute humidity is lower outside than inside and the optional interval switch ("Timer") is active. Recommended settings for UVR61-3 Menu Menu Code: 32 Code: 64...
Page 6
(protection against too much cooling down in the winter) and the optional interval switch ("timer") is active. Recommended settings for UVR61-3 Menu Menu ENTER Par...
Page 7
(protection against too much cooling down in the winter) and the optional interval switch ("Timer") is active. The fan for “comfort ventilation” runs Daily according to time window Recommended settings for UVR61-3 Menu Menu ENTER Par...
Page 8
T3 and E3 Exterior temperature T4 and E4 Interior room temperature Electrical connection UVR61-3 Output 3 must be made potential-free. For this, the red jumper on the rear of the detacha- ble upper controller part is removed. Meaning of the luminous digits : Fan operation for room drying activated : Fan operation for “comfort ventilation”...
Page 9
(protection against too much cooling down in the winter) and the optional interval switch ("Timer") is active. The fan for “comfort ventilation” runs daily according to time window if the room temperature is high enough. Recommended settings for UVR61-3 Menu ENTER Par Code: 32...
Page 10
Absolute exterior humidity (g/m³, displayed in °C) T3 and E3 Exterior temperature T4 and E4 Interior room temperature Electrical connection UVR61-3 Output 3 must be made potential-free. For this, the red jumper on the rear of the detachable upper controller part is re- moved.
Page 11
("Timer") is active. The fan for “comfort ventilation” runs daily according to the time window regardless of other settings (example: 10:00 to 10:30 a.m.), up to three time windows can be set Recommended settings for UVR61-3 Menu Menu ENTER Par...
Page 12
Relative exterior humidity (%, displayed in °C) T5 and E3 Interior temperature T6 and E4 Exterior temperature Electrical connection UVR61-3 Output 3 must be made potential-free. For this, the red jumper on the rear of the detachable upper controller part is re- moved.