pump has been installed, it must be checked to
ensure proper operation. This check is part of the
start­up process which must be done by the installing
contractor.
IMPORTANT
Drain should have a slope of at least ¼ inch per foot and
should be approved corrosion-resistant pipe. You must
confirm operation of every drain and pump in the system
as part of the commissioning procedure.
Figure 16. Condensate Line

Outdoor Unit Installation

Placement Considerations

Consider the following when positioning the unit:
In coastal areas or other places with salty atmosphere
of sulfate gas, corrosion may shorten the life of the
unit. In coastal areas, the coil should be cleaned with
potable water several times per year to avoid corro­
sive buildup (salt).
Some localities are adopting sound ordinances based
on the unit's sound level registered from the adja­
cent property, not from the property where the unit is
installed. Install the unit as far as possible from the
property line.
When possible, do not install the unit directly outside
a window. Glass has a very high level of sound trans­
mission.
Install unit level.
Ground
Level
Figure 17. Install Unit Level
Choose a place solid enough to bear the weight and
vibration of the unit, where the operation noise will not
be amplified.
CORRECT
Make sure there are no
kinks or dent in drain
hose to ensure proper
drainage.
Building Structure
Choose a location where the hot air discharged from
the unit or the operation noise will not be a nuisance
to neighbors.
Avoid installing the outdoor unit near a bedroom or
other places where noise may cause a problem.
There must be sufficient space to carry the unit into
and out of the site.
There must be unobstructed air flow around the air
inlet and the air outlet.
The unit must not be installed in areas where a flam­
mable gas leak may occur.
Install the outdoor unit a minimum of 3 feet (1m) away
from any antenna, power cord (line), radio, telephone,
security system, or intercom. Electrical interference
and radio frequencies from any of these sources may
affect operation.
Since water drains from the outdoor unit during vari­
ous stages of operation, do not place anything which
may be damaged by moisture under the unit.

Direct Sunlight and Rain Protection

If the outdoor unit is subjected to prolong exposure to
direct sunlight with temperatures over 100°F (38°C) a
canopy is recommended as illustrated in "Figure 18.
Outdoor Unit on Pedestal and Protective Canopy"or
"Figure 19. Dog House­Style Shelter" on page 9.
Protective canopy
305 mm
Air Inlet
Air Outlet
Pedestal
(stand)
Side View
Figure 18. Outdoor Unit on Pedestal and Protective
24 in
610 mm
12 in
305 mm
NOTE - Minimum clearances shown.
Figure 19. Dog House-Style Shelter
9
Protective canopy
24 in
610 mm
12 in
Front View
Canopy
24 in
610 mm
Pedestal
(stand)
12 in
305 mm