1. WELCOME
Thank you for choosing this quality Ektor product.
This manual is intended to help you install this
product in a way that ensures the safety of yourself
and others. Whilst this Ektor product is designed
to be installed easily, we highly recommend you
take the time to read this manual thoroughly before
commencing installation. When installed correctly
and serviced regularly, this product will provide
hassle free operation for many years.
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 1808 and is the answer not in the manual?

Questions and answers

Summary of Contents for ektor 1808

  • Page 1: Table Of Contents

    Compliance standards Technical support and troubleshooting 1. WELCOME Thank you for choosing this quality Ektor product. This manual is intended to help you install this product in a way that ensures the safety of yourself and others. Whilst this Ektor product is designed...
  • Page 2: Overview

    CIRCULAR PEARL EMERGENCY INSTALLATION INSTRUCTIONS 2. OVERVIEW Ektor Generation III platform introduces you to a new era of emergency lighting control. With years in the making, the third generation platform builds on the Ektor product ranges’ increasing quality, reliability and performance.
  • Page 3: Installation

    CIRCULAR PEARL EMERGENCY INSTALLATION INSTRUCTIONS 4. INSTALLATION The Ektor Weatherproof Circular can be installed by mounting the product to the ceiling. To install the Circular please follow the steps listed below: Remove the product from the box and inspect it for any damage. If you believe the product to be damaged or otherwise unsound, DO NOT install the product.
  • Page 4: Mounting

    CIRCULAR PEARL EMERGENCY INSTALLATION INSTRUCTIONS 5. MOUNTING CEILING MOUNT Before you start mounting your Circular, the access point for the terminal block wiring must be chosen. There are three different access points(A, B, C), option C is specificaly for conduit entry. Drill a hole through the Circular base in the desired position.
  • Page 5: Terminal Block Wiring

    CIRCULAR PEARL EMERGENCY INSTALLATION INSTRUCTIONS 6. TERMINAL BLOCK WIRING OPTIONS The wiring for Circular differs between models and accessories installed. Wiring schematics for the terminal blocks used with the Circulars in the following sections. EV-PEARL & EV-PEARL-PRO Switched Standard External sensor Figure 3: Mains operation only EV-PEARL-EM &...
  • Page 6: Self-Test Wiring / Central Battery System

    CIRCULAR PEARL EMERGENCY INSTALLATION INSTRUCTIONS EV-PEARL-S & EV-PEAR-PRO-S Standard Switched Internal Internal sensor sensor Sensor out Sensor out Optional Optional Figure 5: Microwave models EV-PEARL-EM-S & EV-PEAR-EM-PRO-S Standard DALI emergency Combined input Internal Internal sensor sensor Sensor out Sensor out Optional Optional Figure 6: Emergency microwave models...
  • Page 7: Using The Inverter With A Switch

    CIRCULAR PEARL EMERGENCY INSTALLATION INSTRUCTIONS 9. USING THE INVERTER WITH A SWITCH A mains rated switch can be wired with this product to turn ON/OFF the non-emergency light in normal use. This does not affect operation in emergency mode. See external switch wiring diagram in section 6 (page 5). NOTE: Emergency models with microwave sensors do not support an external switch.
  • Page 8: Battery Life

    AS/NZS 2293 or an equivalent standard can have a positive effect on the battery performance as long as 12 discharge cycles per year is not exceeded. 15. POWER AND BATTERY CHARGE The Ektor Generation III platform uses smart battery charging technology which reduces power consumption and increases battery life. Max charge voltage...
  • Page 9: Wireless Daughterboard

    Figure 10: Maintained/non-maintained jumper 18. DISCHARGE RATING SELECTION The inverter supports a number of discharge ratings which can be selected by the user. The output from the LED scale based on the discharge rating (see ektor.com.au for output information). HOURS Remove expansion cover...
  • Page 10: Onboard Microwave Sensor Settings

    CIRCULAR PEARL EMERGENCY INSTALLATION INSTRUCTIONS 19. ONBOARD MICROWAVE SENSOR SETTINGS DETECTION AREA Detection area can be reduced by selecting the combination on the DIP switches to fit precisely for each specific application. RANGE 100% (default) Figure 12: Microwave sensor HOLD TIME The time period you would like to keep the lamp on 100% after the person has left the detection area.
  • Page 11: Accessories List

    EV-3000mAh-64V-LiFePO4 1303 Wireless Daughterboard EV-DAUGHTER-DAUG 6118 Easy commissioning module - DALI EV-ECM-DALI 5304 Easy commissioning module - EKTOR EV-ECM-EKTOR 5305 Microwave Sensor EV-MICROWAVE-SENS 6124 21. SELF TEST INDICATOR LEDS The table below shows the operation of the Circular status indicators:...
  • Page 12: Self Test/ Commissioning Interval Programming

    CIRCULAR PEARL EMERGENCY INSTALLATION INSTRUCTIONS 22. SELF TEST/ COMMISSIONING INTERVAL PROGRAMMING The self test mode must first be enabled to perform tests by switching the emergency power breaker, or test button in the correct sequence. The test interval is fixed and set to 26 weeks / 182 days. The LEDs indicate the status of the device and which functions are being performed.
  • Page 13: Product Specifications

    IP65 Charger type Smart charge L’ Output 400 W Max. Evolt code Name Max. power Code EV-PEARL-EM-WP Circular Emergency Weatherproof 1808 21 W EV-PEARL-EM-PRO-WP Circular Pro Emergency Weatherproof 1809 29 W EV-PEARL-WP Circular Weatherproof 1810 18 W EV-PEARL-PRO-WP Circular Pro Weatherproof...
  • Page 14: Australian Emergency Classification

    If you choose to expose the Ektor emergency products to such harsh operating conditions, Evolt may not honour any warranty on the life of the batteries or the dish. This Ektor emergency product is designed to undergo regular discharge tests but it is recommended that the intervals between consecutive tests are not less than two weeks.
  • Page 15: Testing Precautions

    27. TESTING PRECAUTIONS When the Ektor emergency product is permanently connected to the mains supply you will need to allow 24 hours to charge its battery. Once the battery is fully charged you will need to conduct a manual discharge test as per the requirements of AS/NZS 2293 or other relevant standards.
  • Page 16: Warranty Information

    Australian Competition and Consumer Act and other Australian laws. Ektor products are warranted in Australia for a period of 12 months from the date of delivery of the product, provided that the products are properly stored, installed, used and maintained in accordance with the instructions contained within their manual.
  • Page 17: Compliance Standards

    CIRCULAR PEARL EMERGENCY INSTALLATION INSTRUCTIONS 30. COMPLIANCE STANDARDS STANDARD TITLE Australian/ New Zealand AS/NZS 2293-3:2005+A1:2010 Emergency escape lighting and exit signs for buildings. Part 3: Emergency escape luminaires and exit signs. Standards AS/NZS 60598-2-22:2005 Luminaires Part 2.22: Particular requirements - Luminaires for emergency lighting (IEC 60598-2-22, Ed.
  • Page 18 CIRCULAR PEARL EMERGENCY INSTALLATION INSTRUCTIONS...
  • Page 19 CIRCULAR PEARL EMERGENCY INSTALLATION INSTRUCTIONS...
  • Page 20 Ph: + 612 9502 1161 Fax: + 612 9502 1154 Email: sales@evolt.com.au evolt.com.au Reference: 602887_V2.9...