Install a terminating resistor (Ω120) at the last indoor unit terminals P and Q of the daisy chain.
All shields of shielded cable connect to
18 GA., stranded, 2-conductor, shielded control wire (polarity sensitive).
Typical Wiring Diagram, NEC/CEC and Local Codes apply.
Figure 17. Typical Communication Wiring Diagram (VRF Heat Pump System)
Tightening torque for the terminal screws
Use the correct screwdriver for tightening the terminal
screws.
If the terminal screws are over tightened, screws
might be damaged.
Refer to Table 5 for the tightening torque of the
terminal screws.
IMPORTANT
DO NOT adjust DIP switch settings. Settings may only
be adjusted by a trained technician as part of the com-
missioning procedures.
Outdoor unit
(sub1 unit)
(H1 H2
)
(H1 H2
)
K1
(PQ)
chassis GROUND terminal at Indoor Units.
Outdoor unit
(sub2 unit)
(H1 H2
)
K2
O
A
Outdoor Unit Communication Terminal Block
Table 5. Terminal Screw Tightening Torque
Terminal base of
remote controller/Signal
transmission wire (X2M)
Terminal base of power
supply (X1M)
Grounding terminal (M4)
After wiring, confirm all connections are correct; Then
turn on power supply to the unit.
16
X
Y
P
Q
HA HB 12V COM P
Indoor Unit Communication Terminal Block
Ground cable shield
to Indoor Unit chassis
Tightening torque (lb-ft)
0.58-0.72
0.87-1.06
1.06-1.43
H1 H2
Q