Seal RA Flange Perimeter w/
Foam Gasket Tape
Min. 2"
Front of Cabinet to
Front Drywall
Perimeter
RA Panel Frame
Figure 20
Notes:
The framing should be installed for a min. 1/8" and max. 1" clearance between unit RA flange and RA panel sleeve.
Return air panel should be centered in front of the unit return air opening.
With rear/side risers, allow for min. 6" typical clearance at the rear/side of the units.
Seal RA perimeter with foam gasket tape or foil tape.
Insulate the drywall enclosure with plenum rated acoustical insulation for additional sound attenuation.
31
VSHP CABINET
"S"
Unit RA Flange to RA Panel
(Min. = 1/8"; Max.= 1")
1/2" Unit RA
Flange
2"
Rough-In Width
Perimeter Panel Furring Detail—Typ. 2x2 Framing Plan View
Figure 21
Perimeter Panel — Typ. 2x4 Framing Plan View
Unit Cabinet to Back Wall:
No Risers = Min. 1/2"
W/ Risers = Min. 6" Typ.
Screws x 6
www.omega-heatpump.com
OMEGA-VSHP.F-IOM-1907
Unit Cabinet to Left/Right Wall:
W/ Nom. 2"x2" Studs = Min. 3"
Nom. 2x2 Studs Shown
(1-1/2" x 1-1/2")
Typ. 1/2" Drywall
Use Foam Gasket
Tape