Omega DRG-AR-DC Instruction Sheet

Dc input, field configurable limit alarm

Advertisement

Quick Links

Inputs
>50mV/5mA: 0.1% of full scale
Voltage Input
<50mV/5mA: 0.2% of full scale
Range: 10mV to +200V
Stability
Impedance: >100KΩ
Temperature: +0.05% of full
Overvoltage: 200V rms, max.
scale/°C, max.
Current Input
Excitation Voltage
Range: 1mA to +100mA
24VDC, 20mA, maximum
Impedance: 20Ω, typical
Common Mode Rejection
Overcurrent: 170mA rms, max.
DC to 60Hz: 120dB
Overvoltage: 60VDC
Isolation
(protected by self resetting fuse)
1800VDC between contacts, input
Common Mode (Input to Ground):
and power
1800VDC, max.
EMC Compliance (CE Mark)
LED Indicators
Emmissions: EN50081-1
Input Range (Green)
Immunity: EN50082-2
>110% input: 8Hz flash
Safety: EN50178
<0% input: 4Hz flash
Humidity (Non-Condensing)
Setpoint (Red)
Operating: 15 to 95% (@45°C)
Tripped: Solid red
Soak: 90% for 24hours (@65°C)
Safe: Off
Temperature Range
Limit Differentials (Deadbands)
Operating: 0 to 55°C (32 to 131°F)
>50mV/5mA: 0.25% to 5% of span
Storage: -25 to 70°C (-13 to 158°F)
<50mV/5mA: 1% to 5% of span
Power
Response Time
Consumption: 1.5W typical,
Dynamic Deadband: Relay status
2.5W max.
will change when proper
Supply Range: 9 to 30VDC,
setpoint/process condition exists
inverter isolated
for 100msec.
In-rush Current: 300mA, max.
Normal Mode (analog filtering):
Relay Contacts
<250mSec, (10-90%)
2 SPDT (2 form C) Relays
Setpoints
1 Relay per setpoint
Effectivity: Setpoints are adjustable
Current Rating (resistive)
over 100% of the selected input
span.
Repeatability (constant temp.):
OMEGA ENGINEERING, INC. warrants this unit to be free of manufacturing defects for the life of the product.
If the unit should malfunction, it must be returned to the factory for evaluation. OMEGA's Customer Service Department will issue an Authorized Return
OMEGAnet
SM
On-Line Service
Internet e-mail
(AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is found to be defective it will be repaired or replaced at
info@omega.com
http://www.omega.com
no charge. OMEGA's WARRANTY does not apply to defects resulting from any action of the purchaser, including but not limited to mishandling, improper
interfacing, operation outside of design limits, improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having
been tampered with or shows evidence of being damaged as a result of excessive corrosion; or current, heat, moisture or vibration; improper specifica-
Servicing North America:
tion; misapplication; misuse or other operating conditions outside of OMEGA's control. Components which wear are not warranted, including but not
USA:
One Omega Drive, Box 4047
limited to contact points, fuses, and triacs.
ISO 9001 Certified
Stamford, CT 06907-0047
Telephone: (203) 359-1660
Fax: (203) 359-7700
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes responsibility
e-mail:info@omega.com
for any omissions or errors nor assumes liability for any damages that result from the use of its products in accordance with
information provided by OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by it will be as
Canada:
976 Bergar
specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER,
Laval (Quebec) H7L 5A1
Telephone: (514) 856-6928
EXPRESSED OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MER-
Fax: (514) 856-6886
CHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The
e-mail: canada@omega.com
remedies of purchaser set forth herein are exclusive and the total liability of OMEGA with respect to this order, whether
For immediate technical sevice or application assistance:
based
on
the
component
USA and Canada:
Sales Service: 1-800-826-6342 / 1-800-TC-OMEGA
SM
d a m a g e s .
Customer Service: 1-800-622-2378 / 1-800-622-BEST
SM
SM
Engineering Service: 1-800-872-9436 / 1-800-USA-WHEN
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a "Basic Component" under 10 CFR 21 (NRC), used in
TELEX: 996404 EASYLINK: 62968934 CABLE: OMEGA
or with any nuclear installation or activity; or (2) in medical applications or used on humans. Should any Product(s) be used in or with any nuclear
Mexico and
Tel: (95) 800-TC-OMEGA
SM
installation or activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as set forth in our basic WAR-
Fax: (95) 203-359-7807
RANTY/DISCLAIMER language, and additionally, purchaser will indemnify OMEGA and hold OMEGA harmless from any liability or damage whatsoever
Latin America:
En Espanol: (203) 359-1660 ext. 2203
e-mail: espanol@omega.com
arising out of the use of the Product(s) in such a manner.
Servicing Europe:
Benelux:
Postbus 8034, 1180 LA Amstelveen, The Netherlands
Tel: (31) 20 6418405
Fax: (31) 20 6434643
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER
Toll Free in Benelux: 06 0993344
MUST OBTAIN AN AUTHORIZED RETURN (AR) NUMBER FROM OMEGA'S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING
e-mail: nl@omega.com
DELAYS). The assigned AR number should then be marked on the outside of the return package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in transit.
Czech Republic:
Ostravska 767, 733 01 Karvina
Tel: 42 (69) 6311899
Fax: 42 (69) 6311114
FOR WARRANTY RETURNS, please have the following information
e-mail: czech@omega.com
available BEFORE contacting OMEGA:
1.
P.O. number under which the product was PURCHASED,
France:
9, rue Denis Papin, 78190 Trappes
2.
Model and serial number of the product under warranty, and
Tel:33 0130-621-400
Fax: 33 0130-699-120
3.
Repair instructions and/or specific problems relative to the product
Toll Free in France: 05-4-06342
e-mail: france@omega.com
Germany/Austria:
OMEGA's policy is to make running changes, not model changes, whenever an improvement is possible. This affords our customers the latest in technology and
Daimlerstrasse 26, D-75392 Deckenpfronn, Germany
Tel:49 (07056) 3017
Fax: 49 (07056) 8540
engineering.
Toll Free in Germany: 0130 11 21 66
OMEGA is a registered trademark of OMEGA ENGINEERING, INC.
ã Copyright 1996 OMEGA ENGINEERING, INC. All rights reserved. This documentation may not be copied, photocopied, reproduced, translated, or reduced to any
e-mail: germany@omega.com
electronic medium or machine-readable form, in whole or in part, without prior written consent of OMEGA ENGINEERING, INC.
United Kingdom:
25 Swannington Road,
P.O. Box 7, Omega Drive
ISO 9002 Certified
Broughton Astely, Leicestershire,
Irlam, Manchester,
It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply. OMEGA is constantly pursuing certification of its products to the European
LE9 6TU, England
M44 5EX, England
New Approach Directives. OMEGA will add the CE mark to every appropriate device upon certification.
The information contained in this document is believed to be correct but OMEGA Engineering, Inc. accepts no liability for any errors it contains, and reserves the right to alter
Tel: 44 (1455) 285520
Tel: 44 (161) 777-6611
specifications without notice.
Fax: 44 (1455) 283912
Fax: 44 (161) 777-6622
WARNING: These product are not designed for use in, and should not be used for, patient connected applications.
Toll Free in England: 0800-488-488
e-mail: uk@omega.com
120VAC: 5A
240VAC: 2A
28VDC: 5A
Material: Silver-Cadmium Oxide
5
Electrical Life:10
operations
at rated load
Note: External relay contact
protection is required for use
with inductive loads (see
Figures 2 & 3).
Mechanical Life: 10
7
operations
Wire Terminations
Screw terminations for 12-22 AWG
Agency Approvals
CSA certified per standard C22.2, No.
0-M91
and
142-M198
No.LR42272) UL recognized per stan-
dard per standard UL508 (File
No.E99775). CE conformance per
1
EMC directive 89/336/EEC and Low
Voltage 73/23/EEC (Input<75VDC,
only).
Mounting
32mm and 35mm DIN Rail
PIN CONNECTIONS
11 N.O. Relay B
12 Com. Relay B
13 N.C. Relay B
21 DC Power (+)
22 DC Power (-)
23 No Connection
41 Analog Input (+)
42 Analog Input (-)
43 (+) 24VDC Excitation
WARRANTY/DISCLAIMER
contract,
warranty,
negligence,
indemnification,
strict
liability
or
otherwise,
shall
not
upon
which
liability
is
based.
In
no
event
shall
OMEGA
be
liable
for
consequential,
RETURN REQUEST/ INQUIRIES
FOR NON-WARRANTY REPAIRS, consult OMEGA for current repair
charges. Have the following information available BEFORE contacting OMEGA:
1.
P.O. number to cover the COST of the repair,
2.
Model and serial number of product, and
3.
Repair instructions and/or specific problems relative to the product.
DRG-AR-DC
DC Input, Field Configurable Limit Alarm
Instruction Sheet M2399/0796
DESCRIPTION
The DRG-AR-DC is a DIN rail mount,
DC voltage or current input limit alarm
(File
with dual setpoints and two contact
closure outputs. The field configurable
input and alarm functions offer flexible
setpoint capability. Input voltage spans
from 10mV to 200V and input current
spans from 1mA to 100mA can be field
configured. Bipolar inputs are also
accepted.
The DRG-AR-DC is configurable as a
single or dual setpoint alarm, with HI or
LO trips and failsafe or non-failsafe
operation. Also included are adjust-
able deadbands (0.25 to 5% of full
scale input) for each setpoint, a 24VDC
voltage source (isolated from line
power) for transducer excitation, and
a flexible DC power supply which ac-
cepts any voltage between 9 and
30VDC.
DIAGNOSTIC LEDS
The DRG-AR-DC is equipped with
three front panel LEDs. The green
LED is a dual function LED labeled
INPUT. This LED indicates line power
and input signal status. Active DC
power is indicated by an illuminated
exceed
the
purchase
price
of
LED. If this LED is off, check DC
incidental
or
special
power and wiring connection. If the
input signal is more than 110% of the
full scale range, the LED will flash at 8
Hz. Below 0%, the flash rate is 4 Hz.
Two red LEDs indicate the relay state
for each setpoint. An illuminated red
LED indicates the tripped condition.
OUTPUT
The DRG-AR-DC is equipped with two
SPDT (form C) relays, rated at 120VAC
or 28VDC at 5 amperes. Each of these
relays is independently controlled by
the field configurable setpoint and
deadband.
721−0607−00Β
11/97
OPERATION
CONFIGURATION
The field configurable DRG-AR-DC
Unless otherwise specified, the
factory presets the Model
limit alarm setpoints can be configured
for HI or LO, failsafe or non-failsafe
DRG-AR-DC as follows:
operation. Each of the setpoints has
Input:
a respective HI or LO deadband. In a
Range:
tripped condition, the setpoint is ex-
Output:
ceeded and the appropriate red LED
Trip:
will illuminate. The trip will reset only
Failsafe:
when the process falls below the HI
Deadband: A, B: 0.25%
deadband or rises above the low
The DC power input accepts any DC
deadband (see Figure 1). For proper
source between 9 and 30V, typically a
deadband operation, the HI setpoint
12V or 24VDC source is used.
must always be set above the LO
setpoint. In failsafe operation, the
For other I/O ranges, refer to Table 1
relay is energized when the process is
and Figure 4. Reconfigure switche
below the HI setpoint or above the LO
SW1 for the desired input type, range
setpoint (opposite for non-failsafe). In
and function.
the failsafe mode, a power failure
results in an alarm state output.
WARNING: Do not attempt to
change any switch settings with power
Illustrating LO Setpoint
Illustrating HI Setpoint
applied. Severe damage will result!
Setpoint
100
Relay returns to its
untripped condition
1. With DC power off, set positions 9
Relay Trips
(LED Off)
(LED Red)
and 10 of switch "SW1" for current or
voltage.
} 10% Deadband
50
} 10% Deadband
2. Set position 1 through position 4 of
Relay Trips
(LED Red)
input range switch "SW1" for the de-
Relay returns to its
untripped condition
sired input range (see Table 1).
(LED off)
Time
3. Set position 5 of input range switch
Figure 1: Limit alarm operation
"SW1" to ON for unipolar (e.g. zero
and effect of deadband(s).
based, 0-20mA) range or OFF for
DYNAMIC DEADBAND
bipolar (e.g. -100% offset,
LSI circuitry in the DRG-AR-DC pre-
-20 to 20mA) range (see Figure 4).
vents false trips by repeatedly sam-
4. Set position 6 and 7 of input
pling the input. The input must remain
range switch "SW1" to ON for a HI trip
beyond the setpoint for 100 millisec-
setpoint or OFF for a LO trip setpoint
onds, uninterrupted, to qualify as a
(see Figure 4).
valid trip condition. Likewise, the input
must fall outside the deadband and
5. Set position 8 of input range
remain there for 100 milliseconds to
switch "SW1" to ON for non-failsafe
return the alarm to an untripped con-
operation or OFF for failsafe
dition. This effectively results in a
operation (e.g. alarm trips upon
"dynamic deadband" —based on
power failure).
time— in addition to the normal
deadband.
Current
0-20mA
Dual, SPDT
A:HI, B:LO
No

Advertisement

loading

Summary of Contents for Omega DRG-AR-DC

  • Page 1 New Approach Directives. OMEGA will add the CE mark to every appropriate device upon certification. deadband. The information contained in this document is believed to be correct but OMEGA Engineering, Inc. accepts no liability for any errors it contains, and reserves the right to alter Tel: 44 (1455) 285520 Tel: 44 (161) 777-6611 specifications without notice.
  • Page 2 Readjust deadband to 5% (fully clock- wise). Set voltage/current input signal to desired deadband position. Slowly adjust deadband until relay untrips. 47 ohm 0.1uF 1/2W Film Figure 3: AC Inductive Loads Figure 7: Terminal Wiring Diagram for DRG-AR-DC Figure 8: Mechanical Dimensions for DRG-AR-DC...