Wiring; Connecting Wiring To Conduit Cover Actuators - Honeywell ML6161 Series Product Data

Non-spring return direct coupled actuators
Table of Contents

Advertisement

35 AND 70 LB-IN. NON-SPRING RETURN DIRECT COUPLED ACTUATORS
IMPORTANT
Run an entire check of the operation after completing
this procedure.
THIS SETSCREW
CORRESPONDS WITH
CLOSING IN THE
CW DIRECTION
Fig. 9. Setscrew location for ML6161 and ML6174.

Wiring

CAUTION
Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect all power supplies before installation.
Actuators with auxiliary switches can have more than
one disconnect.
All wiring must comply with local electrical codes, ordinances
and regulations. Voltage and frequency of the transformer
used with the actuator must correspond with the
characteristics of both the power supply and the actuator.
Screw terminals are provided for easy hookup. See Fig. 11
through 14 for typical wiring hookups.
Connecting Wiring to Conduit Cover Actuators (Fig.
10)
1. Remove the cover from the actuator by lifting the top
and pivoting the cover to the rear of the actuator.
2. Remove the conduit knockouts with a flat-bladed screw-
driver. Discard the knockouts.
3. Install the conduit connector.
4. Run the connecting wire through the conduit connector,
strip the wire ends (if necessary) and connect to the
CW, COM and CCW terminals using Fig. 11 through 14,
Fig. 16 through 20, or the control manufacturer
instructions.
5. Apply power to the actuator.
6. After operational checkout, replace the cover by
reversing the procedure outlined in step 1.
63-2209—8
THIS SETSCREW
CORRESPONDS WITH
CLOSING IN THE
CCW DIRECTION
M10247
8
Fig. 10. Conduit cover for ML6161C,D
and ML6174C,D DCA.
EXTERNAL
SWITCH
1
T87F
L1
W
(HOT)
L2
R
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2
AUXILIARY SWITCHES ARE REQUIRED TO TURN OFF THE MOTOR
AT EACH END OF THE STROKE.
Fig. 11. ML6161 or ML6174 used with T87F in
heating-only or cooling-only application.
NOTE: See Fig. 12 for the 201052B Auxiliary Switch wiring.
L1
(HOT)
SPDT
L2
CONTROL
1
ON/OFF
CONTROL
4
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
SET SWITCH TO CLOSE WHEN STROKE REACHES FULL CW POSITION.
2
3
SET SWITCH TO CLOSE WHEN STROKE REACHES FULL CCW POSITION.
4
ON-OFF CONTROL REQUIRES AN R8222 SPDT RELAY IN PLACE OF THE
SPDT CONTROL.
Fig. 12. 201052B Auxiliary Switch wiring.
COVER
CONDUIT
KNOCKOUTS
M10075
2
ML6161, ML6174
R8222
RED
BLUE CW
WHITE CCW
Y
ML6161, ML6174
201052B
RED
COM
2
BLUE CW
WHITE CCW
3
COM
M18019
M17350