BAPI -Stat 4M Installation & Operating Instructions Manual

Temperature sensor, w/display, button setpoint, fan or system mode control

Advertisement

Quick Links

25188_ins_BS4M
Product Identification and Overview
The BAPI-Stat 4M room temperature sensor
features a large format LCD and pushbutton
setpoint adjustment. Additonal options include
pushbutton override, fan speed and mode
adjustments.
The setpoint is available as a resistance or
voltage output. The override is a momentary
closure signal that can be configured in parallel
with the sensor or setpoint, or as a separate
momentary or latching contact output. A 3.5mm
(1/8"), RJ11 or RJ22 communication jack can
also be mounted in the unit's base to provide
direct access to the network.
Mounting
JUNCTION BOX
1. Pull the wire through the wall and out of the junction box, leaving about 6 inches free.
2. Pull the wire through the hole in the base plate.
3. Secure the base to the box using the #6-32 x 1/2 inch mounting screw provided.
4. Terminate the unit according to the guidelines in the Termination section.
5. Attach Cover by latching it to the top of the base, rotating the cover down
and snapping it into place.
6. Secure the cover by backing out the lock-down screws using a 1/16" Allen
wrench until they are flush with the bottom of the cover.
DRYWALL MOUNTING
1. Place the base plate against the wall where you want to mount the sensor.
2. Using a pencil, mark out the two mounting holes and the area where the
wires will come through the wall.
3. Drill two 3/16" holes in the center of each marked mounting hole. Insert a
drywall anchor into each hole.
4. Drill one 1/2" hole in the middle of the marked wiring area.
5. Pull the wire through the wall and out the 1/2" hole, leaving about 6" free.
6. Pull the wire through the hole in the base plate.
7. Secure the base to the drywall anchors using the #6 x 1 inch mounting screws provided.
8. Terminate the unit according to the guidelines in the Termination section.
9. Attach Cover by latching it to the top of the base, rotating the cover down and snapping it into place. Secure the cover
by backing out the lock-down screws using a 1/16" Allen wrench until they are flush with the bottom of the cover.
NOTE: In a wall-mount application, the mixing of room air and air from within the wall cavity can lead to erroneous
readings, condensation, and premature failure of the sensor. To prevent this condition, plug the conduit hole with
insulation in the junction box.
BAPI-Stat 4 Sensor, w/Display, Button Setpoint, Fan or System Mode Control
Fig. 1: BAPI-Stat 4M
with optional Setpoint,
Override, Fan and Mode
Control.
Specifications subject to change without notice.
BA/BS4M Temperature Sensor
Installation & Operating Instructions
Note: BAPI-Stat 4M shown with
five buttons. Two, three or five
buttons may be present. See "Front
Panel & Control" section.
Fig. 5: Mounting hardware is provided
for both J-Box and drywall installation
rev. 01/18/16
Fig. 2: 2 Button Unit
Fig. 3: 3 Button Unit
Fig. 4: 5 Button Unit
(J-Box installation shown)
1 of 8

Advertisement

Table of Contents
loading

Summary of Contents for BAPI BAPI-Stat 4M

  • Page 1 BAPI-Stat 4 Sensor, w/Display, Button Setpoint, Fan or System Mode Control BA/BS4M Temperature Sensor Installation & Operating Instructions 25188_ins_BS4M rev. 01/18/16 Product Identification and Overview The BAPI-Stat 4M room temperature sensor features a large format LCD and pushbutton setpoint adjustment. Additonal options include pushbutton override, fan speed and mode adjustments.
  • Page 2 All wiring must comply with the National Electric Code (NEC) and local codes. Do NOT run this device’s wiring in the same conduit as AC power wiring. BAPI’s tests show fluctuating and inaccurate signals are possible when AC power wiring is in the same conduit as the signal lines.
  • Page 3 BAPI-Stat 4 Sensor, w/Display, Button Setpoint, Fan or System Mode Control BA/BS4M Temperature Sensor Installation & Operating Instructions 25188_ins_BS4M rev. 01/18/16 Optional Communication Jack Wiring C35L Comm. Jack Wiring Fig. 8: C35L Fig. 7: Location WIRE COLOR Comm. Jack Back Plate (3.5mm plug...
  • Page 4: Numerical Display

    Separate Shorting Contact Output, -L# Option = Override as a Latching Switch, See “Latching Override Operation” on pg. 5.) If the occupied input (EXT OVR) terminal is grounded, then the BAPI-Man will stay filled in, indicating an occupied state. If the input is open, then the BAPI-Man will revert to hollow, indicating unoccupied (or the icon will disappear completely if there has never been a ground on the EXT OVR terminal).
  • Page 5: Entering Program Mode And Making Changes

    BAPI-Stat 4 Sensor, w/Display, Button Setpoint, Fan or System Mode Control BA/BS4M Temperature Sensor Installation & Operating Instructions 25188_ins_BS4M rev. 01/18/16 Optional Technician Adjustments (The sensor set-up is factory set per your order. Set-up adjustments are not required) The unit is shipped ready to install per the order and does not requires any special setup or programming. The following Setup or Program Menu Changes are available if the installer decides to change the factory settings.
  • Page 6 Override button is pushed. On Options 1, 3, 5 & 7, the BAPI-Man Icon is filled or solid for 3 to 5 seconds after the Override button is pushed, but it will only remain solid or filled when there is a ground signal to the EXT OVR terminal of the unit.
  • Page 7: General Diagnostics

    BAPI-MAN ICON: The BAPI-Man Icon shows the status of the room – Solid for Occupied, Hollow for “Unoccupied” (Fig. 11). The unit must receive a confirmation (ground) signal on the “EXT OVR” terminal for the BAPI-Man to remain visible on the screen.
  • Page 8: Specifications

    BAPI-Stat 4 Sensor, w/Display, Button Setpoint, Fan or System Mode Control BA/BS4M Temperature Sensor Installation & Operating Instructions 25188_ins_BS4M rev. 01/18/16 Specifications Power for 5 VDC Power Units: 0 to 5 VDC Setpoint or Resistive Setpoint ..5V ±1% (5 VDC nominal, Input regulation affects accuracy) Power for 24 VDC Power Units: 0 to 5 VDC Setpoint or Resistive Setpoint ...9 to 40 VDC (24 VDC nominal)

This manual is also suitable for:

Ba/bs4m

Table of Contents