York MM9E Series Installation Manual
York MM9E Series Installation Manual

York MM9E Series Installation Manual

Single stage manufactured housing or modular home gas furnaces
Table of Contents

Advertisement

INSTALLATION MANUAL
SINGLE STAGE
MANUFACTURED HOUSING OR
MODULAR HOME GAS FURNACES
MODELS: MM9E Series - 33" -
(95.0% AFUE Multi-Position)
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
DUCTWORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
FILTERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
GAS PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
ELECTRICAL POWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
VENTING CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
COMBUSTION AIR AND VENT SYSTEM . . . . . . . . . . . . . . . . . . . 17
Duct Attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Attachment to Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Combustible Floor Base Accessory . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Mobile Home Filter Frame Accessories . . . . . . . . . . . . . . . . . . . . . . . 7
Blend Air Installation (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Blend Air Bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Downflow Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Furnace and Coil Attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Dimensions (Upflow Configuration Shown) . . . . . . . . . . . . . . . . . . . . 9
Side Return Cutout Markings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Left Side Supply Gas Pipe Arrangement . . . . . . . . . . . . . . . . . . . . . 10
Upflow/Downflow Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Line Wiring Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Single Stage Heat Thermostat Connections . . . . . . . . . . . . . . . . . . 12
Accessory Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Unit Clearances to Combustibles . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Cabinet and Duct Dimensions - MM9E . . . . . . . . . . . . . . . . . . . . . . . 9
Nominal Manifold Pressure - High Fire . . . . . . . . . . . . . . . . . . . . . . 11
Ratings and Physical/Electrical Data - MM9E . . . . . . . . . . . . . . . . . 12
Maximum Equivalent Pipe Length . . . . . . . . . . . . . . . . . . . . . . . . . . 18
High Altitude Pressure Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Elbow Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Equivalent Length of Fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
These high efficiency, compact units employ induced combustion, reli-
able hot surface ignition, and high heat transfer aluminized tubular heat
exchangers. The units are factory shipped for installation in downflow
applications and may be converted for upflow applications.
Shipped in Downflow Configuration
LIST OF SECTIONS
LIST OF FIGURES
LIST OF TABLES
START-UP AND CHECKS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
SAFETY CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
NORMAL OPERATION AND DIAGNOSTICS . . . . . . . . . . . . . . . . . 30
REPLACEMENT PARTS LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
REPLACEMENT PART CONTACT INFORMATION . . . . . . . . . . . . 32
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
START UP SHEET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Typical Condensate Drain, Vertical Installation . . . . . . . . . . . . . . . . 13
Upflow Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Downflow Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Elbow Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Home Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Termination Configuration - 2 Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Termination Configuration - 2 Pipe Basement . . . . . . . . . . . . . . . . . 21
Downward Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Outside and Ambient Combustion Air . . . . . . . . . . . . . . . . . . . . . . . . 23
Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Reading Gas Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Furnace Control Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Size at Furnace (All Models) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Estimated Free Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Unconfined Space Minimum Area in Square Inch . . . . . . . . . . . . . . 23
Free Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Gas Rate (CU FT/HR) at Full Input . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Inlet Gas Pressure Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Nominal Manifold Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Default Blower Speeds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
These furnaces are designed for residential installation in a basement,
closet, alcove, attic, recreation room, or garage. All units are factory
assembled, wired, and tested to ensure safe, dependable, and eco-
nomical installation and operation.
These units are Category IV listed and may not be common vented with
another gas appliance as allowed by the National Fuel Gas Code.
5715184-BIM-A-0519

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MM9E Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for York MM9E Series

  • Page 1: Table Of Contents

    INSTALLATION MANUAL SINGLE STAGE MANUFACTURED HOUSING OR MODULAR HOME GAS FURNACES MODELS: MM9E Series - 33" - Shipped in Downflow Configuration (95.0% AFUE Multi-Position) LIST OF SECTIONS SAFETY ..........2 START-UP AND CHECKS .
  • Page 2: Safety

    5715184-BIM-A-0519 SECTION I: SAFETY 9. It is permitted to use the furnace for heating of buildings or struc- tures under construction where the application and use must com- This is a safety alert symbol. When you see this symbol on ply with all manufacturer’s installation instructions including: labels or in manuals, be alert to the potential for personal •...
  • Page 3 5715184-BIM-A-0519 • Refer to the unit rating plate for the furnace model number, and The furnace requires OUTDOOR AIR for combustion when the furnace then see the dimensions page of this instruction for return air ple- is located in an area where the furnace is being exposed to the follow- num dimensions in Figures 9 and 10.
  • Page 4: Unit Clearances To Combustibles

    5715184-BIM-A-0519 These instructions cover minimum requirements and conform to exist- 3. Where adequate combustion air will be available (particularly when the appliance is not using outdoor combustion air) ing national standards and safety codes. In some instances these instructions exceed certain local codes and ordinances, especially 4.
  • Page 5: Ductwork

    5715184-BIM-A-0519 SECTION II: DUCTWORK WARNING DUCTWORK GENERAL INFORMATION The duct system must be properly sized to obtain the correct airflow The duct system’s design and installation must: for the furnace size that is being installed. • Handle an air volume appropriate for the served space and within Refer to the furnace rating plate for the correct rise range and static the operating parameters of the furnace specifications.
  • Page 6: Attachment To Structure

    5715184-BIM-A-0519 DUCTWORK INSTALLATION AND SUPPLY PLENUM DOWNFLOW DUCT CONNECTORS CONNECTION - UPFLOW All downflow installations must use a suitable duct connector approved by the furnace manufacturer for use with this furnace. The duct connec- Attach the supply plenum to the furnace outlet. The use of tors are designed to be connected to the rectangular duct under the an approved flexible duct connector is recommended on all floor and sealed.
  • Page 7: Mobile Home Filter Frame Accessories

    5715184-BIM-A-0519 DOWNFLOW RETURN PLENUM CONNECTION BLEND AIR INSTALLATIONS The return air duct and the return air plenum are not required by the fur- Upflow nace manufacturer provided the combustion air and vent system have This bracket is to be used only for Alcove application on the 90% Gas been installed and maintained as a Two Pipe Sealed Combustion Air Furnaces.
  • Page 8: Downflow Venting

    5715184-BIM-A-0519 DOWNFLOW APPLICATION COIL INSTALLATION Furnace is shipped in downflow configuration. It may be necessary to IMPORTANT: On all installations without a coil, a removable rotate the vent blower 180° left so that the vent pipe passes through the access panel is recommended in the outlet duct such that smoke or side of the furnace casing.
  • Page 9: Filters

    5715184-BIM-A-0519 FIGURE 9: Dimensions (Upflow Configuration Shown) Table 2: Cabinet and Duct Dimensions - MM9E Approximate Cabinet Dimensions (Illustrated in Figure 9) Nominal BTUH (kW) Cabinet Operating Weights Input Size CFM (m /min) A (in.) A (cm) B (in.) B (cm) C (in.) C (cm) 60 (17.6)
  • Page 10: Gas Piping

    5715184-BIM-A-0519 SECTION IV: GAS PIPING GAS SAFETY IMPORTANT: Plan your gas supply before determining the correct gas pipe entry. Use 90-degree service elbow(s), or short nipples and conventional 90-degree elbow(s) to enter through the cabinet access holes. FIGURE 12: Left Side Supply Gas Pipe Arrangement FIGURE 11: Gas Valve If local codes allow the use of a flexible gas appliance connection, always use a new listed connector.
  • Page 11: Nominal Manifold Pressure - High Fire

    5715184-BIM-A-0519 GAS ORIFICE CONVERSION FOR PROPANE (LP) 11. Remove the natural gas tag and replace with the propane gas tag supplied in the orifice bag. This furnace is constructed at the factory for natural gas-fired operation, 12. Remove the blue conversion label on the furnace door after the fur- but may be converted to operate on propane (LP) gas by following the nace has been converted.
  • Page 12: Electrical Power

    5715184-BIM-A-0519 SECTION V: ELECTRICAL POWER CAUTION ELECTRICAL POWER CONNECTIONS Use copper conductors only. Field wiring to the unit must be grounded. Electric wires that are field installed shall conform to the temperature limitation for 63°F (35°C) rise wire when installed in accordance with instructions. Refer to Table 5 in these instructions for specific furnace electrical data.
  • Page 13: Condensate Piping And Furnace

    5715184-BIM-A-0519 ACCESSORY CONNECTIONS IMPORTANT: Condensate must be disposed of properly. Follow The furnace control allows power-switching control of various accesso- local plumbing or wastewater codes. The drain line must maintain a ries. See Figure 17 for connection details. 1/4 in. per foot (20 mm/m) downward slope to the drain. IMPORTANT: If an external exhaust vent tee is being installed, then it must have its own condensate trap before it is disposed into an open or vented drain.
  • Page 14 5715184-BIM-A-0519 WARNING CONDENSATE DRAIN TERMINATION A condensate sump pump MUST be used if required by local codes, or Liquid anti-freeze will cause damage to internal plastic parts of this if no indoor floor drain is available. The condensate sump pump must furnace.
  • Page 15: Upflow Configuration

    5715184-BIM-A-0519 FIGURE 19: Upflow Configuration Johnson Controls Ducted Systems...
  • Page 16: Downflow Configuration

    5715184-BIM-A-0519 FIGURE 20: Downflow Configuration Johnson Controls Ducted Systems...
  • Page 17: Combustion Air And Vent System

    5715184-BIM-A-0519 SECTION VII: COMBUSTION AIR AND COMBUSTION AIR/VENT PIPE SIZING VENT SYSTEM The size of pipe required is determined by the furnace model, the total COMBUSTION AIR AND VENT SAFETY length of pipe required, and the number of elbows required. Table 6 lists the maximum equivalent length of pipe allowed for each This Category IV, dual certified direct vent furnace is designed for resi- model of furnace.
  • Page 18: Maximum Equivalent Pipe Length

    5715184-BIM-A-0519 Table 6: Maximum Equivalent Pipe Length Elevation Sea Level–2000 Elevation 6001–7000 Model Input (BTUH) Pipe Size (in.) Max. Equivalent Length (ft) Model Input (BTUH) Pipe Size (in.) Max. Equivalent Length (ft) 60,000 60,000 60,000 60,000 60,000 60,000 80,000 80,000 80,000 80,000 80,000...
  • Page 19: Elbow Dimensions

    5715184-BIM-A-0519 TABLE 10: Combustion Air Intake and Vent Connection Size at Furnace (All Models) FURNACE VENT CONNECTION SIZES Furnace Input Intake Pipe Size 2 in. (5.1 cm) Vent Pipe Size 2 in. (5.1 cm) IMPORTANT: Furnace vent pipe connections are sized for 2 in. (5.1 cm).
  • Page 20: Home Layout

    5715184-BIM-A-0519 VENT CLEARANCES FIGURE 22: Home Layout Direct Vent Terminal Clearances Canadian Installations US Installation A. Clearance above grade, veranda, porch, deck, or 12 in. (30.5 cm) 12 in. (30.5 cm) balcony 12 in. (30.5 cm) for models 100,000 BTUH (30 kW), Two-pipe (direct vent) applications: 12 in.
  • Page 21: Termination Configuration - 2 Pipe

    5715184-BIM-A-0519 VENT SYSTEM This furnace is certified to be installed with one of two possible vent configurations. • Horizontal vent system. This vent system can be installed com- pletely horizontal or combinations of horizontal, vertical, or offset using elbows. • Vertical vent system. This vent system can be installed com- pletely vertical or a combination of horizontal, vertical, or offset using elbows.
  • Page 22: Downward Venting

    5715184-BIM-A-0519 DOWNWARD VENTING In some applications, it may be necessary to run the vent pipe and air intake downwards. If this is to be done, the following rules must be fol- lowed. • A condensate trap hose must be connected to both the air intake pipe and the vent pipe at the lowest part of the horizontal run.
  • Page 23: Outside And Ambient Combustion Air

    5715184-BIM-A-0519 Dampers, Louvers and Grilles (Canada Only) Table 12: Unconfined Space Minimum Area in Square Inch 1. The free area of a supply air opening shall be calculated by sub- Minimum Free Area in Square Feet tracting the blockage area of all fixed louvers grilles or screens from BTUH Input Rating Required for Each Opening the gross area of the opening.
  • Page 24: Attic And Crawl Space Combustion Air Termination

    5715184-BIM-A-0519 Ventilated Combustion Air Ventilated Combustion Air Termination (Modular Home Installations Only) (Modular Home Installations Only) The ventilated attic space or a crawl space from which the combustion Refer to Figure 30 for required attic termination for the combustion air air is taken must comply with the requirements specified in “COMBUS- intake pipe.
  • Page 25: Start-Up And Checks

    5715184-BIM-A-0519 SECTION VIII: START-UP AND CHECKS WARNING The initial start-up of the furnace requires the following additional proce- dures: HOT SURFACE IGNITION SYSTEM Do not attempt to light this furnace by hand (with a match or IMPORTANT: All electrical connections made in the field and in the any other means).
  • Page 26: Gas Rate (Cu Ft/Hr) At Full Input

    5715184-BIM-A-0519 Table 14: Gas Rate (CU FT/HR) at Full Input Size of Test Dial Size of Test Dial Seconds For Seconds For 1 Revolution 1 Revolution 1 Cu Ft 2 Cu Ft 5 Cu Ft 1 Cu Ft 2 Cu Ft 5 Cu Ft 1800 1636...
  • Page 27: Gas Valve

    5715184-BIM-A-0519 VERIFY MANIFOLD GAS PRESSURE AND INPUT Read the manifold gas pressure RATE Connect the positive side of the manometer to the OUT P Tap on the gas valve. Do not connect any tubing to the negative side of the Inlet and manifold gas pressure may be measured by connecting the U manometer, as it references atmospheric pressure.
  • Page 28: Default Blower Speeds

    5715184-BIM-A-0519 AIRFLOW SETTINGS Gas Heating Airflow Default Setting This unit is equipped with a five-speed blower motor. The heating Cooling Airflow Settings blower speed is set at the factory to the default blower speed, which is This unit is equipped with a five-speed blower motor. The required cool- the blower speed that delivers the correct airflow for proper heating ing airflow can be selected by connecting the required motor speed tap operation in most applications.
  • Page 29: Furnace Control Board

    5715184-BIM-A-0519 DIAGNOSTIC ERROR CODE RETRIEVAL BUTTON BLOWER OFF DELAY JUMPER ELECTRONIC AIR CLEANER TERMINAL CONTINUOUS FAN SPEED JUMPER HUMIDIFIER TERMINAL FIGURE 33: Furnace Control Board Table 18: Blower Performance CFM - Any Position (Without Filter) - MM9E Airflow Data (SCFM) Models Speed Ext.
  • Page 30: Safety Controls

    5715184-BIM-A-0519 SECTION IX: SAFETY CONTROLS Intermittent Blower - Cooling CONTROL CIRCUIT FUSE Cooling/heating thermostats have a fan switch that has an ON and AUTO position. In the AUTO position the thermostat circuit is completed A 3-amp fuse is provided on the control circuit board to protect the 24- between terminals R and G when there is a call for cooling.
  • Page 31 5715184-BIM-A-0519 If the main limit switch opens five times within a single call for heat, the WARNING control will also indicate 4 Red Flashes and will enter a one-hour soft lockout. Never bypass any safety control to allow furnace operation. To 5 RED FLASHES: This fault is indicated if the normally closed rollout do so will allow furnace to operate under potentially hazardous switch opens.
  • Page 32: Replacement Parts List

    Click the Brand Links button. b. Click the Customer Service button. • You can contact us by mail. Send a written request to the following address: Johnson Controls Ducted Systems Consumer Relations 5005 York Drive Norman, OK 73069 Johnson Controls Ducted Systems...
  • Page 33: Wiring Diagram

    5715184-BIM-A-0519 SECTION XII: WIRING DIAGRAM Wiring Diagram - 95% Standard ECM M/H Furnace CAUTION PRECAUTION OPEN ALL DISCONNECTS BEFORE OUVREZ LES DISJONCTEURS AVANT SERVICING THIS UNIT DE PROCEDER AVEC LE SERVICE BLU/WHT RED-LOW YEL-MED LO Legend GRY-MED LO COOL SEE NOTE 2 BLU-MED HI DS - Door Switch...
  • Page 34 5715184-BIM-A-0519 NOTES Johnson Controls Ducted Systems...
  • Page 35: Start Up Sheet

    5715184-BIM-A-0519 SECTION XIII: START UP SHEET 33" 95% AFUE ECM Single Stage Gas Furnace Start Up Sheet Proper furnace start up is critical to customer comfort and equipment longevity Start-Up Date Technician Performing Start-Up Installing Contractor Name Owner Information Name Address City State or Province...
  • Page 36 Explain thermostat use and programming (if applicable) to owner Additional Job Detail Subject to change without notice. Published in U.S.A. 5715184-BIM-A-0519 Copyright © 2019 by Johnson Controls. All rights reserved. Supersedes: Nothing York International Corp. 5005 York Drive Norman, OK 73069...

This manual is also suitable for:

M9e080b12Mm9e080c16Mm9e080c20Mm9e060b12Mm9e100c16

Table of Contents