Timer, counter, frequency meter

Advertisement

Quick Links

59
48
48
45
100
10
I
nputs
1500V isolation (only with Vac feed to logic output).
3 inputs for count, reset of Counter or Timer, Up-Down or Start/Stop,
Hold.
Maximum counting frequency with 50% duty cycle:
- type 2 inputs: fmax = 100Hz
- type 1 inputs: fmax = 1KHz
- type 0 inputs: fmax = 5KHz
Input types:
Mechanical contact: voltage-free, configured in opening/closing
Proximity switch: 2/3 wires NPN
Logic: OFF ≤ 1Vdc, 3mA; 10Vdc < ON < 50Vdc
O
utputs
Relays:
With 5A/250Vac contacts at cosj = 1 (3.5 at cosj = 0,4)
Spark suppression on NO contact.
Logic (on request):
23Vdc, Rout = 470Ω (20mA, max. 12V)
p
Ower supply
110/220Vac ±10% - 120/240Vac ±10%
24/48Vac ±10% - 24Vdc ±10% - 50/60Hz; 5VA max.
p
s
Ower supply fOr
ensOr
12Vdc, 30mA
A
C
mbIent
OndItIOns
Working temperature: 0...50°C
Storage temperature: -20...70°C
Relative humidity: 20...85% non-condensing
O
perAtIOn
Timer
The software can be programmed to have the timer count up or down.
If the timer is used, the inputs have the following significance:
IN1: Start/Stop input
IN2: Reset input
IN3: Hold or Up/Down input
Output action after alarm is configurable. (*TN47, TVD1)
80469C_MHW_556_02-2011_ENG
556
TIMER - COUNTER - FREQUENCY METER
1 • INSTALLATION
• Dimensions and cut-out; panel mounting
Panel mounting.
Faceplate dimensions: 48x48mm./1.89"x1.89" (1/16DIN); depth: 100mm/3.94"
Cut-out dimension: 45(+0.6/-0)x45(+0.6/-0)mm/1.77" (+0.02/ -0)x1.77"(+0.02/-0)".
70
To attach the instrument, insert the two brackets in the housings on the top and bottom of the case and
tighten with the screws. To mount two or more instruments in a row or column, use the clips and respect
the following cut-out dimensions:
Row: Base (48 x n) -3, (1.89"x n) -0.11" Height 92 (+0.8/ -0) /3.62" (+0.03/ -0)
Column: Base 45 (+0.6/-0)1.77"(+0.02/-0) Height (96xn)-4/(3.78"xn)0.15"
70
where "n" is the number of instruments.
CE MaRkIng:The instrument conforms to the European Directives 2004/108/CE and 2006/95/CE with
reference to the generic standards: EN 61000-6-2 (immunity in industrial environment) EN 61000-6-3 (emission
in residential environment) EN 61010-1 (safety).
45
MaInTEnanCE: Repairs may be done only by trained and specialized personnel. Cut power to the instru-
ment before accessing internal parts. Do not clean the case with hydrocarbon-based solvents (trichloro-
ethylene, gasoline, etc.). The use of such solvents will compromise the instrument's mechanical reliability.
Use a clean cloth moistened with ethyl alcohol or water to clean external plastic parts.
TEChnICaL sERvICE: GEFRAN has a technical service department. Defects deriving from any use not
conforming to this manual are excluded from the warranty
!
2 • TECHNICAL DATA
For correct installation, follow the instructions and warnings contained in this manual.
Counter
The counter can be configured to count up or down.
A prescale factor (:2, :10, :100, x2) can be inserted on the Clock.
The displayed/set value can be expressed in engineering units.
Conversion (from number of pulses to engineering units) is done by
setting two factors (MUL and DIV), which will be multiplied or divided,
respectively, by the number of pulses actually counted.
The counter inputs perform the following functions:
IN1 : Clock input (fmax. 5KHz)
IN2 : Reset input
IN3 : Hold or Up/Down input
Output action is configurable. (*CN47, CVD)
Frequency meter
The inputs perform the following functions:
IN1 : Clock input
IN2 : Reset input for max. peak or min. peak functions
IN3 : Hold input
In this configuration as well, the display and setting can be expressed
as the value converted into engineering units by means of the MOL and
DIV factors. (*DRM)
(*)Gefran instruments replaced by model described
O
utput funCtIOns
The output performs the following functions:
configuration as timer with countdown and input IN3 with HOLD (a) or
UP/DOWN (b) function.
In all other cases (counter and frequency meter), output functions are
unchanged.
In timer and counter mode, the max. trip delay is 1msec non-repetitive.
w
eIght
240g
1

Advertisement

loading

Summary of Contents for gefran 556

  • Page 1 The use of such solvents will compromise the instrument’s mechanical reliability. Use a clean cloth moistened with ethyl alcohol or water to clean external plastic parts. TEChnICaL sERvICE: GEFRAN has a technical service department. Defects deriving from any use not conforming to this manual are excluded from the warranty For correct installation, follow the instructions and warnings contained in this manual.
  • Page 2: Faceplate Description

    3 • FACEPLATE DESCRIPTION A Display CONTROLS Real value of current time/count/frequency. The real value is the value of the time/ C “FUNCTION” button count active at that time: Time 1 (count 1) or Time 2 (count 2). Symbol of parameter set on display B during Accesses display/setting of Time 2 (count 2) setpoint or hysteresis for type U4 configuration.
  • Page 3: Hardware Configuration

    5 • HARDWARE CONFIGURATION Accessing the boards POWER BOARD To remove the electronic parts from the case, open the extraction clips. Power board To select the supply voltage 110/220V (24/48Vac; 120/240V): 110V (24/120V) - close two jumpers P and remove jumpers S; 220V (48/240V) - close two jumpers S and remove jumpers P;...
  • Page 4: Software Configuration

    (accessible only with jumper S10 closed) Pro/ software protection level 0 - display and change of setpoint with saving of current count in EEPROM at shutdown (556 only) 1 - display of setpoint with saving of current count in EEPROM at shutdown (556 only)
  • Page 5 7 • SOFTWARE CONFIGURATION 0 - Normal frequency value Sc.1/ Select Time 1 scale (for timer only) seconds (0.000-9.999) 1 - Maximum peak value of frequency 0 - seconds (00.00-99.99) 2 - Minimum peak value of frequency 1 - seconds (000.0-999.9) +4 - with settable sampling time 2 - seconds (0000-9999) +8 - with fixed scale...
  • Page 6 8 • DESCRIPTION OF OUTPUT FUNCTIONS out=3 Function U3 - Cyclical with timed reset Function (U3) Cyclical timer with timed reset As opposed to the previous function, the timer reloads the preset value (S.P.1) when time 2 (S.P.2) has elapsed, during which the output remained active.
  • Page 7: Power Supply

    Resistors must be at least 2W); fit a 1N4007 diode in parallel with the coil of inductive loads that operate in DC. GEFRAN spa will not be held liable for any injury to persons and/or damage to property deriving from tampering, from any incorrect or errone- ous use, or from any use not conforming to the device specifications.