Parameter: A-DIAL DL
This parameter sets the auto-dialer activation delay to avoid false alarms. This delay is added to the set point delay
(SP DLY) time.
The range is from zero (0) to 3600 seconds. The default is ten seconds (10s).
Parameter: BATTERY OPT
This parameter controls the optional battery backup options.
OFF:
No battery option (deactivates all battery alarms).
NiMH: Internal short-term battery option is installed (2, 8.4V, NiMH internal batteries)
BBU
BBU1000 is the power source, see the
Parameter: BATTERY ACK
The parameter enables (ON) or disables (OFF) battery faults activating the horn/beeper alarms.
The alarms are "BATTERY MISSING," "BATTERY SHORT," and BATTERY LOW."
Parameter: AC LOSS RLY
Selects the AC loss relay output that is activated when the monitor is running on batteries (DC).
Choices are K1, K2, K3, K4, K5, K6, and OFF. The relay can be shared with any other alarm.
The default relay is OFF.
Parameter: K6 OPER
Selects normally open (N/O) or normally closed (N/C) K6 relay operation.
If N/C, the relay is normally closed when there are no fault conditions.
Parameter: LATCH ACK
If set to ON, the audible alarms (internal beeper and external horn) are not automatically cleared when the alarm
condition no longer exists (e.g., danger or critical alarm).
Press ACK on-screen or temporarily activate IN1 via an external push button to silence the alarm.
Parameter: POx MODE
This parameter sets the analog outputs (POx) signal range.
"0-20mA"
Allows one to use a 500 ohm resistor to produce a 0-10V signal for some data loggers.
"4-20mA"
Standard 4-20mA signal compatible with most if not all site installationsL Default setting.
Parameter: BAUD RATE
This parameter sets the RS-232 and RS-485 baud rate. The serial port is used to communicate with remote devices
and update the installed PS-1000S firmware. There is no RS-485 node addressing at this time, so only one PS-
1000 can connect to an RS-485 connection.
Choices are 1200, 2400, 4800, 9600, 19200, and 38400.
Parameter: CHANGE SETUP PW (password)
Allows one to change the set up password.
Parameter: CHANGE ALARM PW (password)
Allows one to change the alarm password.
CONFIGURATION (continued)
EXTERNAL LONG-TERM BATTERY BACKUP
section of this manual.