The A.C. power should be wired into the GD-1000 (TB5) by a qualified electrician. This is
not covered by Eagle Microsystems, Inc. or its distributors.
The GD-1000 gas sensor can be separated from the GD-1000 meter 1000ft or more if the
appropriate cable is used. The resistance of the cable should be less than 200 ohms total (both
wires).
Mount the GD-1000 meter at eye level. Mount the sensor(s)
12" off the floor. The GD-1000 is provided with 12' of cable each
sensor.
Wire the cable from the GD-1000 to the sensor (see below).
Sensor 1 wiring:
Clear/white connects to TB3-1 (24V SRC)
Black connects to TB3-2 (PV1+)
Sensor 2 wiring:
Clear/white connects to TB3-1 (24V SRC). This is the same as sensor one.
Black connects to TB3-4 (PV2+)
Install the NiMH 9V batteries if supplied.
lithium, carbon-zinc, etc types. Only use the 8.4V NiMH battery type supplied. NiCd types
are not recommended, either.
Select the appropriate supply voltage (115V/230V) by S1 (upper left of PS-1000S-CPU).
A qualified electrician should wire the AC power to the GD-1000, see TB5 above.
The red LED on each sensor box will illuminate if the sensors are wired properly and
when the meter is powered by the mains or battery.
Remove the calibration plug on each sensor and store it in a safe place. One can store it
inside the GD-1000 or sensor enclosure.
After proper installation and a calibration verification, the monitor is ready to operate.
INSTALLATION

QUICK START INSTALLATION

DUAL SENSORS

Do not substitute the battery with alkaline,
(TB3)

SINGLE SENSOR