Wired Controller Placement - LG Multi V Art Cool ARNU093SFA4 Engineering Manual

Wall-mounted indoor unit
Hide thumbs Also See for Multi V Art Cool ARNU093SFA4:
Table of Contents

Advertisement

APPLICATION GUIDELINES
Wiring Guidelines
Figure 54: Simplified View of Indoor Unit Terminal Connections—SF Gallery Frames.
Indoor Unit Terminal Block
L(L1)
N(L2)
3
Power Input
To Outdoor Unit
208-230V /
60 Hz / 1 Phase
Ground
Figure 55: Simplified View of Indoor Unit Terminal Connections—SJ and SK Wall-Mounted Frames.
Indoor Unit Terminal Block
1(L)
2(N)
3(A)
Power Input
208-230V /
To Outdoor Unit
Ground
60 Hz / 1 Phase
Figure 56: Simplified View of Indoor Unit Terminal Connections—SV Wall-Mounted Frames.
Indoor Unit Terminal Block
To Outdoor Unit
L(L1)
N(L2)
3(A)
4(B)
Power Input
208-230V /
60 Hz / 1 Phase

Wired Controller Placement

Gallery and Wall-mounted indoor units can be used with various wired controllers
(optional; sold separately). Wired controllers include a sensor to detect room tem-
perature. To maintain comfort levels in the conditioned space, the wired controller
must be installed in a location away from direct sunlight, high humidity, and where it
could be directly exposed to cold air. Controller must be installed four (4) to five (5)
feet above the floor where its LED display can be read easily, in an area with good
air circulation, and where it can detect an average room temperature.
Do not install the wired controller near or in:
• Drafts or dead spots behind doors and in corners
• Hot or cold air from ducts
• Radiant heat from the sun or appliances
• Concealed pipes and chimneys
• An area where temperatures are uncontrolled, such as an outside wall
122 | GUIDELINES
SODU
IDU
4
B
A
-
SODU
4(B)
B
A
-
SODU
IDU
B
A
A
Ground
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Outdoor Unit Terminal Block
INTERNET
DRY1
DRY2
-
B
A
-
-
Outdoor Unit Terminal Block
IDU
INTERNET
DRY1
DRY2
-
B
A
-
-
Outdoor Unit Terminal Block
INTERNET
DRY1
DRY2
B
B
A
-
-
Figure 57: Proper Location for the Wired Controller.
GND 12V
-
-
GND 12V
-
-
GND
12V
-
-
YES
TEMP
Remote Controlle r
NO
TEMP
Remote Controlle r
4 to 5 feet
above the floor
TEMP
Rem
ot e
Cont
roller
NO
NO