LG Multi V Art Cool ARNU093SFA4 Engineering Manual page 106

Wall-mounted indoor unit
Hide thumbs Also See for Multi V Art Cool ARNU093SFA4:
Table of Contents

Advertisement

STANDARD WALL-MOUNTED
Heating Capacity Tables
ARNU073SJA4
Table 52: ARNU073SJA4 Heating Capacity Table.
Outdoor
Air Temp.
Model No. /
Capacity Index
°F DB
-21.6
-17.1
-12.6
-7
-4
0
5
10
15
ARNU073SJA4/
20
7.5
25
30
35
40
45
47
50
55
60
TC: Total Capacity (MBh).
The System Combination Ratio must be between 50–130%.
Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change
without notice.
Low ambient performance with LGRED° heat technology is included in Multi V 5 Air Source Units produced after February 2019.
106 | STANDARD
Indoor Air Temperature (°F DB)
59
61
64
TC
TC
TC
°F WB
MBh
MBh
MBh
-22.0
4.3
4.3
4.3
-17.5
4.8
4.8
4.8
-13
5.4
5.4
5.4
-7.6
5.5
5.5
5.5
-4.4
5.7
5.7
5.7
-0.4
5.9
5.9
5.9
4.5
6.6
6.6
6.5
9
6.9
6.9
6.9
14
7.3
7.3
7.3
19
7.7
7.7
7.7
23
8.1
8.1
8.1
28
8.3
8.3
8.3
32
8.5
8.5
8.5
36
8.8
8.8
8.8
41
9.2
9.2
9.2
43
9.5
9.4
9.4
46
10.2
9.8
9.4
51
10.4
9.9
9.4
56
10.4
9.9
9.4
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
67
70
73
76
80
TC
TC
TC
TC
TC
MBh
MBh MBh MBh
MBh
4.3
4.3
4.3
4.3
4.3
4.8
4.8
4.8
4.8
4.8
5.4
5.3
5.3
5.3
5.3
5.5
5.4
5.4
5.4
5.4
5.7
5.6
5.6
5.6
5.6
5.9
5.9
5.8
5.8
5.8
6.5
6.5
6.5
6.5
6.5
6.8
6.8
6.8
6.8
6.8
7.3
7.3
7.3
7.2
7.1
7.7
7.6
7.6
7.4
7.4
8.1
8.1
7.9
7.8
7.4
8.3
8.3
8.1
7.8
7.4
8.5
8.4
8.3
7.8
7.4
8.8
8.5
8.3
7.8
7.4
8.9
8.5
8.3
7.8
7.4
8.9
8.5
8.3
7.8
7.4
8.9
8.5
8.3
7.8
7.4
8.9
8.5
8.3
7.8
7.4
8.9
8.5
8.3
7.8
7.4
Current certified ratings are available at www.ahridirectory.org.