Specifications; Installation - Emerson Fisher SS-263 Instruction Manual

Volume booster
Hide thumbs Also See for Fisher SS-263:
Table of Contents

Advertisement

SS-263 Volume Booster
August 2011
Table 1. Specifications
Port Diameters
Supply Port: 19 mm (0.75 inch)
Exhaust Port: 19 mm (0.75 inch)
Input Signal
Digital valve controller output
Maximum Input Signal Pressure
10.3 bar (150 psig)
Input to Output Pressure Ratio
Fixed at 1 to 1
NOTE: Specialized instrument terms are defined in ANSI/ISA Standard 51.1 - Process Instrument Terminology
1. The pressure/temperature limits in this document, and any applicable code or standard limitation should not be exceeded.

Specifications

Specifications for the SS-263 volume booster are listed in table 1. Information for an individual unit as it comes from
the factory appears on the nameplate (figure 2).
Figure 2. Example Nameplate

Installation

WARNING
Always wear protective clothing, gloves, and eyewear when performing any installation procedures to avoid personal
injury.
System damage may result if a volume booster is installed in a way that it can be physically damaged.
Personal injury or system damage may result when service conditions exceed booster or other equipment ratings.
Exceeding the pressure specifications in table 1 may cause leakage, parts damage, or personal injury due to bursting of
pressure-containing parts or explosion of accumulated gas.
2
Supply Pressure Ranges
Supply pressure also must not exceed the maximum
pressure rating of the actuator.
Up to 10.3 bar (150 psig)
Operative Temperature Limits
-40 to 71_C (-40 to 160_F)
Maximum Flow Coefficients
Supply: 9.5 Cv
Exhaust: 9.5 Cv
C1: 35
Xt: .77
Connections
Input Signal: 1/4 NPT
Supply and Output: 1 NPT
Approximate Weight
Aluminum: 3.6 kg (8 pounds)
Instruction Manual
D103542X012
(1)
(1)

Advertisement

Table of Contents
loading

Table of Contents