Det-Tronics Eagle Quantum Premier Instructions Manual

Det-Tronics Eagle Quantum Premier Instructions Manual

Fire and gas alarm control system and automatic. releasing for pre-action and deluge systems
Table of Contents

Advertisement

Instructions
Eagle Quantum Premier
®
Fire and Gas Alarm Control System and Automatic
Releasing for Pre-Action and Deluge Systems
18.2
Rev: 12/16
95-8533

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Eagle Quantum Premier and is the answer not in the manual?

Questions and answers

Summary of Contents for Det-Tronics Eagle Quantum Premier

  • Page 1 Instructions Eagle Quantum Premier ® Fire and Gas Alarm Control System and Automatic Releasing for Pre-Action and Deluge Systems 18.2 Rev: 12/16 95-8533...
  • Page 2: Table Of Contents

    Table of Contents Section 1 - Safety Section 3 - Installation ALERT MESSAGES ............1-1 SAFETY SYSTEM DESIGN REQUIREMENTS ..... 3-1 Identifying the Area of Protection ........3-1 Section 2 - Introduction Identifying Wiring, Network (LON), and System Power Requirements ........3-1 SYSTEM DESCRIPTION ..........
  • Page 3 Startup Procedure for Controller ........4-19 EQ22xxDCU Digital Communication Unit used with Startup Procedure for EDIO Module ......4-20 Det-Tronics H2S/O2 Sensors or other Two-Wire Startup Procedure for DCIO Module ......4-21 4-20 mA Devices ............3-43 Relay Module Startup ........... 4-21 Assembly and Wiring Procedure .......
  • Page 4 Table of Contents – Continued Section 5 - Maintenance Section 6 - Specifications EQ3XXX Controller ............6-1 ROUTINE MAINTENANCE .......... 5-1 EQ3LTM LON Termination Module ........6-3 Batteries ................. 5-1 EQ3730EDIO Enhanced Discrete I/O Module ....6-3 Manual Check of Output Devices ........5-1 EQ3700 DCIO Module ............
  • Page 5 Equipment Safety Symbols Symbol Description Direct current Alternating current Both direct and alternating current Three-phase alternating current Earth (ground) current Protective conductor terminal Frame or chassis terminal On (power) O (power) Equipment protected throughout by double insulation or reinforced insulation Caution, possibility of electric shock Caution, hot surface Caution*...
  • Page 6: Section 1 - Safety

    All wiring shall be installed in accordance with the manufacturer’s recommendations. CAUTION Identifies hazards or unsafe practices 3. Some Eagle Quantum Premier devices that COULD result in minor personal contain semiconductor devices that are injury or damage to equipment or susceptible to damage by electrostatic property.
  • Page 7: Section 2 - Introduction

    • Peer-to-peer communications application and the regulations that cover the • Short message formats type of protection required. See Figure 2-1 for a block diagram of the Eagle Quantum Premier • Expandability system. The Controller utilizes several mechanisms All field devices are tied into a communication to continuously check the LON loop for fault loop that starts and ends at the Controller.
  • Page 8: Lon Communication Heartbeat

    HARDWIRED I/O MODBUS RS-485 INTERFACE P2114 ETHERNET OR SERIAL INTERFACE BOARD Figure 2-1—Block Diagram of Eagle Quantum Premier System Only devices that have been approved for use Controller continuously tests with Eagle Quantum Premier can be connected continuity by sending out a heartbeat on one up to the LON.
  • Page 9: Theory Of Operation

    Table 2-1—Controller Based Faults Table 2-2—Field Device Based Faults Controller Faults Trouble LON Fault Trouble Field Device Faults Trouble Trouble Shown on Text Relay Shown on Text Display Relay Display 290 Volt Fault Controller Fault AC Failed Device Offline Battery Fault Extra LON Device Beam Block Invalid Config...
  • Page 10: Controller Logs

    Table 2-3—Eagle Quantum Premier Status Update Rates # of Input – Input – Input – Controller Type Devices No Exception With Exception With Exception U-Series PIRECL (UV & UVIR) DCIO, EDIO, AIM Relay Module ASM/ASH Module X-Series LS2000 1 to 100...
  • Page 11: Communication Network Fault Operation

    LON fault timeout period has elapsed. The LON fault isolation routine will be enabled NODE 2 NODE 7 when the device again receives a heartbeat. CONTROLLER TRONICS ® EAGLE QUANTUM PREMIER Safety System Controller NODE 1 NODE 8 Eagle Quantum Premier Fire Alarm Trouble Inhibit Power Time &...
  • Page 12: Major Component Descriptions

    MAJOR COMPONENT DESCRIPTIONS ETHERNET OR ETHERNET RS-232 OR MODBUS SERIAL LINK RS-485 DCS/PLC/HMI The system has three main component groups – the System Controller, LON (Local Operating CONTROLLER A Network), and Intelligent Field Devices. LON ADDRESS 1 CONFIGURATION SOFTWARE HIGH SPEED SYSTEM CONTROLLER RS-232 SERIAL LINK...
  • Page 13: Controlnet Board Or Ethernet Dlr Board

    Table 2-4—Ports on Ethernet Interface Board Table 2-5—Ports on Serial Interface Board Port Name Comm Function Port Name Comm Function Modbus (Master/ Modbus (Master/ Slave) Ground Serial Port 2 RS-485 Slave) Ground Fault Serial Port 2 RS-485 Fault Monitored, Monitored, Isolated Isolated Modbus (Master/ Modbus TCP/IP...
  • Page 14: Eqp Marine Application System

    Modbus Slave TCP/IP Server TCP/IP Server 10/100M Ethernet LAN TCP/IP Client Modbus Master Figure 2-8—Eagle Quantum Premier Network Extender HMI/DCS Figure 2-7—Ethernet TCP/IP Server/Client Relationship & Modbus RTU Master/Slave Relationship NOTE All LON devices support ANSI/NFPA • Modular trouble and alarm configuration 72 Class X communication with the •...
  • Page 15: Eq21Xxps Series Power Supplies And Eq2100Psm Power Supply Monitor

    Table 2-8—Flame Detector Instruction Manuals Detector Manual Number X3301 95-8704 X3301A 95-8527 & 95-8534 X3302 95-8576 X5200 95-8546 X2200 95-8549 Figure 2-9—Ground Fault Monitor X9800 95-8554 UVHT 95-8570 EQ21xxPS Series Power Supplies and EQ2100PSM Power Supply Monitor The Power Supply, Power Supply Monitor, and backup batteries are used to provide power FIELD DEVICES to the system.
  • Page 16: U5015 Explosion-Proof Smoke Detector

    EQ3730EDIO Enhanced Discrete Input/ Output Module The 8 Channel EDIO Module (see Figure 2-10) expands the Input and Output capability of the Eagle Quantum Premier System. The unit is designed to provide continuous and automated fire/gas protection, while ensuring system operation through continuous supervision of System Inputs/Outputs.
  • Page 17: Eq3700 8 Channel Dcio Module

    EQ3700 8 Channel DCIO Module EQ3720 8 Channel Relay Module The 8 Channel Discrete Input/Output (DCIO) The 8 Channel Relay Module (see Figure 2-12) Module (see Figure 2-11) consists of eight consists of eight individually configured output individually configured channels. Each channel channels.
  • Page 18: Eq3710Aim Analog Input Module

    (see devices with a calibrated 4–20 mA output Figure 2-14). Options include: Window, NTP/ signal to the Eagle Quantum Premier System. Metric ports, and a Ground Fault Monitor (GFM) Refer to the EQ3770EIO Instruction Manual...
  • Page 19: Eq3760Asm Addressable Smoke And Heat Module

    EQ3760ASM Addressable Smoke & Heat Module The EQ3760ASM Addressable Smoke & Heat Module (see Figure 2-15) is an interface device designed to provide continuous and automated fire protection for the EQP system. The EQ3760ASM is located directly on the LON of the EQP system, with a loop of up to 100 addressable devices tied into the EQ3760ASM.
  • Page 20: Eq22Xxarm Agent Release Module

    The EQP Controller continuously monitors the The device can monitor and control two output status of the ASH module, as well as the status devices (24 Vdc rated) that are programmed of each device connected to the ASH module. and energized together. The release circuits ASH module alarm and fault status conditions are compatible with a variety of solenoid or are logged in the EQP controller.
  • Page 21: Eq22Xxsam Signal Audible Module

    NFPA 72:2010 or earlier. NOTE Input types (e.g. fire alarm, trouble, and gas alarms) are configurable through ³ Det-Tronics Safety System Software (S NOTE Special Condition of Use: For use in systems installed in compliance with NFPA 72:2010 or earlier.
  • Page 22: Ud10 Dcu Emulator

    The EQ22xxDCUEX is a specialized version ordering information, refer to form number of the DCU that contains a transmitter for 95-8656. connection to a Det-Tronics Model CGS catalytic combustible gas sensor. Refer to the EQ22xxDCU Specification Data sheet (form number 90-1118) for additional information.
  • Page 23: Pirecl Pointwatch Eclipse

    As part of providing the total solution to monitoring of combustible hydrocarbon gas commercial and industrial customers globally, concentrations in the range of 0–100% LFL. Det-Tronics offers several performance approved hazardous area (EQ3900N The LON supervision meets Signaling Line...
  • Page 24: Section 3 - Installation

    Eagle Quantum Premier party certifications. For local installation System. practices, consult the local authority having jurisdiction.
  • Page 25 The Eagle Quantum Premier system utilizes a In order to calculate the power supply voltage power supply that provides an isolated 24 Vdc for the end device, calculate the voltage drops battery backed-up power to the fire protection that occur due to each wire segment between devices as described in NFPA 72.
  • Page 26: Determining Power Requirements

    Determining Power Requirements Tables 3-1 and 3-2 are provided for calculating the total current requirements for those parts of the system requiring battery backup. Table 3–1—Standby Current Requirements at 24 Vdc Number of Standby Device Type Total Current for Device Type Devices Current EQP Controller...
  • Page 27 Table 3-2—Alarm Current Requirements at 24 Vdc Number of Device Type Alarm Current Total Current for Device Type Devices EQP Controller 0.430 EQ3LTM Module 0.001 EDIO 8 Inputs 0.130 EDIO 8 Outputs 0.075 DCIO 8 Inputs 0.130 DCIO 8 Outputs 0.075 Relay Module 0.120...
  • Page 28: Eq211Xps, Eq213Xps And Eq217Xps

    Table 3-3A—EQ21xxPS Power Supply Specifications Characteristic Power Supply EQ2110PS/EQ2111PS EQ2130PS/EQ2131PS EQ2175PS/EQ2176PS Input Voltage 120 vac 120/208/240 vac 120/208/240 vac Input Current 4 Amps 11/6/6 Amps 24/15/12 Amps Input Frequency 60 Hz – EQ2110PS 60 Hz – EQ2130PS 60 Hz – EQ2175PS Input Frequency 50 Hz –...
  • Page 29: Eqp2410Ps(-P) Converter

    Table 3-4—Backup Battery Requirements for Automatic Release of Extinguishing Systems Except Deluge Standby Current Standby Time* Standby Amp Hours 24 Hours Alarm Current 5 Minute Alarm Time* Alarm Amp Hours 0.083 Hours Sum of Standby and Alarm Amp Hours Multiply by 1.2 (20% Safety Factor) T0014B Total Battery Amp Hour Requirement * FM MINIMUM REQUIREMENT FOR EXTINGUISHING SYSTEMS...
  • Page 30: Shield Grounding

    Table 3-3B – EQP2XX0PS Power Supply and Converter Specifications Characteristic EQP2120PS(-B) EQP2410PS(-P) Power Supply Converter Input Frequency 60/50 Input Voltage 120/220 Vac 24 Vdc Input Current, Max. 6.6 / 3.6 Iac 15.7 Idc Output Voltage Range 24.5 … 28.0 Vdc 24.5 …...
  • Page 31: Ground Fault Monitor (Gfm) Installation

    Many devices contain semiconductors that are susceptible to damage by – – electrostatic discharge. NOTE RELAY For more information on proper handling, refer to Det-Tronics Service Memo form SPARE 75-1005. COMMON EARTH GROUND FAULT MONITOR GROUND (GFM) INSTALLATION NOTE: RELAY CONTACTS ARE SHOWN IN THE REST STATE, NO POWER APPLIED.
  • Page 32 (Manufacturer and Part No.)* Feet Meters NOTE Belden 3073F (Tray Rated) 6,500 2,000 Det-Tronics NPLFP 6,500 2,000 Cables designed to ISA SP50 Type A or IEC Technor BFOU 4,900 1,500 61158-2 Type A are suitable for use in LON/ SLC wiring.
  • Page 33 NOTE Controller. The recommended lubricant is a silicone ENCLOSURE REQUIREMENTS free grease, available from Det-Tronics. The Controller must be properly installed in a suitable enclosure that is rated for the location. 7. Place the cover on the enclosure. Tighten The enclosure must provide space to install only until snug.
  • Page 34: Mounting

    ATEX/CE) hazardous area enclosures that have t h e v o l tag e i n p u t to t h e d ev i c e Eagle Quantum Premier equipment installed in (measured at the device) must be within the enclosure.
  • Page 35 COMMON 21 INPUT, + N. O. 22 COMMON, – N. C. 23 – Figure 3-4—Unsupervised Input Wiring Figure 3-5—Unsupervised Relay Output When controller and power supplies are installed in separate NRTL cabinets, two opening the N.C. contact (terminals 45-47). power cables from two distribution circuits are The relay coil is de-energized in the trouble required, so that if one is lost, the controller condition.
  • Page 36 Jumper P26 – LON COM 2 Termination Software selectable baud rates are 2400, 4800, 9600,19200, 38400, 57600, and 115200. COM 2 Terminated (factory setting) Software selectable parity is None, Odd, and COM 2 Unterminated (Redundancy) Even. The controller uses 8 data bits with 1 stop bit.
  • Page 37 Connector P9, Terminals 57, 58 & 59 — 115200 (factory default is 115200). Software ³ Configuration Port selectable parity is None, Odd, and Even. Configuration data downloaded into the Port Pinout (3-position terminal block) controller configures the serial interface 57 — GND transmission baud rate and parity check for the 58 —...
  • Page 38 SHIELD COM 1 – 24 VDC INPUT POWER – SHIELD COM 2 RESET 1– ACKNOWLEDGE RS-485 2– PORT 1 DIGITAL INPUTS 1 TO 4 SILENCE 3– RS-232 INHIBIT ENABLE CONFIG 4– PORT ENTER 5– CANCEL SERIAL INTERFACE BOARD 6– DIGITAL INPUTS 5 TO 8 NEXT 7–...
  • Page 39: Controller To Controller Communication

    CONTROLLER TO CONTROLLER Connector P10, Terminals 60, 61 & 62, Port 2– RS-485 Modbus RTU Master/Slave COMMUNICATION Configuration data downloaded into the Controller to Controller Communication controller configures the serial interface (SLC485) with Signaling Line Circuit transmission baud rate, parity check for the Classification Class B or X, per NFPA 72 serial port, and Modbus device address.
  • Page 40 RS-232 Transmit LED (Amber) RS-485 Receive LED (Green) P25: RS-485 Termination Jumper RS-232 Receive LED (Green) TRONICS ® RS-485 Transmit LED (Amber) EAGLE QUANTUM PREMIER Safety System Controller Channel RS-485 Termination Jumper Indicators Eagle Quantum Premier Fire Alarm Trouble Inhibit...
  • Page 41 RS-485 Transmit LED (Amber) RS-485 Receive LED (Green) P5: RS-485 Ground Fault Monitor Jumper RS-232 Receive LED (Green) TRONICS ® RS-485 Transmit LED (Amber) EAGLE QUANTUM PREMIER Safety System Controller Channel RS-485 Termination Jumper Indicators Eagle Quantum Premier Fire Alarm Trouble...
  • Page 42 P25: RS-485 Termination Jumper, P25: RS-485 Termination Jumper, Position 1 & 2 Position 1 & 2 TRONICS TRONICS ® ® EAGLE QUANTUM PREMIER EAGLE QUANTUM PREMIER Safety System Controller Safety System Controller Eagle Quantum Premier Eagle Quantum Premier Fire Alarm Trouble...
  • Page 43: Configuration

    Subnet Mask 255.255.255.000 Software Defined Addresses NOTE ³ Det-Tronics Safety System Software (S is programmed with the addresses that Maximum Modbus update time per port are assigned to the controller when the is 250 mSec. configuration file is downloaded into the controller.
  • Page 44 EQP CONTROLLER No. 1 EQP CONTROLLER No. 3 SINGLE MODE FIBER OPTIC CABLE PORT 1 PORT 1 RS-485 RS-485 T– T– R+D+ R+D+ Moxa Moxa R–D– R–D– TCF-142-S TCF-142-S EQP CONTROLLER No. 2 EQP CONTROLLER No. 4 PORT 1 PORT 1 RS-485 RS-485 B2328...
  • Page 45: Eq3Xxx Redundant Controller Installation

    TROUBLE INPUT EQP CONTROLLER No. 1 TROUBLE INPUT EQP CONTROLLER No. 3 TO EQP SYSTEM TO EQP SYSTEM MULTI MODE FIBER OPTIC CABLE PORT 2 PORT 2 RS-485 RS-485 D(P) D(P) Phoenix Phoenix D(N) D(N) PSI-MOS- PSI-MOS- RS485W2/FO RS485W2/FO EQP CONTROLLER No. 2 EQP CONTROLLER No.
  • Page 46: High Speed Serial Link (Hssl)

    HIGH SPEED SERIAL LINK (HSSL) controller has the correct output information. Information coming from the PLC should be The redundant controllers are connected written to both Premier Controllers. together by a dedicated high-speed serial link. This link is a pre-fabricated cable that has a EtherNet DLR custom connector for ease of use.
  • Page 47: Mounting

    MOUNTING 4. Connect external wiring to the appropriate points on Power Supply. Refer to Figure 3-18 Mount the power supply monitor in a Nationally for terminal block locations and Figures Recognized Test Laboratory (NRTL) labeled 3-19 and 3-20 for terminal identification. enclosure.
  • Page 48: Measuring Battery Voltage And Charging Current

    J1: POWER AND LON WIRING LON ADDRESS SWITCHES J3: AC INPUT TERMINAL NO. 1 TERMINAL J2-1 TO TERMINAL B TERMINAL J2-2 TO SWITCH NO. 1 TERMINAL C + – YELLOW LED RED LED TERMINAL NO. 1 GREEN LED C1949 0.0005 OHM SHUNT J2: BATTERY TEST POINTS TERMINAL NO.
  • Page 49: Eqp2Xx0Ps(-X) Power Supplies And Redundancy Module Installation

    POWER SUPPLY MONITOR TERMINAL J1 See Note 10 AC MONITOR See Note 4 – AC POWER – 24 VDC See Notes 1 & 3 OUTPUT – POWER DIST CKT #1 – POWER DIST CKT #2 – POWER DIST CKT #3 –...
  • Page 50 1. Connect external wiring NOTE appropriate points on Power Supplies. Contacts are closed during normal operation. The circuit shall be wired to Refer Figure 3-23A terminal an input on the EQP system (EDIO or locations EQP21X0PS(-X). IDC). In Logic, the selected input must be inverted and used to activate an Refer Figure...
  • Page 51 NRTL DISTRIBUTION CABINET – PRMARY POWER 24 VDC – See Notes 1 & 2 OUTPUT EQP2120PS(-x) POWER SUPPLY – – 24 VDC – SECONDARY POWER OUTPUT See Notes 2 & 4 – – POWER DIST CKT #1 – POWER DIST CKT #2 EQP2410PS(–P) CONVERTER REDUNDANCY –...
  • Page 52: Startup

    ENHANCED DISCRETE NOTE INPUT/OUTPUT (EDIO) For additional information, refer to the MODULE INSTALLATION power supply manufacturer’s documents provided with the support documentation received with the Eagle Quantum Premier system. All electrical connections are made to the field wiring connectors furnished with the module. STARTUP Refer to Figure 3-23 for identification of module wiring terminals.
  • Page 53 Connector P3, Terminals 1 to 12 Connect external system wiring to the appropriate terminals on the terminal block. Terminals A,B & C Channels 1 to 4 Input / Output Terminals For Class B wiring, see Figure 3-27. For Class A wiring, see Figure 3-28.
  • Page 54 The input to the EDIO module consists of IMPORTANT normally open switches, with a 10 K ohm, 1/4 No more than 15 devices can be watt EOL resistor in parallel across the return connected per channel. channel, and a 3.3 K ohm, 1/4 watt resistor in series with each switch.
  • Page 55 Supervised Output— module. This type of output does not require the use of EOL resistors or diodes to supervise Notification Supervised for Open & Short Circuits the circuit. Connect external system wiring to the The output can be configured for latching, appropriate terminals on the terminal block.
  • Page 56: Configuration

    A tag number must include zone designation, which will be shown on the The DCIO can be panel or DIN rail mounted. controller's display when the point is in alarm. Det-Tronics S ³ Safety System Software is used for device configuration. The following shows...
  • Page 57: Wiring

    895630 1500 Cat # 81-895630-000 Kidde-Fenwal 890181 1500 Det-Tronics PN 00219-209 Ansul 570537 Macron 304.209.001 *Note: Alternate secondary power source when accept by Local AHJ, may increase permissible wire voltage drops. Actual secondary voltage must be determined. Voltage and current at solenoid must be known and used in the equation.
  • Page 58 EQ3700DCIO COMMON C IN–/OUT+ B CHANNEL 8 SHLD COM 2 SHLD + SUPPLY A LON FROM COM 2 B PREVIOUS DEVICE COMMON C COM 2 A CHANNEL 7 IN–/OUT+ B SHLD COM 1 SHLD LON TO + SUPPLY A COM 1 B NEXT DEVICE COM 1 A COMMON C...
  • Page 59 The input to the DCIO module consists of a NOTE normally open switch, with a 10 K ohm, 1/4 No connection should be made to the “+ watt EOL resistor in parallel across the switch, Supply” terminal. and a 3.3 K ohm, 1/4 watt resistor in series with the switch.
  • Page 60 Each output channel is individually activated NOTE for response pattern: For solenoids, this wire length includes – continuous output both the wiring from the power supply to – 60 beats per minute the DCIO module and the wiring from the –...
  • Page 61: Configuration

    4 and 5. Shields are to be connected to terminals 3 and 6. ³ Det-Tronics S Safety System Software is used for device configuration. The following shows the minimum software/firmware releases: Controller Firmware ³...
  • Page 62: Configuration

    Be sure to observe polarity when wiring the identification. LON. 1 — "A" side of signaling circuit for COM 1 Det-Tronics S ³ Safety System Software is used 2 — "B" side of signaling circuit for COM 1 for device configuration. The following shows 4 —...
  • Page 63: Wiring

    The enclosure should be rated for the Power Connector — Terminals 1 to 6 temperature range of the location plus the 24 Vdc Power Input temperature rise of all equipment installed 1 — + inside the enclosure. The enclosure must be 2 —...
  • Page 64: Configuration

    COM Connector — Terminals 1 to 6 CONFIGURATION LON Terminals Setting Analog Input Module Be sure to observe polarity when wiring the Network Address LON. One unique network address must be assigned 1 — "A" side of signaling circuit for COM 1 to each analog input module.
  • Page 65: Gas Detector Location And Installation

    Det-Tronics S ³ Safety System Software is used 3. Ventilation characteristics. Air movement for device configuration. The following tables will cause gas to accumulate more heavily show the minimum software/firmware releases: in one area than another. The devices should be placed in areas where the...
  • Page 66: Eq22Xxdcu Digital Communication Unit Used With

    Halogens compounds containing EQ22XXDCU DIGITAL COMMUNICATION halogen are materials of this nature and UNIT USED WITH DET-TRONICS others include: H2S/O2 SENSORS OR OTHER Examples: TWO-WIRE 4-20 MA DEVICES Chlorine Determine the best mounting locations for Bromine the detectors.
  • Page 67 A1571 COM 1 Figure 3-50—Printed Circuit Boards in Universal DCU A1726 See Figure 3-52 for an example of a Det-Tronics Figure 3-51—Wiring Configuration for DCU electrochemical sensor connected to a DCU. Attach the communication module to the H 2 S/TOXIC/O 2 standoffs as shown in Figure 3-48.
  • Page 68: Sensor Separation For Dcu With H2S And O2 Sensors

    Sensor Separation for DCU with H2S 2. A communication module mounted above the terminal wiring board using the standoffs and O2 Sensors provided. See Figure 3-50. Since the transmitter for the electrochemical sensor is already mounted within the sensor housing, simply mount the entire sensor Assembly and Wiring Procedure assembly to the sensor separation kit junction Attach the PointWatch/DuctWatch to the DCU...
  • Page 69: Eq22Xxdcuex Digital Communication Unit

    EQ22XXDCUEX DIGITAL COMMUNICA- DCU TRANSMITTER BOARD 1 DCU TERMINAL BOARD (MIDDLE BOARD) TION UNIT (USED WITH DET-TRONICS POINTWATCH CALIBRATE COMBUSTIBLE GAS SENSORS) Mounting 4 TO 20 MA IN Determine the best mounting location for the – – device. Whenever practical, the device should...
  • Page 70: Sensor Separation With Dcuex

    Lubricate the box cover with a thin coat of silicone-free O-ring and the threads of the junction box grease (available from Det-Tronics). cover with a thin coat of silicone-free grease (available from Det-Tronics). 12. Replace the device cover.
  • Page 71: Typical Applications

    Alternate Method A plug with screw terminals is provided for connecting the cable to P2 on the transmitter If the transmitter board must be mounted board. Observe the wiring color code. Connect separate from the sensor (high temperature the shield to the ground terminal in the DCUEX applications, etc.), separate the sensor only, junction box.
  • Page 72 SINGLE SOLENOID DUAL SOLENOIDS CH 1 CH 2 CH 3 CH 4 CH 5 CH 6 CH 7 CH 8 RELAY 6 RELAY 7 RELAY 8 RELAY 5 DIGITAL INPUTS RELAY 1 RELAY 2 RELAY 3 RELAY 4 18.2 3-49 95-8533...
  • Page 73: System Configuration

    SYSTEM CONFIGURATION SETTING DEVICE NETWORK ADDRESSES Overview of Network Addresses Each device on the LON must be assigned a unique address. Addresses 1 to 4 are reserved for the controller. Valid addresses for field devices are from 5 to 250. Figure 3-58—Field Device Address Switches for ARM, SAM, DCU and IDC IMPORTANT...
  • Page 74: Rocker Switch Table

    Rocker Switch Table Node Rocker Switch Node Rocker Switch Address Address 18.2 3-51 95-8533...
  • Page 75 Rocker Switch Table Node Rocker Switch Node Rocker Switch Address Address 95-8533 18.2 3-52...
  • Page 76: Section 4 - Operation

    Reset resets all controller latched outputs that are no longer active. Acknowledge silences the internal beeper. Silence turns on the Silence LED and sets Silence status in user logic. TRONICS ® EAGLE QUANTUM PREMIER Safety System Controller Eagle Quantum Premier Fire Alarm Trouble Inhibit Power Time &...
  • Page 77: Controller Status Indicators

    If multiple alarms or trouble conditions diagnostics options. exist, the display scrolls through all active status conditions until they go inactive and are reset using the controller pushbutton. TRONICS ® EAGLE QUANTUM PREMIER Safety System Controller Eagle Quantum Premier Fire Alarm Trouble Inhibit Power Time &...
  • Page 78 Marque Display Auto Scrolling Alarm Enter / Cancel Screen Display Current Time/Date (no active alarms) Display Alarms Screen Display Alarms Enter Next Display Alarms Prev Enter Fire Alarms Cancel Display Devices* Next Gas Alarms Reset Prev Trouble Pressing the ack Device Tagname Supervisory switch acknowledges...
  • Page 79 Pressing the NEXT or PREVIOUS pushbuttons Main Menu allows cycling through devices. Pressing the >Display Alarms CANCEL pushbutton will return the display to the Main Menu. Display Devices Device Tagnames DEVICE TAG NAMES displays device tag name information for all devices on the LON Moving within the Main Menu is done by using loop.
  • Page 80 SERIAL PORTS displays port information on Cntr Mode all available ports. Indicates whether the controller is in master or standby mode. Serial Ports Configuration Port My Config Serial Port 1 Indicates whether the controller is the primary Serial Port 2 or secondary controller.
  • Page 81: Controller Audible Alarm

    Lon Comm Table 4-2—EQP Controller Alarm Tone Patterns Redundant controllers exchange information Priority Controller Tone Tone Pattern across the LON network. This is primarily done Fire Alarm Temporal to prevent both controllers from becoming the Supervisory Supervisory master in the event that the HSSL fails. The fault is annunciated when a controller fails to receive Trouble Trouble...
  • Page 82: Controlnet Status Indicators (Optional)

    Steady - The indicator is on continuously in the defined state. TRONICS Network Status ® Module Status Network Status EAGLE QUANTUM PREMIER Link Status 1 Link Status 2 Link Status 1 Safety System Controller Alternating - The two indicators alternate Eagle Quantum Premier...
  • Page 83: Data Download

    (approximately 30 seconds). 9. Text display’s first line indicates "*** a) Text display’s first line indicates "Det- Program Mode ***" Tronics Eagle Quantum Premier." 10. Text display’s third line displays download b) Text display’s third line displays time status.
  • Page 84: Controller Redundancy

    CONTROLLER REDUNDANCY 5. The controller that is connected with the secondary end of the HSSL is assigned Pushbuttons address 2. The pushbuttons are active on the master 6. If there are no faults present, the primary controller and inactive on the standby controller defaults to the master controller controller.
  • Page 85 Sequence of Events During a 5. The controller indicates “Device Download Active” until the LON devices have been Configuration Download successfully updated. WARNING Automatic Switchover The system is inactive and not executing logic/alarm functions during a program An automatic transfer will be initiated if the download (in both single and redundant master controller goes into an error (self controller configurations).
  • Page 86: Enhanced Discrete I/Omodule

    ENHANCED DISCRETE I/O STATUS INDICATOR LEDs MODULE The EDIO Module (see Figure 4-6) has 18 LED status indicators, two for the device and two for each channel, located on the front panel. Refer to Tables 4-7 and 4-8 for a description of the LED indicators.
  • Page 87: Channel Dcio Module

    8 CHANNEL DCIO MODULE STATUS INDICATOR LEDs The DCIO Module (see Figure 4-7) has 18 LED status indicators, two for the device and two for each channel, located on the front panel. Refer to Tables 4-9 and 4-10 for a description of the LED indicators.
  • Page 88: Channel Relay Module

    8 CHANNEL RELAY MODULE STATUS INDICATOR LEDs The Relay Module (see Figure 4-8) has 18 LED status indicators, two for the device and two for each channel, located on the front panel. Refer to Tables 4-11 and 4-12 for a description of the LED indicators.
  • Page 89: Analog Input Module

    ANALOG INPUT MODULE STATUS INDICATOR LEDs The Analog Input Module (see Figure 4-9) has 18 LED status indicators, two for the device and two for each channel, located on the front panel. Refer to Tables 4-13 and 4-14 for a description of the LED indicators.
  • Page 90: Eq21Xxpsm Power Supply Monitor

    EQ21XXPSM POWER SUPPLY EQ2220GFM GROUND FAULT MONITOR MONITOR The power supply monitor (see Figure 4-10) The ground fault monitor (see Figure 4-11) has has three LEDs used to provide a visual three LEDs used to provide a visual indication indication of device status: of device status: + GND FLT LED –...
  • Page 91: Eq22Xxdcu And Eq22Xxdcuex Digital

    EQ22XXDCU AND EQ24XXNE NETWORK EQ22XXDCUEX DIGITAL EXTENDER COMMUNICATION UNITS The EQ24xxNE has three LEDs (one green, two amber) for indicating device status. The DCUs have three LEDs to provide a visual indication of device status. They are visible through the window on the enclosure cover. NOTE Table 4-21—Network Extender Status Indicators If the communication module has not...
  • Page 92: System Startup

    Redundant Controller SYSTEM STARTUP The I/O and LON wiring is correctly installed, PRE-OPERATION CHECKS observing polarity. All cable shields are General properly terminated and insulated. Insulate all shields to prevent shorts to device Power wiring is installed and power source is housing or to any other conductor.
  • Page 93: General Start-Up Procedures

    Verify correct address setting. Check for correct installation of EOL resistors. 5. Program the system for the desired operation using Det-Tronics Safety System Software (S ³ ). Download configuration data ARMs to all devices.
  • Page 94: Startup Procedure For Controller

    To verify that the Controller is powered-up and operating properly, ensure that: NOTE The module is configured using Det-Tronics 1. When power is first applied, all LEDs are on. Safety System Software. The ACK LED flashes while the memory test is running.
  • Page 95: Startup Procedure For Dcio Module

    NOTE matrix. The module is configured using 3. The output circuits should indicate the Det-Tronics Safety System Software. proper state for the programmed device (channel active LED illuminates when the Activation Time circuit is active). Check the power supply and Timers are made available for output circuits associated wiring.
  • Page 96: Relay Module Startup

    DCIO Startup Relay Module Startup 1. The Power-on LED should be illuminated. 1. The Power-on LED should be illuminated. The Fault LED should blink once on power The Fault LED should blink once on power up, then remain off. up, then remain off. 2.
  • Page 97: Section 5 - Maintenance

    NOTE it. If it feels dry, a thin coating of lubricant Refer to the Eagle Quantum Premier should be applied. When re-installing the Sy s te m S a fe t y M a n u a l ( n u m b e r...
  • Page 98: Calibration And Adjustments

    CALIBRATION ALGORITHM A IMPORTANT FOR MANUAL CALIBRATION OF 4–20 mA devices not manufactured by UNIVERSAL DCU Det-Tronics must be pre-calibrated. To Normal Calibration ensure adequate protection, calibration must be performed on a regularly 1. Activate the reed switch. (The red LED scheduled basis.
  • Page 99: Sensor Replacement

    11. Remove the span gas, and return the 11. Remove the span gas and return the analog input to normal. analog input to normal. 12. Activate the reed switch. (The red LED 12. Activate the reed switch. (The red LED blinks for three seconds while the reed flashes for three seconds while the switch switch is closed)
  • Page 100: Initial Installation And Sensor Replacement - Combustible Gas

    7. The calibrate LED stays on steady. 5. Connect a volt meter to the test points on the transmitter board. Connect the “+” lead 8. Remove the calibration gas. to TP1 (red). Connect the “–” lead to TP2 9. The communication module waits until the (black).
  • Page 101: Sensor Replacement - Toxic Gas

    Sensor Replacement — Toxic Gas 9. Remove the calibration gas and replace the DCU enclosure cover. NOTE 10. The communication module waits until the When replacing a sensor, compare analog value drops below 4% full scale. part numbers to be sure the correct The calibration is complete.
  • Page 102: Calibration Algorithm Gfor Dcus With Pointwatch Or Ductwatch

    4. Activate the reed switch. (The red LED 7. The calibrate LED stays on steady. flashes for three seconds while the switch 8. Remove the calibration gas. is closed.) 9. The communication module waits until the 5. The communication module records sensor input drops below 4% full scale.
  • Page 103: Device Calibration Logs And Records

    Return all equipment transportation prepaid to REPLACEMENT PARTS the factory in Minneapolis. Eagle Quantum Premier devices are not designed to be repaired in the field. If a problem should develop,...
  • Page 104 Table 5-2—System Controller Troubleshooting Guide Symptom Possible Cause Corrective Action Controller Power No Power to Input. – Measure input voltage (18 to 30 Vdc). LED/ – Check that P1 is fully inserted. Text Display OFF If voltage is present and P1 is fully inserted, replace controller.
  • Page 105: Ordering Information

    ORDERING INFORMATION LON DEVICES Part Number Description When ordering, please specify: 006607-xxx EQ22xxDCU Digital Refer to the appropriate model matrix in Communication Unit (specify Appendix G for the following devices: gas) 006941-xxx EQ24xxNE Network Extender EQ3XXX EQP Controller EQ3700DCIO Discrete Input/Output Module 008056-001 HART Interface Module EQ3710AIM Analog Input Module...
  • Page 106: Section 6 - Specifications

    Section 6 SERIAL INTERFACE BOARD— Specifications RS-485 Communication: Modbus master/ slave capability, ground fault monitored. NOTE Digital communication, transformer isolated F o r U S C G A p p r o v e d S y s t e m (up to 230 kbps).
  • Page 107 (17.78) Class I, Zone 2, Group IIC (T4). TRONICS Tamb = –40°C to +80°C. ® ® APPROVED EAGLE QUANTUM PREMIER 5.95 Performance verified. Safety System Controller (15.1) Refer to Appendix A for FM Approval details, Eagle Quantum Premier Fire Alarm...
  • Page 108: Eq3Ltm Lon Termination Module

    EQ3LTM LON TERMINATION EQ3730EDIO ENHANCED MODULE DISCRETE INPUT/OUTPUT MODULE INPUT VOLTAGE— 24 Vdc nominal, 18 to 30 Vdc. 10% overvoltage POWER REQUIREMENTS— will not cause damage to the equipment. 3 watts nominal, 11 watts maximum. INPUT POWER— INPUT VOLTAGE— 1 watt maximum. 24 Vdc nominal, 18 to 30 Vdc.
  • Page 109 1.35 (3.4) (6.4) 5.02 (12.7) (11.3) (11.3) (13.2) 1.66 (13.2) (4.2) A2449 (4.8) PANEL MOUNTING DIMENSIONS DIN RAIL MOUNTING DIMENSIONS Figure 6-3—Dimensions of the EDIO / DCIO / Relay Module / AIM in Inches (Centimeters) IECEx: IECEx ULD 10.0004X. For Class A wiring on inputs, configure adjacent Ex nA nC IIC T4 GC.
  • Page 110 SUPERVISED OUTPUT RATING-SIGNAL- NOTE ING CIRCUIT EDIO SIL has the capability of monitoring MAXIMUM OUTPUT CURRENT solenoid circuits for shorts. The minimum (Per Channel)— solenoid inductance for correct operation 2 amperes at 30 Vdc maximum. is 100 mH. See Table 3-10 for a list of Automatic short circuit protection provided.
  • Page 111 ATEX/EMC Directive Compliant. MAXIMUM OUTPUT CURRENT— 2 amperes maximum, 15 Amp inrush. Automatic short circuit protection provided. ATEX: II 3 G. ® APPROVED SUPERVISORY CURRENT— Ex nA nC IIC T4 Gc. Reverse current monitored at 3.0 mA, ± 2.0 ® DEMKO 02 ATEX 133864X.
  • Page 112: Eq3720 Relay Module

    EQ3720 RELAY MODULE EQ3710AIM ANALOG INPUT MODULE POWER REQUIREMENTS— 3 watts nominal, 4 watts maximum. POWER REQUIREMENTS— Module power consumption: 6 watts. INPUT VOLTAGE— When supplying power three-wire 24 Vdc nominal, 18 to 30 Vdc. 10% overvoltage transmitters: will not cause damage to the equipment. Maximum current at power input: 7.4 amperes.
  • Page 113: Hart Interface Module

    EQ21XXPS POWER Note: Refer to Appendix C for ATEX and IECEx approval details and Special Conditions for SUPPLIES Safe Use. INPUT VOLTAGE— Selectable for 120, 208 or 240 vac input power, Refer to Appendix D for USCG Approval details. ±10%. HART INTERFACE MODULE INPUT CURRENT—...
  • Page 114: Eqp2Xx0Ps(-X) Power Supplies

    EQP2XX0PS(–X) POWER REDUNDANCY MODULE SUPPLIES QUINT–DIODE/40 INPUT VOLTAGE— TEMPERATURE RANGE— EQP2120PS(-B): Auto selectable for 120/220 Operating: –13°F to +131°F (–25°C to +55°C) Vac, –15%, +10%; 60/50 Hz, single phase; (All Applications) EQP2410PS(-P) Converter: 24 Vdc, –15%, Storage: –40°F to +185°F (–40°C to +85°C). +10%.
  • Page 115: Eq21Xxpsm Power Supply Monitor

    EQ2220GFM GROUND EQ21XXPSM POWER SUPPLY FAULT MONITOR MONITOR INPUT VOLTAGE— INPUT VOLTAGE— 24 Vdc nominal, 18 to 30 Vdc. 24 Vdc nominal, 18 to 30 Vdc. 10% overvoltage will not cause damage to the equipment. POWER CONSUMPTION— 2.0 watts maximum. INPUT POWER—...
  • Page 116 EQ22XXDCU AND CERTIFICATION— FM / CSA: Class I, Div. 2, Groups A, B, C, D (T4). EQ22XXDCUEX DIGITAL Class I, Zone 2, Group IIC (T4 ). COMMUNICATION UNIT ® APPROVED Refer to Appendix A for FM Approval details. INPUT VOLTAGE— Refer to Appendix B for CSA Approval details.
  • Page 117: Eq24Xxne Network Extender

    EQ24xxNE NETWORK CERTIFICATION— FM / CSA: Class I, Div. 1, Groups B, C, D. EXTENDER Class I, Zone 1, Group IIC. Class I, Div. 2, Groups A, B, C, D (T4). INPUT VOLTAGE— Class I, Zone 2, Group IIC (T4 ). ®...
  • Page 118: Combustible Gas Sensor

    EQ3750 ASH ADDRESSABLE EQ21XXPS POWER SUPPLY SMOKE & HEAT MODULE The EQ21xxPS Rectifier / Power Supply has many inherent advantages such as voltage For complete information regarding the ASH regulation, high efficiency, high power factor Module, refer to instruction manual number and short circuit protection.
  • Page 119 Section 7 Ordering Information CONTROLLER MODEL MATRIX MODEL DESCRIPTION EQ3001 EQP Controller - 246 Nodes EQ3016 EQP Controller - 16 Nodes TYPE MOUNTING OPTION Din Rail Panel Mount TYPE COM BOARD 1 None ControlNet EtherNet DLR TYPE COM BOARD 2 None Ethernet Port Expansion Serial Port Expansion...
  • Page 120 DCIO MODEL MATRIX MODEL DESCRIPTION EQ3700 8 Channel Discrete Input/Output (DCIO) Module TYPE MOUNTING OPTION DIN Rail Panel TYPE APPROVALS* FM/CSA/ATEX/IECEx *Type "APPROVALS" can use one or more letters to designate the approvals of the product. Some configurations are not available. Check with factory for additional information. AIM MODEL MATRIX MODEL DESCRIPTION...
  • Page 121 See description on page D-6 000523-010 000523-010 See description on page D-6 For other USCG Approved EQP System components, refer to Table D-1 or contact Det-Tronics Customer Service. Refer to Section 3 of this manual for determining power requirements. 95-8533...
  • Page 122 • National Fire Alarm Code performance verified per NFPA 72-2013. Refer to Table A-1 for device and circuit supervision characteristics. • See section 2 "Field Devices Flame Detectors" for information regarding Det-Tronics approved flame detectors and associated manuals. Additional two second response time applied for system communication.
  • Page 123 EAGLE QUANTUM PREMIER FIRE AND GAS ALARM CONTROL PANELS: Hazardous Locations: Non-Incendive Solutions (Class 1, Div 2): EQ3900N - See Manual 95-8559 Explosion Proof Solution (Class 1, Div 1): EQ3900E - See Manual 95-8763 EQ3900RPS Remote Power Supply Enclosure - See Manual 95-8745...
  • Page 124 Parker (Viking): 11591 NC, 11592 NC, 71395SN2#NJ1NOH111C2, 73218BN4TNLVNOC322C2, 73212BN4TNLVNOC322C2, and 73212BN4TN00N0C111C2 ASCO RedHat: R8210A107, 8210A107, 8210G207, 11601, 11602 Viking PN: HV274608 N.C., HV2740607 N.C. Kidde-Fenwall: 897494, 895630, 890181 Cat #: 202-749-260563, 202-749-260563 Det-Tronics PN: 00219-209 Ansul: 570537 Macron: 304.209.001 18.2 95-8533...
  • Page 125 Table A-1—Circuit Classifications-Continued Signaling Path NFPA 72 Supervision Discrete I/O, Input (software Unsupervised per ANSI/NFPA 72, Cl. 12.6.9 configurable) Initiating Device Circuit (IDC): Class B Discrete I/O, Output (software Unsupervised per ANSI/NFPA 72, Cl. 12.6.9 configurable) Notification Appliance Circuit (NAC): Class B Supervised Solenoids (Class B): Group B: ASCO T8210A107 Group D: ASCO 8210G207...
  • Page 126 Figure A-1 (FM Drawing 007545-001) 18.2 95-8533...
  • Page 127 CLASS – 4828 02 – Signal Appliances – Toxic Gas Detection Instruments for Hazardous Locations HAZARDOUS LOCATIONS Eagle Quantum Premier (EQP) System and Components Class I Division 2 Groups A, B, C & D, T4 Class I Zone 2 IIC, T4, When installed in a suitable CSA Certified labeled Type rated enclosure:...
  • Page 128 Class I Division 1 Groups B, C & D, T6, TYPE 4X: EQ3770EIO Series Class I Division 2 Groups A, B, C & D T3A Class I Zone 2, IIC T3, TYPE 4X: EQ3900N Series Ordinary Locations : EQ3900G Series EQP System Gas Detector / Sensors Class 4828-01 &...
  • Page 129: Appendix C - Atex/Ce And Iecex Certification

    ATEX AND IECEX CERTIFICATION ATEX AND IECEX CERTIFICATION DETAILS The Eagle Quantum Premier Fire and Gas Detection / Releasing System was tested and certified to hazardous location and combustible gas performance standards. Refer to Figure C-1 for system classification details.
  • Page 130 PIRECL). 6. Controller Model EQ3XXX with UD10/DCU Emulator and CGS Conditioning Board, in combination with the Det-Tronics gas sensor Model CGS (tested as a gas detection system with methane applied to the CGS). 7. Controller Model EQ3XXX with OPECL or LS2000.
  • Page 131 APPENDIX D EAGLE QUANTUM PREMIER SYSTEM MARINE APPLICATIONS DNV AND U.S. COAST GUARD APPROVAL NUMBER 161.002/49/0 Approved System Description Refer to Table D-1 for a complete list of DNV and USCG approved equipment. Table D-1— List of Approved Equipment Equip.
  • Page 132 Table D-1— List of Approved Equipment (Continued) Equip. Manufacturer Equipment type Series/Model Description UD10 Universal Det-Tronics UD10A (S) 5N (5M) 25 (28) W 2 Display X3301 X3301A (S) 4N (4M) 11 (13, 14, 23) W (T) 1 (2) ; Det-Tronics...
  • Page 133 Table D-1— List of Approved Equipment (Continued) Equip. Manufacturer Equipment type Series/Model Description Cooper CCH ETH 2416 Uses CCH EAJC26 conduit outlet box with cover, Crouse Hinds Horn 3/4 NPT hub size. Applied Strobe AST-4-10-30-DC-CL-CM-75-ULC; AST-4-1030 Strobe Technology with clear lenses (Canada) Air Products SL-2000-P...
  • Page 134 IMPORTANT The EQP2120PS-B Power Supply providies EQP System devices with power from input supply 120 to 220 Vac. The EQP2120PS-B Power Supply is used in pairs where primary source of input supply is connected to one and the secondary source is connected to the other. Use of these power supplies may provide the source of the secondary supply.
  • Page 135 QUINT-DIODE/40 REDUNDANCY MODULE 8 (2 Power Supplies can be connected to each module) max Number of units: Input voltage: 24.5….28.0 Vdc IMPORTANT The output voltage is adjustable. An even current distribution must be ensured by precisely setting all power supply units that are operated in parallel to the same output voltage ±10 IMPORTANT To ensure symmetrical current distribution it is recommended that all cable connections from all power supply units/diode redundancy modules to the power distribution bus are the...
  • Page 136 NOTE SHCS # 10-24 SST screws are recommended for the Power Supply and Diode Redundancy Module panel mounting. NOTE Terminal End Brackets DEC P/N 000133-517 are recommended for use with EQ371(2)(3)0D (DIN rail mount) and EQ2220GFM Modules. POWER SUPPLY SUPERVISION— The EQP2120PS-B Power Supply and EQP2410PS-P Converter shall be monitored for Trouble.
  • Page 137 See description on page D-6 000523-010 See description on page D-6 For other USCG Approved EQP System components, refer to Table D-1 or contact Det-Tronics Customer Service. Refer to Section 3 of this manual for determining power requirements. USCG insignia marked on the controller and power supplies indicates USCG certification of a system made-up of components in Table D-1.
  • Page 138 Table D-2—Temperature and Humidity Ranges Temperature & RH Non-Condensing Installation Category Installation in Equip. Product consoles, Controlled housings, etc.; Weather exposed environment Non-weather areas (Salt mist) protected or cold locations EQ3XXX Controller 0°C to +55°C -25°C to +70°C -25°C to +70°C with or without 5-95%RH 5-95%RH...
  • Page 139 Table D-2—Temperature and Humidity Ranges (Continued) Temperature & RH Non-Condensing Installation Category Installation in Equip. Product consoles, Controlled housings, etc.; Weather exposed environment Non-weather areas (Salt mist) protected or cold locations EQ2220GFM 0°C to +55°C -25°C to +70°C -25°C to +70°C Ground Fault Monitor 5-95%RH 5-95%RH...
  • Page 140 Table D-2—Temperature and Humidity Ranges (Continued) Temperature & RH Non-Condensing Installation Category Installation in Equip. Product consoles, Controlled housings, etc.; Weather exposed environment Non-weather areas (Salt mist) protected or cold locations 0°C to +55°C -25°C to +70°C -25°C to +70°C AST-4-1030 Strobe 5-95%RH 5-95%RH...
  • Page 141 95-8533 18.2 D-11...
  • Page 142 Phone: 952.946.6491 Corporate Office © 2017 Detector Electronics Corporation. All rights reserved. Toll-free: 800.765.3473 6901 West 110 Street Det-Tronics manufacturing system is certified to ISO 9001— Fax: 952.829.8750 Minneapolis, MN 55438 USA the world’s most recognized quality management standard. det-tronics@det-tronics.com www.det-tronics.com...

Table of Contents

Save PDF