Gesint RL Manual

Gesint RL Manual

Level transmitter for reed probe
Hide thumbs Also See for RL:

Advertisement

Quick Links

Technical data
Power supply:
Power consumption:
Input signal:
Reed probe voltage:
Analogue output:
Output impedance:
Relay output:
Mechanical life:
Electrical life:
Contact rating:
Programming:
Protection:
Storage temperature:
Working temperature:
Relative humidity:
Installation:

Electrical connection:

Dimensions:
CE mark according to Directive 89/336/CEE, complies with the following harmonised
regulations:
EN50081-1,
EN
50082-2,
EN61000-4-4, EN61000-4-5, EN61000-4-6, EN61000-4-11 and Low Voltage Directive
73/23/CEE and subsequent modifications.
The warranty is valid for 12 months from purchase, and expires if instrument is improperly
used or not correctly installed on system.
GESINT S.R.L.
Via Perosi, 5 - 20010 Bareggio (MI) - ITALY
Tel. +39-02-9014633 - +39-335-6282615
Fax +39-02-90362295
GESINT
E-mail: info@gesintsrl.it - WWW.GESINTSRL.IT
®
24VAC/DC switching
2VA / 1,8W max
Potentiometric
5 Vdc
0/4-20mA or 0/2-10V
Max 750Ω (mA) or Min 1KΩ (V)
1 SPDT relay
7
min. 10
cycles
4
N.O. @ 3A 250VAC : 5x10
5
N.C. @ 2A 250VAC : 2x10
3A @ 30 VDC (resistive load)
3A @ 250 VAC (resistive load)
2 push buttons
IP20
from –30 to +80°C
from –20 to +60°C
from 0 to 85%, no condensate
35 mm DIN rail
Removable terminal board
90(H) x 35(L) x 60(P) mm
EN55022,
EN61000-4-2,
EN61000-4-3,
Warranty
Level transmitter
GESINT
for reed probe
®
Electrical connection
It is recommended to use a connection cable of at least 0,5mmq
section and a maximum length of 250mt. Connection cables must
have separate run from power cables.
If the reed probe is installed upside-down, that is with the output
connector near the minimum level, the connection polarity
(PIN 4 and 6) must be inverted to obtain an output matching the
level measured.
In order to use voltage output (0-10V) pin 7 and 8 must be
connected together.
RL
RL transmitter convert the level measure from a
GSH reed probe and a magnetic float in a
4-20mA or 0-10Vdc analog output signal.
The output signal of the instruments is
proportional to the distance between minimum
and maximum point set during calibration.
The transmitter is supplied with 1 relay output
that can be used as level threshold or alarm.
Digital calibrations and settings with 2 push
buttons.
Rev.2

Advertisement

loading
Need help?

Need help?

Do you have a question about the RL and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Gesint RL

  • Page 1: Electrical Connection

    ® Input signal: Potentiometric Reed probe voltage: 5 Vdc RL transmitter convert the level measure from a Analogue output: 0/4-20mA or 0/2-10V GSH reed probe and a magnetic float in a Output impedance: Max 750Ω (mA) or Min 1KΩ (V) 4-20mA or 0-10Vdc analog output signal.
  • Page 2 LED signalling Relay settings It is possible to use the relay output as level threshold or alarm in case the reed probe is GREEN LED (Power): not sensing the magnetic float.  ON: transmitter is powered and working  Fast blinking: programming mode In order to access the 2 programming buttons, remove the front cover of the transmitter.