USER MANUAL “Aquarius Plus” UNI EN ISO 9001-2015 n° 9115.BRMO BRAGA MORO SISTEMI DI ENERGIA S.p.A VIA LUDWIG VAN BEETHOVEN N.24 20092 CINISELLO BALSAMO (MI) Tel.: +39 02 51 67 22 01 Fax: +39 02 51 67 22 13 mailto:sales@bragamoro.com www.bragamoro.com...
USER MANUAL “Aquarius Plus” UNI EN ISO 9001-2015 n° 9115.BRMO 1. DOCUMENT CHECK SECTION Drawing Written by Role Date Alessandri David Technical Staff 29-03-17 Control Control by Date Role Alessandri David Technical Staff 29-03-17 Approved Approved by Role Date Abbondio Adelio...
USER MANUAL “Aquarius Plus” UNI EN ISO 9001-2015 n° 9115.BRMO 1. Preface Thank you for purchasing our UPS, it is safe and reliable, little maintenance is required. Read this manual carefully and completely. It includes safety and operating installation instructions.
USER MANUAL “Aquarius Plus” UNI EN ISO 9001-2015 n° 9115.BRMO Description UPS (Uninterruptible Power Supply) is a device that allows continuity in the supply of loads in alternating current, but also has protection and monitoring functions. The UPS plays a very important role in the supply of computers and the computer network to which the computer is possibly connected.
Page 6
USER MANUAL “Aquarius Plus” UNI EN ISO 9001-2015 n° 9115.BRMO battery. In this case the group does not switch on to supply loads until the voltage and frequency of the main source fall within the allowed ranges. 11. When there is no power supply, the UPS can be started by battery. This feature is called cold start and is used to supply loads in emergencies.
USER MANUAL “Aquarius Plus” UNI EN ISO 9001-2015 n° 9115.BRMO Safety Instructions This chapter mainly introduces safety marks and notes on the 1KVA-3KVA online UPS series. Read this chapter carefully before using the equipment. 2.2 Safety There are dangerous voltages and high temperatures inside the UPS. During the installation and maintenance operation, please follow the safety instructions in the interior and the relevant laws, otherwise personal injury or damage to the equipment may occur.
USER MANUAL “Aquarius Plus” UNI EN ISO 9001-2015 n° 9115.BRMO Dangerous: Indicates the risk of serious injury or death or serious damage to the equipment Attention: Indicates the risk of serious injury or damage to the equipment. Warning: Indicates risk of injury or equipment damage.
Page 9
USER MANUAL “Aquarius Plus” UNI EN ISO 9001-2015 n° 9115.BRMO Illustration 2: Rear panel 3.2 The principle of the product Illustration 3: Principle outline File name Date Page PUT9I001 PUT9I1K5 Code PUT9I002 9 di 32 DF19009A 05/04/19 PUT9I003 MD03006C - All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.
Page 10
Internal battery charger 1A,4 batterie PCS 7AH 3KVAS Internal battery charger 1A,6 batterie PCS 7AH Table 1: Aquarius model To request an expansion battery box, for long term backup contact the Braga Moro sales office, or write to the following E-Mail address: sales@bragamoro.com File name Date...
USER MANUAL “Aquarius Plus” UNI EN ISO 9001-2015 n° 9115.BRMO Installation 4.1 Unpacking and inspection 1. Unpack the UPS and check that there is no damage caused during transport. If any parts are damaged or missing, do not start the appliance and inform the carrier and report it to the service center.
Page 12
USER MANUAL “Aquarius Plus” UNI EN ISO 9001-2015 n° 9115.BRMO Illustration 6: mounting brackets for 2/3KVA File name Date Page PUT9I001 PUT9I1K5 Code PUT9I002 12 di 32 DF19009A 05/04/19 PUT9I003 MD03006C - All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.
Page 13
USER MANUAL “Aquarius Plus” UNI EN ISO 9001-2015 n° 9115.BRMO 4.4 Mounting of rack mounting brackets The following illustrations show how to fix the brackets on the groups, to perform a rack mount. The screws (SCREW A and B) shown in illustration 9 are from M4.
Page 14
USER MANUAL “Aquarius Plus” UNI EN ISO 9001-2015 n° 9115.BRMO 4.5 UPS output input connection the UPS to the mains and to the loads with the supplied power cable. 4.6 Connection to the high autonomy battery box Attention: Before installing the battery, make sure the UPS is turned off and its switch is open. Use all the precautions dictated by the safety rules at work, in order to avoid accidents.
USER MANUAL “Aquarius Plus” UNI EN ISO 9001-2015 n° 9115.BRMO The UPS can supply output voltage regardless of whether the power cord is connected to the power outlet. If you want the UPS not to supply output voltage, first open the circuit- breaker and then detach the network.
Page 16
USER MANUAL “Aquarius Plus” UNI EN ISO 9001-2015 n° 9115.BRMO Key setting function Consultation mode: Press and hold this key for more than 2 seconds: interface setting function. Mode setting function: Press the button for more than half a second (less than 2 seconds): Confirms the set option.
Page 17
USER MANUAL “Aquarius Plus” UNI EN ISO 9001-2015 n° 9115.BRMO Illustration 9: Example screen LCD display includes a section with numerical values, a graphic section of the power supplied, a graphic section of the fan status and a graphic section of the battery status.
Page 18
USER MANUAL “Aquarius Plus” UNI EN ISO 9001-2015 n° 9115.BRMO 5.4 operation 5.4.1 UPS start-up Starting the UPS, the Line Mode. Once the mains supply is connected, the UPS charges the batteries. The display will show that the output voltage is 0, which means that UPS cannot yet power the load. If you plan to use the bypass, you can set the bps "ON"...
Page 19
USER MANUAL “Aquarius Plus” UNI EN ISO 9001-2015 n° 9115.BRMO 5.4.3 Self-test/Mute modality By pressing the self-test / mute button for more than one second, the group will start the self- checking sequence. The LEDs will turn on and off in sequence. During this phase the UPS will check the quality of its circuits.
Page 20
USER MANUAL “Aquarius Plus” UNI EN ISO 9001-2015 n° 9115.BRMO Illustration 11: ECO ON Press the button to choose which ECO function to activate. The activated functions have the word ON, while the non-active functions the word OFF. To activate or deactivate the features, press the button for two seconds.
Page 21
USER MANUAL “Aquarius Plus” UNI EN ISO 9001-2015 n° 9115.BRMO To activate or deactivate the Bypass function by keeping the button pressed for at least half a second . The display will begin to flash. Illustration 13: Bypass ON To confirm the selection, keep the key pressed , for at least 2 seconds.
Page 22
USER MANUAL “Aquarius Plus” UNI EN ISO 9001-2015 n° 9115.BRMO Press the button again for half a second . Numerical values will appear under the word OPU. With the key choose the desired output voltage value. The selectable values are: 208V, 220V, 230V and 240V.
Page 23
USER MANUAL “Aquarius Plus” UNI EN ISO 9001-2015 n° 9115.BRMO Illustrazione 17: Potenza Finally, the measurement relating to the internal temperature of the group and those relating to the battery will be available: available voltage and capacity. 5.7 Run mode 5.7.1 Bypass mode...
Page 24
USER MANUAL “Aquarius Plus” UNI EN ISO 9001-2015 n° 9115.BRMO The green LED of the inverter is on. This condition remains if the input voltage is present and remains in the allowed ranges. 5.7.3 Battery mode The visual signals in Battery mode are as follows: The green LED of the inverter, the yellow LED of the battery and the red warning LED are on.
USER MANUAL “Aquarius Plus” UNI EN ISO 9001-2015 n° 9115.BRMO NOTE: THE ALARM CODES ARE INCLUDED IN THE APPENDICES OF THIS MANUAL. INFORMATION: This procedure must be carried out when a UPS with a generator (GE) is powered: ...
Page 26
2. If the acoustic signal is active, a critical state is present. 3. In the presence of one of the situations it is advisable to contact the Braga Moro customer service by sending an E-mail to: assistenza@bragamoro.com. Specifying the following data: •...
Page 27
USER MANUAL “Aquarius Plus” UNI EN ISO 9001-2015 n° 9115.BRMO 7.1 Alarm codes and related visual signals Appendix 1 Error codes Description Code Bus KO 00-19 Inverter KO 20-39 overtemperature 40-44 Short-circuit 45-49 Overload 50-54 KO output relay 55-59 Input NTC KO...
Page 28
USER MANUAL “Aquarius Plus” UNI EN ISO 9001-2015 n° 9115.BRMO Notifications Acoustic N° Status Comments warnings Line mode ● Nobody Voltage within the limits Voltage out of bounds ● ● ★ Every 4 seconds UPS in Battery mode Battery mode ●...
Page 29
8 hours. Insufficient backup Check the loads and remove the least UPS in overload time significant ones. Contact the Braga Moro service center Dated battery for battery replacement. The keys were not pressed Press the ON buttons simultaneously correctly There is a problem with...
“Aquarius Plus” UNI EN ISO 9001-2015 n° 9115.BRMO Reference standards The Braga Moro uninterruptible power supplies have been manufactured according to the regulations listed in the table in this paragraph and have obtained the CE mark in compliance with European standards.
USER MANUAL “Aquarius Plus” UNI EN ISO 9001-2015 n° 9115.BRMO performance Line mode Full load≥86% Full load≥88% Battery mode Full load≥84% Full load≥94% ≤3% (100% linear load) Output Voltage Distortion ≤5% (100% non-linear load) Battery voltage 24VDC 24VDC 48VDC 48VDC...
Page 32
USER MANUAL “Aquarius Plus” UNI EN ISO 9001-2015 n° 9115.BRMO PIN 1(hole)to computer serial port PIN 2(needle)to UPS serial port To acquire data from the group's serial port, the UPSILON2000 software must be installed on the computer. 12.2 Smart Slot The following smart cards can be installed in the UPS intelligent slot: USB intelligent card, SNMP card and relay card.