Product Manual Rosa Thermostat
EAE KNX Rosa Thermostat
Rosa Thermostat PM R1.0
EAE ROSA THERMOSTAT
Product Manual Rosa Thermostat
EAE Technology
www.eaetechnology.com
Page1 / 77
©

Advertisement

Table of Contents
loading

Summary of Contents for EAE ROSA

  • Page 1 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 EAE ROSA THERMOSTAT Product Manual Rosa Thermostat EAE Technology www.eaetechnology.com Page1 / 77 ©...
  • Page 2: Table Of Contents

    Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Content 1. General..................................4 2. Device Technology..............................4 2.1 Button Definitions..............................4 2.2 Connection Diagram............................4 2.3 Technical Data..............................5 2.4 Dimensions................................5 3. Communication Object Table............................6 4. Parameters and CommunicationObjects......................17 4.1General.................................
  • Page 3 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 4.4.5.4 Fan Coil..............................64 4.4.5.5 Split Unit..............................66 4.4.6Cooling Control Main Stages..........................67 4.4.7Cooling Control Additional Stages.........................67 4.4.8 Fan Control............................68 4.4.8.1 Parameter..........................68 4.4.8.2Communication Objects.......................... 69 Setpoints..............................70 4.5.1 Parameter............................71 4.5.2Communication Objects..........................73 4.6 Local Control................................
  • Page 4: General

    EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 1. General Extendable up to 4 folds, Rosa thermostats offer a wide range of functional flexibility with integrated programmable switches. Buttons on Rosa thermostats can be programmed to control lighting, shutter/blind drivers, speakers, make scene calls and mimic panic buttons.
  • Page 5: Technical Data

    Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Technical Data Protection Type IP20 EN 60529 Safety Class EN 61140 Supply Voltage Range 21-30V DC, Supply from EIB/KNX line Supply Voltage 20 mA Power Consumption 20 mA x 30V...
  • Page 6: Communication Object Table

    Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 3. Communication Object Table Number of Object Name Object Function Flags Bits General, operation Active Rocker 1, switch On/Off Rocker 1, shutter Up/Down Rocker 1, value[0,1] Send Rocker 1, value[0…255] Send Rocker 1, value[0…65535]...
  • Page 7 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Number of Object Name Object Function Flags Bits Button 1, value[0…65535] Send Button 1, value[-32768…32768] Send Button 1, value[0…4294967295] Send Button 1, value(4-byte float) Send Rocker 1, shutter...
  • Page 8 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Number of Object Name Object Function Flags Bits Button 2, value[0…4294967295] Send Button 2, value(4-byte float) Send Button 2, shutter Top Position Button 2, (Status) On/Off Button 2, shutter...
  • Page 9 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Number of Object Name Object Function Flags Bits Button 3, shutter Stop/Lamella Adj Button 3, value[0,1] On/Off Button 3, value[0…255] Send Button 3, value[0…65535] Send Button 3, value[-32768…32768] Send Button 3, value[0…4294967295]...
  • Page 10 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Number of Object Name Object Function Flags Bits Button 4, value[0…255] Send Button 4, value[0…65535] Send Button 4, value[-32768…32768] Send Button 4, value[0…4294967295] Send Button 4, value(4-byte float)
  • Page 11 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Number of Object Name Object Function Flags Bits Rocker 3, dimming Send CRWT Rocker 3, shutter Stop/Lamella Adj Button 5, dimming Send CRWT Button 5, shutter Stop/Lamella Adj...
  • Page 12 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Number of Object Name Object Function Flags Bits Button 6, dimming Send CRWT Button 6, shutter Stop/Lamella Adj Button 6, value[0,1] On/Off Button 6, value[0…255] Send Button 6, value[0…65535] Send Button 6, value[-32768…32768]...
  • Page 13 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Number of Object Name Object Function Flags Bits Button 7, value[-32768…32768] Send Button 7, value[0…4294967295] Send Button 7, value(4-byte float) Send Rocker 4, dimming Send CRWT Rocker 4, shutter...
  • Page 14 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Number of Object Name Object Function Flags Bits Button 8, value[-32768…32768] Send Button 8, value[0…4294967295] Send Button 8, value(4-byte float) Send Button 8, dimming Send CRWT Button 8, shutter...
  • Page 15 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Number of Object Name Object Function Flags Bits 54 Split Cool Error True/False 55 Current Temperature (°C / °F) Temperature 56 Current Setpoint (°C / °F) Temperature Operating Mode...
  • Page 16 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Number of Object Name Object Function Flags Bits 69 Fan Speed 3 Enable 70 Change Setpoint (°C / °F) 71 External Temperature Sensor (°C / °F) Temperature 72 Spot Temperature Sensor (°C / °F)
  • Page 17: Parameters And Communicationobjects

    Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Number of Object Name Object Function Flags Bits Setpoint Away (Status) (°C / °F) Temperature Setpoint Heating Away (Status) (°C / °F) 88 Setpoint Cooling Comfort (Status) (°C / °F) Temperature 89 Setpoint Cooling Night (Status) (°C / °F)
  • Page 18: Parameters

    Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 4.1.1 Parameters Parameter Settings Description In operation can be used to ensure that device is In Operation Telegram checked/unchecked alive and connected to KNX line. Visible when “In Operation Telegram” checked. Bit...
  • Page 19: 2Communication Objects

    Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 *[1] LCD Backlight Control: Additional to the LCD backlight control through “LCD Backlight Control” parameter, LCD has another method to control backlight. Pressing “Fan Speed Button” for 3 seconds will dim the backlight to %10 brightness.
  • Page 20: Rockers

    Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Figure3 4.2.1 Rockers Number of rockers should be selected in “General” tabs in parameters and should be chosen as compatible with the device that will be configured. Rockers are numbered from top to bottom, topmost rocker as Rocker 1, below it Rocker 2, and so on.
  • Page 21 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 4.2.1.1.1 Switch Selecting “Switch” as “Rocker Function “enables to send 1 bit On(1)/Off(0) telegrams to the group address that is linked to respective communication object. Status LEDs can be configured to notify the current status of operation directly with buttons or using communication objects for confirmation to show current status.
  • Page 22 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 4.2.1.1.2 Communication Objects Object Name Function Data Type Flags 1 bit Rocker1 – Telegr.switch On/Off DPT 1.001 On/Off telegrams will be sent to group address that is linked to this communication object.
  • Page 23 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 4.2.1.2.1 Parameters Parameter Setting Description Left Button Brighter (On) Right Button Select which rocker button is on Mode of Darker(Off) / Left Button Brighter(Off) Right button and which rocker button is off...
  • Page 24 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 4.2.1.2.2 Communication Objects Object Name Function Data type Flags 1 bit Rocker 1 – switch On/Off DPT 1.001 On/Off telegrams will be send to group address that is linked to this communication object.
  • Page 25 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Shutter/Venetian Blind Function Firstly, select which rocker button is used for “up” operation, which rocker button is used for “down” operation by “Mode of Buttons” parameter. Both buttons have two functions as “short press” function and “long press”...
  • Page 26 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 4.2.1.3.1 Parameters Parameter Setting Description Mode of Buttons LeftUpRightDown Select which rocker button is “Up Left Down Right Up Button” and which rocker button is “Down Button”. Control Type Shutter/Venetian Blind Selects control type of blinds.
  • Page 27 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 4.2.1.3.2 Communication Objects Object Name Function Data Type Flags Rocker1-shutter Up/Down 1 bit UP/DOWN DPT 1.008 This communication object will be used to start blind movement. Rocker1 –...
  • Page 28 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 4.2.1.4.1 Parameters Parameter Setting Description LED Permanently Off LED always off Function of Led LED Permanently On LED always on Operation Indication Status LED of the pressed rocker button will be on for the time period selected at “Light...
  • Page 29 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 4.2.1.4.2 Communication Objects Object Name Function Data type Flags Button 1 – value[0,1] True/False 1 bit DPT 1.002 Enabled when “Data Type” selected as “1 bit value” Button 1– value[0…255] Send 1 byte DPT 5.010...
  • Page 30: Push Buttons

    Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Object Name Function Data type Flags Button 1- long - value(4-byte float) Send 4 byte DPT 14.068 Enabled when “Long Press Data Type” selected as “4 byte value [floating point] Button 1- long - value[0…4294967295]...
  • Page 31 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 4.2.2.1Switch Selecting “Switch” as “Push Button Function“ enables to send 1 bit On(1)/Off(0) telegrams to the group address that is linked to respective communication object. Pressing and releasing buttons can be assigned to different commands (On, Off, Toggle and No Command).
  • Page 32 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 4.2.2.1.2 Communication Objects Object Name Function Data Type Flags Button 1 switch 1 bit DPT 1.001 On/Off telegrams will be send to group address that is linked to this communication object.
  • Page 33 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Dimming - Step Wise Type When push button pressed (and not released) and pressed duration exceeds “Long Press Duration” time, a step value level configured in “Step Value” parameter will be send using respective communication object.
  • Page 34 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 4.2.2.2.2 Communication Objects Object Name Function Data type Flags Button 1 – On/Off 1 bit switch DPT 1.001 On/Off telegrams will be send to group address that is linked to this communication object.
  • Page 35 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Shutter/Venetian Blind Function When “Controller Type” configured as “Shutter/Venetian Blind”, lamella operations of blind control will be enabled as “short press” function of the push button. Also, “Button Function”...
  • Page 36 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 4.2.2.3.1 Parameters Parameter Setting Description Up / Down / Toggle Push Button Function Chapter 4.2.2.3 Shutter/Venetian Blind Control Type Selects control type of blinds. Blind/Roller/Awning Shutter/Venetian Blind function includes “Lamella Control”...
  • Page 37 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 4.2.2.4 Value Operation Figure 11 Push button can be configured to send predefined values from different data types. Additionally, a long press request can be enabled to be used as a secondary value operation.
  • Page 38 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Parameter Setting Description [0...255]”. Visible when “Data Type” selected as "1-byte percent Value 0…80…100 value [0%…100%]". Visible when “Data Type” selected as “2-byte value [- Value -32768…0…32767 32768…32767]”.
  • Page 39: Temperature Sensor

    Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Parameter Setting Description Visible when “Long Press Data Type” selected as “2- Value -32768…0…32767 byte value [-32768…32767]”. Visible when “Long Press Data Type” selected as “2- Value 0…65535 byte value [0…65535]”.
  • Page 40: Parameters

    Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 4.3.1 Parameters Parameter Function Description Select temperature unit. After selection all temperature Celsius(°C) / Temperature Unit related parameters and communication objects should Fahrenheit(°F) be enter as selected unit.
  • Page 41 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Parameter Function Description External Sensor from Internal or External Sensor on LCD Screen Internal Sensor This parameter allows to show current temperature Temperature Shown on from Internal or External Sensor via KNX object External Sensor “Current Temperature.
  • Page 42: 2Communication Objects

    Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 4.3.2 Communication Objects No Object name Function Data Type Flags 2 byte Current Temperature (°C) Temperature DPT 9.001 2 byte Current Temperature (°F) Temperature DPT 9.027 Communication objects DPT should be decided according to the selected temperature unit. Temperature telegrams will be sent when a temperature change defined at “Minimum Difference”...
  • Page 43: Thermostat

    Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Thermostat Figure 13 Parameters related to thermostat control should be configured in this tab. Whether thermostat will be used for heating, cooling or both and heating, cooling or both with additional stage should be selected here.
  • Page 44 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Parameter Setting Description Selects whether control mode Automatic switchover will be controlled by Switchover Method Manual (via Object) thermostat or controlled manually using Manual (Local and via Object) related communication object or local button.
  • Page 45: Communication Objects

    Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Communication Objects 4.4.2 Object Name Function Data Type Flags Operating Mode Select Operating Mode 1 byte DPT 5.011 Comfort mode Enable 1 bit DPT 1.003 Night Mode Enable 1 bit DPT 1.003...
  • Page 46: Control Types

    Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Control Types 4.4.3 Thermostat uses 5 different control types; these are PI Continuous, PI-PWM, On/Off, Fan Coil and Split. This control types can be used for Additional Control as well. Operation of every control type will be explained in the following chapters.
  • Page 47: Additional Stages

    Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 4.4.3.1.5 Split Unit Split controller does not control directly the split AC, so ambient temperature must be controlled by split AC’s controller. Therefore, “Ambient Temperature” and “Setpoint Temperature” of split ACs communication objects should be linked to “Current Temperature”...
  • Page 48: Heating Control Main Stages

    Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Heating Control Main Stages 4.4.4 Selection of the heating control type, parameters of the selected control type should be configured here. 5 Heating Control types are available which are PI Continuous, PI PWM, On/Off, FanCoil and Split Unit.
  • Page 49 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 4.4.4.1.1 Parameters Parameter Setting Description Invert the output of the controller. For Normal / Inverse Control Value example, if normal output is %80, then inverted output is %20.
  • Page 50: Pi Pwm

    Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Parameter Setting Description This parameter shown when the Reverse Differential Action "Controller Algorithm" is selected as 5…15…255 x 0.1 Band "Alternative PI". Reverse Differential Action Band, given value multiplied by 0.1 Table 29 4.4.4.1.2...
  • Page 51 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 4.4.4.2.1 Parameters Parameter Setting Description Invert the output of the controller. For Control Value Normal / Inverse example, if normal output is 1, then inverted output is 0.
  • Page 52: On/Off

    Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 *[4] “PWM Cycle” and “Minimum Control Signal” parameters should be configured considering the limitations of the actuator. For example; when actuator is Solenoid valve with a response time of 120 seconds, - PWM cycle configured as 10 minutes (Chapter 4.4.3.1.2)
  • Page 53: Fan Coil

    Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 4.4.4.3.1 Parameters Parameter Setting Description Invert the output of the controller. For example, if Control Value Normal / Inverse normal output is 1, then inverted output is 0.
  • Page 54 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 4.4.4.4.1 Parameters Parameter Setting Description Invert the output of the controller. For Normal / Inverse Control Value example, if normal output is %80, then inverted output is %20.
  • Page 55: Split Unit

    Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Parameter Setting Description This parameter shown when the Reverse Differential Action "Controller Algorithm" is selected as 5…15…255 x 0.1 Band "Alternative PI". Reverse Differential Action Band, given value multiplied by 0.1 Table 35 4.4.4.4.2...
  • Page 56: Heating Control Additional Stages

    Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 4.4.4.5.2 Communication Objects Object Name Function Data Type Flags Split Heat On/Off 1 bit DPT 1.001 Visibleif “Send On/OffatControl Mode Switchover” parameter enabled. This communication objectis not a control object, it will send “True”...
  • Page 57 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 4.4.5.1.1 Parameters Parameter Setting Description Invert the output of the controller. For Control Value Normal / Inverse example, if normal output is %80, then inverted output is %20.
  • Page 58 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Parameter Setting Description divided by 1000. This parameter shown when the Reverse Differential Action "Controller Algorithm" is selected as 5…15…255 x 0.1 Band "Alternative PI". Reverse Differential Action Band, given value multiplied by 0.1...
  • Page 59: Pi Pwm

    Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 4.4.5.2 PI PWM Figure 15 For more information how the PI parameters and PWM cycle should be selected Chapter 4.4.3.1.2 4.4.5.2.1 Parameters Parameter Setting Description Invert the output of the controller. For...
  • Page 60 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Parameter Setting Description This parameter enables the Heat Protection via using Spot Temperature Spot Heat Protection checked / unchecked Sensor. Spot Temperature sensor must be enabled in "Temperature Sensor"...
  • Page 61 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Parameter Setting Description Additional stage will be deactivated depends on temperature difference Deactivation Difference 1...10...255 x 0.1K between current temperature and (Close to Setpoint) setpoint. Given value will be multiplied with 0.1...
  • Page 62: On/Off

    Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 4.4.5.3 On/Off Figure 16 Heating control parameters for on/off controller type should be configured here. For more information about on/off controller read Chapter 4.4.3.1.3. 4.4.5.3.1 Parameters Parameter Setting Description Invert the output of the controller.
  • Page 63 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Parameter Setting Description Additional stage will be deactivated depends on temperature difference Deactivation Difference 1...10...255 x 0.1K between current temperature and (Close to Setpoint) setpoint. Given value will be multiplied with 0.1...
  • Page 64: Fan Coil

    Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 4.4.5.4 Fan Coil Figure 17 Heating control parameters for fan coil controller type should be configured here. For more information about on/off controller read Chapter 4.4.3.1.4. 4.4.5.4.1 Parameters...
  • Page 65 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Parameter Setting Description This parameter appears when the "Sending of Control Value" is selected as "Cyclic and Minimum Change 1...4...25 % Change". It determines minimum control output change for transmitting the additional heating control value.
  • Page 66: Split Unit

    Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Parameter Setting Description Additional stage will be activated depends Activation Difference on temperature difference between current 10...40...255 x 0.1K (Away from Setpoint) temperature and setpoint. Given value will be multiplied with 0.1...
  • Page 67: 6Cooling Control Main Stages

    Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 4.4.5.5.1 Parameters Parameter Setting Description Time period to send heating control value over Cyclic Sending Interval 1…5…255 min “Additional Heating Control Value” communication object. Fan Speed of the Additional Fan Coil can be...
  • Page 68: Fan Control

    Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 4.4.8 Fan Control Figure 19 When heating control or cooling control selected as “Fan Coil” or “Split Unit”, “Fan Control” tab will be visible. Note that, if both heat and cool controllers configured as “Fan Coil” or “Split Unit”, only one set of communication objects and parameters for fan control will be enabled.
  • Page 69: 2Communication Objects

    Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 4.4.8.2 Communication Objects No Object Name Function Data Type Flags 1 bit 65 Fan Speed 0 Send DPT 1.002 "1" value will be transmitted from this group object hhen the fan speed is "0" or OFF.
  • Page 70: Setpoints

    Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Setpoints Figure 25 EAE Technology www.eaetechnology.com Page70 / 77 ©...
  • Page 71: Parameter

    Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 4.5.1 Parameter Parameter Setting Description Control values will be sent cyclically only or cyclical Send Setpoint Cyclic / Cyclic and Change and "Minimum Change" of heating control value is reached.
  • Page 72 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 Parameter Setting Description COMFORT MODE This parameter allows to set default Setpoint Setpoint 0...25...99 °C / °F Temperature of Comfort Mode. Setpoint Heating 0...25...99 °C / °F Multi Setpoint parameter must be enabled to see these parameters.
  • Page 73: 2Communication Objects

    Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 4.5.2 Communication Objects No Object Name Function Data Types Flags 1 bit 50 Regulation On/Off DPT 1.002 Thermostat regulation can be turned on/off using this communication object. Also, when regulation controlled through “Operating Mode Button”, the regulation status will be sent using this communication...
  • Page 74 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 No Object Name Function Data Types Flags Setpoint temperature for Comfort mode can be set by "Setpoint Comfort" communication object. If Multi Setpoint is enabled, Setpoint will be changed by "Setpoint Heating Comfort" group object.
  • Page 75 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 No Object Name Function Data Types Flags If Multi Setpoint is enabled, Setpoint will be changed by "Setpoint Cooling Night" group object. 2 byte 84 Setpoint Cooling Away °C DPT 9.001...
  • Page 76 Product Manual Rosa Thermostat EAE KNX Rosa Thermostat Rosa Thermostat PM R1.0 No Object Name Function Data Types Flags DPT 9.027 2 byte Setpoint Heating Away (Status) °C DPT 9.001 2 byte Setpoint Heating Away (Status) °F DPT 9.027 Setpoint temperature for Away mode can be transmitted(read) using the "Setpoint Away Status"...
  • Page 77: Local Control

    Product Manual Rosa Thermostat Series EAE ROSA THERMOSTAT ROSA THERMOSTAT PM R1.0 4.6 Local Control Figure 26 4.6.1 Parameters Parameter Setting Description Setpoint Button Enable / Disable Enable/Disable setpoint buttons on thermostat. Fan Speed Button Enable / Disable Enable/Disable fan speed button on thermostat.