CARBON MONOXIDE (CO) DETECTOR
WITH RELAY OUTPUT
RGS 328
Eng.
• Conforms to CEI EN 50291 & CEI EN 50292 standards
• Incorporates internal sensing element of electrochemical cell type
• LEDs for power supply, pre-alarm, alarm & sensing element fault
• SPDT relay output
• Power supply 230 V~ ; protection IP 42
1. APPLICATION
Carbon monoxide (CO) is undoubtedly one of the most toxic gases for the human body. Its danger, moreover,
is compounded by the fact that it is odourless, colourless and non-irritating and so absolutely undetectable by
human senses.
The RGS 328 detector is able to detect the presence of carbon monoxide in the air and can, therefore, ensure the
safety of persons in domestic spaces where there are gas appliances.
An output relay can activate devices for changing the air and turning off, where possible, the combustion (e.g. by
closing a shut-off valve for appliances operating on combustible liquids or gases).
2. TYPICAL INSTALLATION
3. TECHNICAL DATA
Power supply
Frequency
Consumption
Protection
Electromagnetic compatibility
Ambient temperature :
– operating
– storage
Permitted ambient humidity
Weight
Output SPDT relay :
– type
– maximum switching voltage
– maximum switching current
We reserve the right to make changes without notice
COSTER
230 V ~ ± 10%
Acoustic alarm
50...60 Hz
Sensor stabilisation time
2,5 VA
IP 42
Sensing element:
CEE 93/68
– electrochemical cell
0...40 °C
Alarm & pre-alarm thresholds:
– 20...+ 60 °C
– alarm
classe F DIN 40040
250 g
stagno a gas inerte
250 V ~
– pre-alarm
5 (1) A
G 227 - RGS 328 Eng.
25.11.08 MZ REV. 01
Sixth-Sense ECO-Sure/2e
< 50 ppm: no alarm
50...100 ppm: 60 minutes
100...300 ppm: 10 minutes
> 300 ppm:immediate alarm
time between exceeding
threshold and alarm
G 227
25.11.08 MZ
REV. 01
85 db / 1 meter
120 s
"threshold + time"
1
Need help?
Do you have a question about the RGS 328 and is the answer not in the manual?
Questions and answers