Note: Photograph is for illustrative purposes only.
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Model DDX-LP PrePak System
2" (50mm), 2
3" (80mm), 4" (100mm),
6" (150mm) & 8" (200mm)
Low Pressure Dry-Pipe System
10 psi - 26 psi (0.7 bar - 1.8 bar)
Recommended System Pressure
General Description
The Reliable Model DDX-LP PrePak (Sizes 2" (50mm),
2½" (65 mm), 3" (80 mm), 4" (100 mm), 6" (150mm) and
8" (200mm)) is a completely self-contained, supervised dry
pipe system that can be readily installed within a floor space
of less than 7 square feet (0.65 square meters). Refer to Fig.
1 for cabinet dimensions. Installation of the DDX-LP PrePak
requires just three piping connections: the water supply, the
sprinkler system and the drain. Reference locations of these
piping connections are shown in Fig. 1. One electrical sup-
ply connection is required. Note: The Model DDX-LP PrePak
is available with an optional 115V VAC (60Hz) air compres-
sor.
Full assembly drawings for the units are available on the
Reliable Automatic Sprinkler Company website (www.reli-
ablesprinkler.com).
The heart of the Reliable Model DDX-LP PrePak is the
Model DDX-LP Dry Pipe Valve. The Reliable Model DDX-LP
Dry Pipe Valve is a hydraulically operated, differential-type
valve designed for use as a primary control valve in a low
pressure dry pipe valve system. The trim set used with the
Model DDX-LP Dry Pipe Valve contains the Reliable Model
LP Dry Pilot Actuator releasing device. This Actuator allows
the system air or nitrogen pressure to be considerably less
than the water supply pressure (see Table A). The following
benefits are a direct result of lower air pressure:
1. In refrigerated area systems, lower air pressure de-
creases the possibility of ice plugs that could impede
or prevent the flow of water to fire sprinkler heads in
the event of fire.
2. Lower air pressure allows for smaller capacity, lower
cost dehydration equipment, where required.
3. Lower air or nitrogen pressure can reduce water de-
livery time when the system actuates, and in some
cases, may eliminate the need for an accelerator.
4. For systems supplied with nitrogen, low supervisory
pressure reduces the quantity of nitrogen required to
maintain the system pressure.
Bulletin 748 July 2019
/
" (65mm),
1
2

Advertisement

Table of Contents
loading

Summary of Contents for Reliable DDX-LP PrePak

  • Page 1 4. For systems supplied with nitrogen, low supervisory pressure reduces the quantity of nitrogen required to maintain the system pressure. Note: Photograph is for illustrative purposes only. Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523...
  • Page 2: Listings And Approvals

    Nitrogen pressure in the sprinkler system piping which will cause the Model LP-Dry Pilot Actuator to open. The opening Alarm Pressure switch Potter, 5400928 of this device allows the Model DDX-LP PrePak valve to flow Nitrogen Pressure Switch Potter, 5400930 water into the system piping.
  • Page 3 Fig. 1...
  • Page 4 Table B. hammer” in the water supply piping of the valve can cre- If the Reliable DDX-LP PrePak is to be used with Nitrogen, ate pressures in excess of the rated pressure and should a Nitrogen kit is available as an option. A pressure switch is be avoided by all necessary means.
  • Page 5: System Electrical Requirements

    All 24 VDC electrical connections in the Reliable Model 1. Close the main valve controlling water supply to the DDX-LP PrePak are translated to a water tight terminal box Model DDX-LP PrePak deluge valve. Also, close the mounted on the inside of the enclosure. All field wiring con- two ¼”...
  • Page 6 14. Slightly open the main valve controlling water supply and open the main drain. to the Model DDX-LP PrePak Deluge Valve. This will 2. Verify that the pushrod chamber supply valve is open, begin to fill the deluge valve beneath the clapper with allowing water to enter the pushrod chamber.
  • Page 7 Model DDX-LP Low Pressure Dry Pipe System Valve Legend (Note: Some items omitted for clarity) Fig. 2...
  • Page 8 Fig. 3...
  • Page 9 Fig. 4...
  • Page 10 Ordering Information: PrePak Part Number Configuration 655 U 3 0 0 Y Z 0 DDX-LP PrePak Valve Releasing/Control Size/System Trim Type Solenoid Valve Air Compressor System Air Devices Panel Side Control Valve 2 = 2” 0 = None 0 = None...