Table of Contents
loading
Need help?

Need help?

Do you have a question about the EASYLAB TCU3 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Trox EASYLAB TCU3 Series

  • Page 1 Installation and operating manual GB/en EASYLAB controller Serie TCU3...
  • Page 2 TROX GmbH Heinrich-Trox-Platz 47504 Neukirchen-Vluyn Germany Telephone: +49 (0) 2845 202-0 Fax: +49 (0) 2845 202-265 E-mail: trox@trox.de Internet: www.trox.de M375EV0, 2, GB/en 06/2019 © TROX GmbH 2017 EASYLAB controller Serie TCU3...
  • Page 3: Table Of Contents

    Table of contents General information........4 Cabling............21 Safety and correct use......6 Commissioning........22 General safety notes........6 Maintenance..........25 Correct use..........7 Safety............25 Incorrect use..........7 Operation and maintenance...... 25 Residual risks..........7 Zero point correction........25 Technical data..........
  • Page 4: General Information

    It is essential that these individuals read and fully understand this manual before starting any work. TROX Technical Service The basic prerequisite for safe working is to comply with the safety notes and all instructions in this To ensure that your request is processed as quickly manual.
  • Page 5 Section VI, Warranty Claims, of the Delivery and Payment Terms of TROX GmbH. The Delivery and Payment Terms of TROX GmbH CAUTION! are available at www.troxtechnik.com. Potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
  • Page 6: Safety And Correct Use

    Safety and correct use Safety and correct use Electric shock hazard! General safety notes Disconnect the power supply before you open the device. DANGER! Only skilled qualified electricians are allowed to Risk of injury from the damper blade of the work in areas marked as having electrical voltage.
  • Page 7: Correct Use

    Ä on page 11 shut-off position, supply or extract air and for fume cupboards in combination with a TROX air terminal unit. For safety related applications you should check whether then safety measures are required, such Indoor use for ventilation and air conditioning ...
  • Page 8: Technical Data

    Technical data Technical data Technical data Supply voltage 24 V AC ±15% 50-60 Hz 24 V DC ±15% Do not use 24 V AC and 24 V DC power supplies at the same time! Optional: 230 V AC mains supply, only with the EM-TRF expansion module; optional: 230 V AC mains supply with UPS, only with the EM-TRF USV expansion module Power rating The maximum power required depends on the construction of the controller.
  • Page 9 Technical data Dimensions Fig. 1: Dimensions ① Keep clear to provide access When combined with TAM, TVRK, TVR, TVA, TVZ, TVJ or TVT EASYLAB controller Serie TCU3...
  • Page 10: Transport, Storage And Packaging

    Expansion modules as ordered (see delivery  note) Operating and installation manual  TCU3 is usually factory mounted to a TROX VAV terminal unit. If any expansion modules have been ordered, the controller is factory fitted with these modules and shipped as a complete unit.
  • Page 11: Product Description

    Product description Product description Pressure monitoring Volume flow control The target pressure is monitored by the controller, if the actual value deviates from the configured pres- sure deviation, the following signal is emitted: The red LEDs (on opposite sides of the con- ...
  • Page 12: External Signaling Of Setpoint Deviation

    Product description External signaling of setpoint deviation The monitoring signals can be forwarded externally (only with optional equipment) Monitoring of volume flow rate or room pres- sure Display on the control panel (BE-SEG and/or  BE-LCD): – Red light and sound (flow rate below set- point) –...
  • Page 13: Interfaces And Signal Lamps On The Controller Casing

    Product description Interfaces and signal lamps on the controller casing Fig. 3: Controller casing Status LEDs Colour Name Description Error LED on Up to 3 s: Switch-on procedure. Permanently: Switch-on procedure error LED blinking Error; for detailed diagnosis use EasyConnect software LED blinking slowly Undefined equipment function;...
  • Page 14 Product description External interfaces Name Connection Description point for Contact 500 mm Sash Connection for a volt-free switch contact used to monitor the maximum (X1) operational sash opening (to EN 14175, only for fume cupboard controllers) Connection point for: Terminal-1 (X2) Control panel 1 Terminal-2 (X3) Control panel 2 EasyLAB control panel, e.g.
  • Page 15: Interfaces And Signal Lamps In The Controller Casing

    Product description Interfaces and signal lamps in the controller casing Fig. 4: Interfaces and signal lamps on the PCB Name Description Valve connection Connection point for expansion module EM-AUTOZERO Analogue input 1 (AI1) Connection point for the integral diaphragm pressure transducer, analogue voltage 0-10 VDC, 10 mA max.
  • Page 16 Communication cable termination is active Switch OFF Communication cable termination is inactive Terminal 3 Connection for TROX HPD actuator Do not connect PD here Ä ‘List of terminal connections’ on page 29 For details on the electrical data for each connection see...
  • Page 17: Installation

    Installation Installation Alternative installation position of the dia- phragm pressure transducer Installation orientation The installation orientation of the controller is critical because of the diaphragm pressure transducer; approved installation orientations are shown on a sticker (Fig. 5) on the controller casing. Fig.
  • Page 18 Installation Turn the diaphragm pressure transducer by 90°. Fig. 7: Tubing Check all connections and make sure that the tubes and wires of the transducer are properly connected and have not been kinked. Connect any disconnected wires on the PCB: Valve (1) - Connection to ‘Valve’...
  • Page 19 Installation Wall installation For restricted spaces you can detach the controller from the VAV terminal unit and install it on the wall next to the terminal unit or anywhere else nearby; to fix the controller on a wall, you can use a mounting bracket (Part no.
  • Page 20: Tube Connection On The Pressure Transducer

    Wiring Wiring Tube connection on the pressure transducer Safety instructions Room pressure control – supply air Personnel: Skilled qualified electrician  DANGER! Danger of death due to electric current! Danger of electric shock! Do not touch any live components! – Switch off the supply voltage and secure it against being switched on accidentally before working on the unit.
  • Page 21: Notes On Wiring

    Wiring Notes on wiring Polarity of the power supply Use only cables that are designed for the supply When connecting the supply voltage, the polarity at voltage for which they will be used. The length and 24 V AC and 24 V DC must be observed for all con- cross section as well as any contact resistance may trollers! increase voltage losses.
  • Page 22: Commissioning

    SEG control panel into one of the interfaces shown above. This requires a Bluetooth interface on the PC or Using a PC or notebook and the TROX notebook (either integral hardware or EasyConnect configuration software, you external, e.g. with a USB stick).
  • Page 23 When the zero point correction is finished, reconnect the measuring tubes. Adaptation of the actuator (only for fast-running actuator TUS) For air terminal units with TROX type HPD actuator (A00000067751), adaptation must be carried out during commissioning. This ensures that any incorrect position, e.g. due to shipping or installation, is corrected.
  • Page 24 Commissioning For adaptation, the actuator moves to the end positions and then automatically switches to control mode. Functional test To complete commissioning, perform a func- tional test of the controller using the Easy- Connect software, taking into account the project specifications for the required oper- ating modes.
  • Page 25: Maintenance

    Maintenance Maintenance Zero point correction Safety To ensure continued accuracy of volume flow meas- urements, zero point correction of the diaphragm The system owner is responsible for operational pressure transducer is required in regular intervals reliability. (not required for controllers with expansion module EM-AUTOZERO).
  • Page 26: Decommissioning

    Decommissioning Decommissioning Removing the electronic controller DANGER! Danger of electric shock! Do not touch any live components! Electrical equipment carries a dangerous elec- trical voltage. – Only skilled qualified electricians are allowed to work on the electrical system. – Switch off the power supply before working on any electrical equipment.
  • Page 27: Appendix

    Appendix EASYLAB controller Serie TCU3...
  • Page 28 Wiring example circuit breaker EASYLAB controller Serie TCU3...
  • Page 29 List of terminal connections EASYLAB controller Serie TCU3...
  • Page 30 EASYLAB controller Serie TCU3...
  • Page 31 EASYLAB controller Serie TCU3...
  • Page 32 EASYLAB controller Serie TCU3...

Table of Contents