Trox EN-Ex Installation Manual

Cav controllers

Advertisement

Quick Links

Product overview
Fig. 1: EN-Ex
Scale
Volume flow rate scale lock
Crossbar
Blade connector for equipotential bonding
(2 ground straps and 2 blade connectors are
part of the supply package)
Cam plate
Leaf spring
Bellows inlet
Bellows
Damper blade
Installation manual
CAV controllers
EN-Ex
CAV controllers EN-Ex
GB/en
Important notes
Information on the installation manual
This manual enables operating or service personnel
to correctly install the product described below and
to use it safely and efficiently.
It is essential that these individuals read and fully
understand this manual before starting any work.
The basic prerequisite for safe working is to comply
with the safety notes and all instructions in this
manual.
The local regulations for health and safety at work
and general safety regulations also apply.
Correct use
CAV controllers of Type EN-Ex are used for con-
stant volume flow control in ventilation and air con-
ditioning systems. They can be used for supply air
and extract air systems in the following areas with
potentially explosive atmospheres:
II 2G Ex h IIC T6 Gb
II 2D Ex h IIIC T80 °C Db
Test certificate
Do not use the CAV controller with an electric
actuator!
Do not use CAV controllers in extract air systems in
commercial kitchens unless the extract air has been
cleaned as much as possible with high-sufficiency
aerosol separators; see VDI 2052.
The installation of air terminal devices in humid
rooms, areas with potentially explosive atmos-
pheres or rooms with dust-laden or aggressive air
has to be assessed for each individual case.
TROX GmbH
Heinrich-Trox-Platz
47504 Neukirchen-Vluyn
Germany
Phone: +49 (0) 2845 2020
Fax: +49 (0) 2845 202-265
E-mail: trox@trox.de
http://www.troxtechnik.com
TÜV 05 ATEX 7159 X
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EN-Ex and is the answer not in the manual?

Questions and answers

Summary of Contents for Trox EN-Ex

  • Page 1 ④ ⑨ ⑤ ⑥ ⑧ ⑦ CAV controllers of Type EN-Ex are used for con- stant volume flow control in ventilation and air con- Fig. 1: EN-Ex ditioning systems. They can be used for supply air ① Scale and extract air systems in the following areas with ②...
  • Page 2: Important Notes

    The manufacturer does not accept any liability for any work in order to reduce health or safety haz- damages resulting from: ards to the minimum. Non-compliance with this manual  Incorrect use  Operation or handling by untrained individuals  Unauthorised modifications  CAV controllers EN-Ex...
  • Page 3: Transport And Storage

    If possible, take the product in its transport  packaging up to the installation location. Use only lifting and transport gear designed for  the required load. CAV controllers EN-Ex...
  • Page 4: Technical Data

    Technical data Dimensions and weight B₂ EN–EX 400 x 200 Ø13×20 B₁ Fig. 2: EN-Ex B₂ EN–EX 400 x 200 B₁ Fig. 3: EN-Ex-D (with acoustic cladding) Nominal size Nom- Nom- EN-Ex EN-Ex-D inal inal [mm] [mm] width height [mm]...
  • Page 5: Installation

    Bends, junctions or a narrowing or widening of the Junction Junction duct cause turbulence that may affect measure- ment. Duct connections, e.g. branches off the main duct, must comply with EN 1505. Some installation situations require straight duct sections upstream. 1,5B 1,5H CAV controllers EN-Ex...
  • Page 6 Ensure that all components are clean before you install them. If necessary, clean them thoroughly. If you have to interrupt the installa- tion procedure, protect all openings from the ingress of dust or moisture. CAV controllers EN-Ex...
  • Page 7 Be careful to not damage the controller accidentally: Handle the unit with care.  Lift the unit only by lifting the entire casing.  CAV controllers EN-Ex...
  • Page 8 This requires a cable (by others). In any case, the ductwork has to be con- nected to the terminal point for equipoten- tial bonding of the building. CAV controllers EN-Ex...
  • Page 9: Initial Commissioning

    No further measurement or adjustment is necessary. Volume flow rate setting ranges Nominal size [l/s] (m³/h) 200 × 100 300 × 100 300 × 150 1512 300 × 200 1872 400 × 200 3024 500 × 200 3312 CAV controllers EN-Ex...
  • Page 10: Maintenance And Cleaning

    Remove contamina- tion; if the controller has been damaged, or if there is any corrosion, replace the controller. Check the fixing of the controller and of the  connected ductwork. Check the equipotential bonding.  CAV controllers EN-Ex...
  • Page 11 Incorrect or faulty replacement parts pose a risk to health and safety, and their use can cause Do not use cleaning agents that contain  malfunction, damage to property and total failure chlorine. of equipment. – Use only original replacement parts from TROX. CAV controllers EN-Ex...
  • Page 12: Declaration Of Conformity

    Declaration of conformity Declaration of conformity CAV controllers EN-Ex...