Recycling And Disposal; Safety Precautions; Transportation, Reception And Storage; Mounting - Metso LCP9H Installation Maintenance And Operating Instructions

Local control panels for vg9000h
Table of Contents

Advertisement

4
Maximum distance for power supply:
1200 m
Ex ia IIC T4/T5/T6 Gb:
Ui ≤ 9.8 V
Ii ≤ 47 mA
Pi ≤ 120 mW
Ci ≤ 3.3 nF
Li ≤ 15 µH
Ex ic IIC T4/T5/T6, Ex nL IIC T4/T5/T6 Gc:
Ui ≤ 25.2 V
Ii ≤ 150 mA
Pi ≤ 650 mW
Ci ≤ 25 nF
Li ≤ 201 µH
Ex ic IIC T4/T5/T6 and Ex nL IIC T4/T5/T6 Gc:
Uo ≤ 8.8 V
Io ≤ 42 mA
Po ≤ 93 mW
Co ≤ 45 nF
Lo ≤ 45 µH
Communication cable
The communication cable between the LCP9H_ and the
VG9000H must be a shielded, twisted pair, 4-wire
cable. The shield must be connected to housings in
both ends. The maximum distance between the
VG9000H and the LCP9H_ is 60 m.
Cable requirements:
- Signals and corresponding ground wires twisted
- Wire thickness min. 0.8 mm
- Shield coverage > 85 %
- Test voltage > 1500 V (Ex requirement)
- Resistance < 50 Ω/km
- Capacitance < 50 pF/m
Compatible isolators
MTL
5021
P&F
KFD0-SD2-Ex1.1045
STAHL
9176/.0-14-0
ABB
V17132-520
Dimensions
Without buttons and cable glands:
250 mm x 200 mm x 114 mm (h x w x d)
With buttons and cable glands (approx.):
270 mm x 200 mm x 137 mm (h x w x d)
Material
316L stainless steel
Weight
2.8 kg
Approvals
ATEX II 2G Ex ia T4/T5/T6 Gb
ATEX II 3G Ex ic T4/T5/T6 Gc
ATEX II 3G Ex nL T4/T5/T6 Gc
EMC
Acc. to EN61000-4-2 ... 4-6, 4-8
1.6

Recycling and disposal

Most local control panel parts can be recycled if sorted
according to material. Most parts have material mark-
ing. In addition, separate recycling and disposal
instructions are available from the manufacturer.
The Local Control Panel may also be returned to the
manufacturer for recycling and disposal. There will be a
charge for this.
1.7

Safety precautions

CAUTION:
Do not exceed the permitted values!
Exceeding the permitted values may cause dam-
age to the local control panel and to equipment
attached to the panel.
Damage to the equipment and personal injury may
result.
CAUTION:
During maintenance or commissioning when the
device cover is open, ensure that water does not
go inside the enclosure.
CAUTION:
Do not operate the device with the cover open or
removed!
Electromagnetic immunity is reduced.
NOTE:
Avoid earthing a welding machine in close proximity
to the LCP9H_.
Damage to the equipment may result.
2
TRANSPORTATION, RECEPTION
AND STORAGE
The Local Control Panel is a sophisticated instrument,
handle it with care.
Check the Local Control Panel for any damage
that may have occurred during transportation.
Store the Local Control Panel preferably indoors
and keep it away from rain and dust.
3

MOUNTING

3.1

General

4 pcs. 10 mm holes on the back side. Mounting parts
are provided, including M8 bolts. The diameter of the
holes is 194 mm (vertical) and 230 mm (horizontal). See
Section 10 DIMENSIONS for details.
The open / close button face is user selectable (open/
close). Both face plates are included in the delivery.
7 LCP9H 70 en