Download Print this page
e-controls e-Room Panasonic Stand-Alone Instruction Sheet

e-controls e-Room Panasonic Stand-Alone Instruction Sheet

Advertisement

Quick Links

e-Room® Panasonic Stand-Alone
Stand-alone controller for rooms with climate VRF Panasonic system
PAW-RE2C3-WH – White frame
PAW-RE2C3-GR – Gray frame
e-Room® Panasonic Stand-Alone is a device desig-
ned to perform a global room automation, providing
a high comfortable level, an energy cost reduction,
and a better integration of the rooms in the building.
The device enables or stops an indoor unit climate,
lighting and curtains control and manages the state of a
secondary zone climate when room changes into occupied
or unoccupied state, reducing energetic consumption and
effi ciency integrating climate into global room control.
The device is a compact unit that includes a large
backlight display screen, a built in temperature sen-
sor, pushbuttons on the front panel, and inputs and
outputs for a global control of the main room services.
Product description
Introduction
Room controller e-Room® Panasonic Stand-Alone is a device
designed to perform a global room automation for hotels,
offi ces or homes with climate systems based on VRF Panasonic
indoor units. The device has a communication protocol which
allows managing a climate indoor unit without needing other
remote controls, interacting with the unit when occupied or
unoccupied room is detected.
The device has digital/analogue inputs which are used to
detect the occupancy room state through a keycard contact
or motion sensor and door contact, in addition of a window
contact which is used to stops climate when the window is
open. It is possible to control a second zone climate on separate
rooms like bedroom and bathroom throughout an analogue
input connecting an external temperature sensor. The device
includes various relay outputs to control diff erent functions like
lighting state, motorized curtains or blinds and a second zone
climate.
There are four possible operating modes on the device; each
one has a diff erent operating and input/output confi guration,
which must be selected depending on the installation
confi guration that better suits to the operating requests.
Indoor Unit model 2 Ways / 3 Ways
The device should be confi gured to control the Indoor Unit
installed. The 2 ways (2P) unit confi guration allows user
selecting between COOL and HEAT throughout HEAT and COOL
pushbutton while the 3 ways (3P) machine confi guration allows
user selecting between HEAT, COOL and AUTO. On AUTO mode,
the machine automatically decides between HEAT/COOL
depending on ambient temperature and set-point temperature
confi gured.
Mode OFF/ECO
OFF/ECO mode is used to stop the device or change climate
into ECO mode when room turns to unoccupied. If ECO mode
is confi gured, set-point temperature automatically changes
into economy value preset on HEAT or COOL parameter
confi guration.
User and real setpoint temperatures
The device has diff erent maximum and minimum set-point
temperatures to limit values to defi ne by user. Maximum set-
INS1114507000-0
Electronic Intelligent Controls, S.L.
C/ Murcia, 35 F
1
08830 Sant Boi de Llobregat
Barcelona, Spain
point temperature is used to limit maximum value on heat
mode and minimum set-point temperature is used to limit
minimum value on cool mode.
Maximum/minimum
maximum and minimum values that user can set throughout
the pushbuttons.
Maximum/minimum real set-point temperatures are maximum
and minimum values that perform to the machine. Real values
override values which user sets.
AutoOn Mode
The device has an automatic switch on mode to prevent that
a zone temperature exceeds a preset maximum temperature
value in summer or a minimum temperature value in winter. For
that reason the device has a temperature value for AutoOn in
HEAT mode and another temperature value for AutoOn in COOL
mode, as well as two parameters to enable each operating
mode in a separated way.
The AutoOn mode is automatically activated when the ambient
temperature is 1 degree diff erent from AutoOn set-point value
and automatically deactivates when temperature is 2 degree
diff erent from the set-point value.
AutoOn mode is only activated when room is unoccupied
and if the device is confi gured to changes into OFF state with
unoccupied room.
Indicated temperature values are in Celsius degrees.
Climate restart when power-up
The device can be confi gured in order to automatically restart
climate after voltage drops. On the other hand, it is possible to
confi gure the climate mode with which is desired the device
restarts.
Blinds control
The devices includes a function in order to automatically
raise blinds up when room changes into occupied state or
automatically lower blinds down when room changes into
unoccupied state.
This function is especially useful if it is desired that blinds raise
up when user enters in the room, or that blinds lower down to
preserve room temperature when the user leaves the room.
Tel.: +34 93 652 55 21
www.e-controls.es
Fax: +34 93 652 55 22
info@e-controls.es
Instruction Sheet
user
set-point
temperatures
© 2014 e-Controls®
are

Advertisement

loading

Summary of Contents for e-controls e-Room Panasonic Stand-Alone

  • Page 1 The device has diff erent maximum and minimum set-point preserve room temperature when the user leaves the room. temperatures to limit values to defi ne by user. Maximum set- INS1114507000-0 © 2014 e-Controls®...
  • Page 2: Inputs And Outputs

    1 second will automatically activate raising motor AUTO or fan coil speeds icon just in case the device is in INS1114507000-0 © 2014 e-Controls®...
  • Page 3 - If closing the door room changes into occupied state, Throughout P25 parameter it can be confi gured the automa- output will remain activate while room will be on occu- tically lowering blinds down when room changes into Unoccu- pied state. pied state. INS1114507000-0 © 2014 e-Controls®...
  • Page 4: Device Operating Modes

    - Do not work on the wiring with wet hands. - Do not open or drill through the device. - Keep the device and the supply wires away from moisture and dust. - Use a damp cloth to clean the device. INS1114507000-0 © 2014 e-Controls®...
  • Page 5: Display Description

    Table 2 Device confi guration The device includes an easy to use confi guration menu to set To confi gure the device see the “Confi guration Sheet” document. operating parameters and adjust installation needs. INS1114507000-0 © 2014 e-Controls®...
  • Page 6: Wiring Diagram

    Blinds Up 13 14 General Lighting 15 16 Not used Outputs: Max 5A/250Vac OUT1 OUT2 OUT3 OUT4 e-Room Panasonic ® Inputs: Dry Contact Model: Stand-Alone Indoor Supply: R1 R2/100mA Unit IP20 Indoor Unit Down Lighting Window Blinds INS1114507000-0 © 2014 e-Controls®...
  • Page 7: Technical Features

    Panasonic Stand-Alone aluminium frame ........