Ct1750 Wiring Spec - S&S Northern Merlin CT1750 User Manual

Gas proving & interlock system
Table of Contents

Advertisement

Merlin CT1750
5

CT1750 Wiring Spec

1.
POWER: Mains Electrical Input 100-240VAC.
2.
GAS VALVE: Gas Solenoid Valve Power Output, 100-240VAC.
3.
FAN 1 PD SW: Fan 1 pressure differential switch or current switch. VOLT FREE INPUT
4.
FAN 2 PD SW: Fan 2 pressure differential switch or current switch. VOLT FREE INPUT
5.
BMS OUT: output contacts. Normally Open, Common and Normally Closed.
6.
PRESSURE SENSOR: Gas pressure transducer input
7.
FIRE PANEL (Supplied by others). VOLT FREE INPUT
8.
CO SENSOR: power supply (purchased separately).
9.
CO2 SENSOR: power supply (purchased separately).
10.
TEMP SENSOR: Fusible Links (purchased separately). VOLT FREE INPUT
11.
EM REMOTE: Remote emergency stop buttons and Fire Alarm input. VOLT FREE INPUT
12.
12VDC: Permanent output (Normally used to power a PM2 Current Monitor).
13.
FAN 1 0-10VDC output.
14.
FAN 2 0-10VDC output.
15.
EM SEL: Emergency fan selection
16.
FP SEL: Fire panel fan selection
17.
BMS SEL: Enable / disable
18.
Fan 1 & Fan 2 Speed Calibrator buttons.
19.
Gas Pressure Proving Enable/Disable, Fill Time & Prove Time selection
Rev: 07