Optional plate Technical specifications µ General α The ND800PA valve controller is suitable for rotary and slid- ing stem valves. Actuator connection In accordance with VDI/VDE 3845 standard (S1) or as an option compatibility with other NE-series (S2). To replace an existing NE/NP positioner,...
Page 4
Enclosure Approvals Temp. ≤ +75 °C (+67 °F): Material: Anodized aluminium alloy Protection class: IP65, NEMA 4 and 4X Cenelec EEx ia IIC T5/T6 (pending), Temp. ≤ +50 °C (+122 °F): Mechanical position indicator: on cover CSA Class I, Division 2, Groups A, B, C Pneumatics ports: 1/4 NPT and D (pending)
Attach the bracket (1) to the ND800PA. Attach the bracket (1) to the actuator. The shaft (40) of If the ND800PA is supplied with valve and actuator the tubes are the ND800PA must fit into the draught piece (2) shown mounted and the ND800PA adjusted in accordance with the in Fig.
Mount the controller loosely onto the controller mounting Mounting on linear actuators withMetso bracket. Automation or IEC 60534 mounting face Adjust the controller mounting bracket and the controller See Sections 10.5, 10.6. so that the controller is at 90° to the centre line of the Connect an airset directly to the actuator and position the actuator and the controller feedback lever is horizontal actuator at its mid-stroke position (see serial plate for...
Terminals CAUTION: Do not exceed the permitted supply pressure of the ND800PA! Table 1 provides the recommended tube sizes in accordance with actuator sizes. Tube sizes are the minimum values allowed. For supply air choose a tube one size bigger. Operating times can be tested by the PDM.
Page 8
DOUBLE-ACTING ACTUATOR 1. Self closing. Default setting: PFA = CLO ROT = cC ( lose valve to lockwise) A0 = % (acc. to valve type) cLo = 2 % 2. Self opening. Setting: PFA = OPE ROT = cC ( lose valve to lockwise) A0 = % (acc.
Chapter 6. The ND800PA stays in the selected operation mode during the Now the ND800PA will work with basic settings including 2 ± 0.5 % g and d settings. signal cutoff margins to secure full closing of the valve.
Table 3. Dead angle as percentage Control valve related settings The basic factory settings of the ND800PA assume a positioner fail Valve series action to be closing the valve and a clockwise closing direction for Valve size the position sensor. The setpoint cut-off CLOSE is set to 2 ± 0.5 %...
When cLo appears on the display, press the r key and the current default value as a percentage (%) appears on the The maintenance requirements of the ND800PA valve controller display. The Metso Automation’ standard default value is depend on the service conditions, for instance, the quality of instrument air.
Spool valve Circuit board pack Before removing the spool valve (4) the prestage (3) must be taken Disassembly off. (See Section 5.1) Loosen the M8 screw (66) and turn the position indica- tor (65) outwards from the feedback shaft. Disassembly Unplug all wire connectors from the circuit board (5) and Unscrew the M4 screws (99, 4 pcs.) and remove the spool the signal wires from the terminal block (35).
PDM communication. See the instruc- Tighten the M3 screws. tions in the ND800PA User’s guide. Install a 0,1 mm (0.004 in) thick gauge strip between the sensor and the spiral. Press the sensor against the spiral, without using unnecessary force, and tighten the screws (116) evenly.
Table 4 lists the error messages shown on the LCD display and their by the PDM. The error message is displayed until the cause of error explanations. is eliminated and the ND800PA unit is cold-started, i.e. the fieldbus is momentarily disconnected. Cold-start can also be done using PDM.
Section 4.3 and Fig. 7 the actuator did not move or was stuck during calibration ND800PA/actuator mounting is incorrect, see Figs. 4, 5, 15 and Sections 10.2-10.6 spool valve sticks prestage is defective PDM trouble shooting is explained in the ND800PA User’s Guide.
ND800/K00 (WITH LIMIT SWITCHES) 10.1.3 Technical specifications 10.1.3.1 ND800/K00 10.1 Introduction Microswitch type: OMRON D2VW-5 (05) 10.1.1 General description OMRON D2VW-01 (06) (gold plated contacts) ND800 can be equipped with limit switches. ND800/K00 has 2 microswitches. Protection class IP67 Limit switches are used for electrical position indication of the valves and other devices.
10.2 Installing ND800/K00 on a valve controller 10.5 Removal of the limit switch ND800/K00 for accessing the valve controller The limit switch can be installed on an existing valve controller. Before the protective cover (46) can be removed the limit switch must be detached.
11.5 Mounting parts for D/R linear actuators LEVER ARM IN MID-STROKE POSITION DISTANCE FROM THE CENTER OF FEEDBACK ARM TO THE CENTER OF ACTUATING PIN 3.57 2.87 2.50 1.00" UP TO 5.00" 1.61 STROKE @ 70° ROTATE 1.07 0.80 35° 0.71 3.50 60°...
11.7 Connections 11.7.1 Connection diagram for ND800/K05 and ND800/K06 LIMIT SWITCH (.../K06B) A = Open (LS2) VALVE CONTROLLER (ND800) K = Closed (LS1) PG13,5 ../K06B (with limit switch) Connection diagram shows limit switch when actuator is in intermediate position. Switch A (upper) is activated at the open limit of the travel and switch K (lower at the cloised limit. Micro switches OMRON D2VW-01, gold plated contacts Ambient temperature -40...+85 °C / -40...+185 °F...
11.7.2 Device gland receptacles +Voltage, brown - Voltage, blue Shield, black ND84.../...P1 = male eurofast type WEIDMÜLLER 945565, PG13.5/M12 +Voltage, brown - Voltage, blue Shield, grey ND84.../...P2 = male minifast type TURCK RSFV48/13.5...
Not appplicable with double acting actuators. gauge, scale bar/psi/kPa, basic material bras, nickel plated, housing Single action, linear motion, applicable to Metso Automation stainless steel, glycerine filled. Specified on the option sticker. Filter D/R series diaphragm actuator. Not applicable to attachment size 5 m.
Page 32
Metso Field Systems Inc. Europe, Levytie 6, P.O.Box 310, 00811 Helsinki, Finland. Tel.int +358 20 483 150. Fax int. +358 20 483 151 North America, 4300 Windfern, Houston, TX 77041, USA, Tel. int +1-832-590-5000, Fax. int. +1-832-590-5060 North America, 3100 Medlock Bridge Road, Suite 250, Norcross, GA 30071, USA Tel. int. + 1 770 446 7818 Fax int. + 1 770 242 8386 Latin America, Av.
Need help?
Do you have a question about the ND800PA and is the answer not in the manual?
Questions and answers