Electric Flow Rate, Number And Cross-Section Of Power Connectors, Fuse Protection - Dimplex ASCARI MA 12 Installation And Servicing Instructions

Hide thumbs Also See for ASCARI MA 12:
Table of Contents

Advertisement

3.1- Electric flow rate, number and cross-section of the power
connectors, fuse protection
3.1.1 - Electric datas
ASCARI 12
3.1.2 - Number and cross-section of connectors
Follow local existing regulations regarding electric connections
Electric connections to mains must be installed according to local and national regulations, which generally
specify:
• Type of connectors :
- Type of slipcover
- Number and cross-section of wires,
- etc...
• Type of installation :
- Magnetic interferences inside bundles,
- Ambient temperature,
- Open or covered wires,
- Length of cords,
- etc...
Example: Cord type U1000, loose in open air rack, ambient temperature 20°C, lenght
Boiler
ASCARI 12
Boiler
Maximum output P1
Maximum
output P1
12 kW
Ascari - 12kW -page 12 -
12 kW
IMPORTANT
MINIMUM cross-section for each connector in mm²
and number of connectors for above example
Ph = Phase = 16²
N = Neutral = 16²
Amperes for each phase
230 V mono
52 A
230 V mono
2 x 16² + T *
15 m.