Lydall Affinity User Manual page 25

Custom chiller
Table of Contents

Advertisement

Problem
Compressor
Discharge pressure too high
turns on and off
automatically
Condenser fan(s) not on
Refrigeration high pressure cut-out
set to automatic
Temperature
Loose wire
display reads
incorrectly
Broken RTD
Microprocessor failure
Microprocessor
5 second delay has not timed out
does not work
Microprocessor programmed
incorrectly
Microprocessor failure
O:MANUALS\D4207 (05/17/2002)
Possible Cause
Possible Remedy
Check Facility Water for blockage
Check motor(s) and wiring
Check settings
Disconnect power to unit, then
check wiring
Replace RTD
Replace microprocessor
Wait at least 5 seconds after turning
on
Reprogram microprocessor - Call
Lydall
Replace microprocessor

Advertisement