PLC Input Table
Input
Type
0
Auxiliary
Contact
1
Auxiliary
Contact
2
Level Switch
3
Spare
4
Pressure
Switch
5
Pressure
Switch
6
Flow Switch
7
Level Switch
8
Level Switch
9
Pressure
Switch
10
Selector Switch
11
Selector Switch
12
Flow Switch
13 -14
Spare
15
Auxiliary
Contact
16
Relay
17
Switch
18
Reset Switch
19
Spare
O:\MANUALS\D6629 (10/03/2002)
Description
Pump 1 Overload
Pump 2 Overload
Refrigerant Low
Level
N/A
Low Suction
Pressure
High Discharge
Pressure
Process Flow Loop
1
Loop 1 Low Level
Loop 2 Low Level
High Pressure
Warning
Pump 2 ON/OFF
Pump 1 ON/OFF
Process Flow Loop
2
N/A
Compressor
Overload
Phase Reverse
Relay
Local/Remote
Switch
Alarm Reset
N/A
Status OFF
Overload
Overload
Level > Setpoint
N/A
Pressure < Setpoint
Pressure > Setpoint
Flow < Set-point
Level > Setpoint
Level > Setpoint
Pressure < Setpoint
Pump 2 OFF
Pump 1 OFF
Flow < Setpoint
N/A
Overload
Phase
Loss/Reversal
Local
Normal
N/A
Status ON
No Overload
No Overload
Level < Setpoint
N/A
Pressure > Setpoint
Pressure < Setpoint
Flow > Set-point
Level < Setpoint
Level < Setpoint
Pressure > Setpoint
Pump 2 ON
Pump 1 ON
Flow > Setpoint
N/A
No Overload
Normal
Remote
Resets Faults
N/A