socomec SUNSYS PCS2 Series Installation And Operating Manual
socomec SUNSYS PCS2 Series Installation And Operating Manual

socomec SUNSYS PCS2 Series Installation And Operating Manual

Power conversion system and storage from 33 to 200 kva

Advertisement

2
SUNSYS PCS
Power Conversion System and Storage
from 33 to 200 kVA
EN
www.socomec.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SUNSYS PCS2 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for socomec SUNSYS PCS2 Series

  • Page 1 SUNSYS PCS Power Conversion System and Storage from 33 to 200 kVA www.socomec.com...
  • Page 3: Table Of Contents

    CONTENTS 1. CERTIFICATE AND CONDITIONS OF WARRANTY 2. SAFETY STANDARDS 2.1 DESCRIPTION OF SYMBOLS ..........7 2.2 ABBREVIATIONS .
  • Page 5: Certificate And Conditions Of Warranty

    For all cases, the CUSTOMER shall not be entitled to enforce the warranty unless it shall have fully paid for the SUPPLY. The warranty of SOCOMEC shall be strictly limited to its SUPPLY and does not extend to the equipment within which the SUPPLY is integrated nor to the performance of such equipment. SOCOMEC's liability shall be limited, in its discretion, to the repair or replacement at its expense in its factory of all or part of the SUPPLY recognized as defec- tive.
  • Page 6: Safety Standards

    CAUTION! If the unit is found to be damaged externally or internally, or any of the accessories are damaged or missing, contact SOCOMEC. Do not operate the unit if it has suffered a violent mechanical shock of any kind. NOTE! Install the unit in accordance with clearances in order to prevent access to handling devices and guarantee sufficient ventilation (refer to 'Environmental requirements' chapter).
  • Page 7: Description Of Symbols

    NOTE! Any use other than the specified purpose will be considered improper. The manufacturer/supplier shall not be held responsible for damage resulting from this. Risk and responsibility lies with the system manager. 2.1 DESCRIPTION OF SYMBOLS Comply with all internal and external precautions and warnings on labels and plates on the equipment. Symbols Description Protective earth terminal (PE).
  • Page 8: Abbreviations

    2.2 ABBREVIATIONS For the purpose of this document, the following abbreviations are used: Battery Energy Storage Battery Management System Electro Magnetic Compatibility Energy Management System Energy Storage System Human Machine Interface International Electrotechnical Commission Islanding Mode Insulation Monitoring Device Power Conversion System Protective Earth Power Management System Photovoltaic...
  • Page 9: Foreword

    3. FOREWORD Energy storage is the key solution to meeting the challenges of energy transition, using renewable energy and provid- ing energy cost reductions for the following 4 main applications. • Behind-the-Meter Energy Storage: Reduce peak consumption and maximise PV energy self-consumption. SUNSYS PCS² (IM) can limit the impact of increases in the electricity retail price by supplying the load to cut peak demand (peak shaving), maximising PV energy self-consumption at building or community level.
  • Page 10 • Grid support: Meet the challenge of demand-response energy balance. When directly connected to the grid, SUNSYS PCS (IM) improves stability and management of grid operators thanks to voltage and frequency regulation, load shifting, peak shaving and ancillary services for grid support. •...
  • Page 11: Sunsys Pcs² Ranges

    4. SUNSYS PCS² RANGES 4.1 IEC VERSIONS SUNSYS PCS² SUNSYS PCS² IM 33 kVA 66 kVA 100 kVA 132 kVA 200 kVA 33 kVA 66 kVA 100 kVA 132 kVA 200 kVA Internal transformer (TR version) External transformer (TL version) 4.2 UL VERSIONS SUNSYS PCS²...
  • Page 12: Environmental Requirements And Handling

    5. ENVIRONMENTAL REQUIREMENTS AND HANDLING 5.1 ENVIRONMENTAL REQUIREMENTS Install the unit in an equipment room. The room must be: • of a suitable size; • free from conductive, inflammable and corrosive items; • not exposed directly to sunlight. The floor must support the weight of the unit and guarantee its stability. The unit is designed for indoor rooms only. For information regarding ambient temperature, dimensions and weights refer to 'Technical specifications' chapter.
  • Page 13 • the maximum power required from the load (at 40 °C ambient temperature). Distance from the rear wall Space above the top panel Power 45 cm 100% 30 cm 25 cm 45 cm 20 cm 25 cm 45 cm 10 cm 25 cm SPACING-AIR FLOW Typical air extraction structure...
  • Page 14: Handling

    CABINET LAYOUT SUNSYS PCS SUNSYS PCS SUNSYS PCS 33 TR - 66 TR/TL - 100 TL 100 TR 132 - 200 TL 5.2 HANDLING • The packaging guarantees the stability of the unit during shipping and physical transfer. • The unit must remain in a vertical position during all shipping and handling operations. •...
  • Page 15: Floor Assembly

    5.3 FLOOR ASSEMBLY • PCS range 33 TR - 66 - 100 TR/TL: Remove the protective cover SUNSYS PCS Rear 3 0 cm • PCS 132 - 200 TL: Level adjustment and floor fixing Fixing bolt Level regulation bolt SUNSYS PCS2 Power Conversion System and Storage from 33 to 200 kVA - Ref.: IOMSUNPCXX04-EN 01...
  • Page 16: Installation

    5.4 INSTALLATION POWER MODULE INSERTION WARNING: before installing the module ensure that there is no voltage. NOTE: the module must be handled by at least two people (30.5 kg / 67.2 lb). WARNING! RISK OF TIPPING OVER: before carrying out any operations, ensure the SUNSYS is secured at the feet.
  • Page 17 • Position the cables in the hose clamp to enable correct module insertion. • Remove the Lexan protection on the connectors. SUNSYS PCS2 Power Conversion System and Storage from 33 to 200 kVA - Ref.: IOMSUNPCXX04-EN 01...
  • Page 18 • Place the module on the guides and insert it up to the limit starting by the lower one. In order to ensure the safety of installers, installers shall be at least two people to process the installation (30.5 kg / 67.2 lb). 30.5 67.2 •...
  • Page 19 • Position the Lexan protection and secure it. • Insert the module completely. • Tighten the screws to secure the module to the SUNSYS PCS SUNSYS PCS2 Power Conversion System and Storage from 33 to 200 kVA - Ref.: IOMSUNPCXX04-EN 01...
  • Page 20 • Connect the communication cable. Communication cable SUNSYS PCS2 Power Conversion System and Storage from 33 to 200 kVA - Ref.: IOMSUNPCXX04-EN 01...
  • Page 21: Procedure For Pcs 132 - 200 Tl

    5.4.2 PROCEDURE FOR PCS 132 - 200 TL • Open the doors: - With the appropriate key A open the lock, then pull the hook B and open the right door. - Unhook the upper latch C and lower latch D and open the left door. 135°...
  • Page 22 • Position the cables in the hose clamp to enable correct module insertion. • Remove the Lexan protection on the connectors. SUNSYS PCS2 Power Conversion System and Storage from 33 to 200 kVA - Ref.: IOMSUNPCXX04-EN 01...
  • Page 23 • Insertion of the lower three modules. Place the module on the guides and insert it up to the limit starting by the lower one. SUNSYS PCS2 Power Conversion System and Storage from 33 to 200 kVA - Ref.: IOMSUNPCXX04-EN 01...
  • Page 24 • Insertion of the upper three modules starting by the lower one. The Socomec shelf can be used to facilitate the insertion of the upper three modules. The shelf can be used only by persons authorized by Socomec. Keep this shelf available to service people for commissioning or future maintenance activities.
  • Page 25 - Make sure the shelf is properly assembled. • Place the module on the shelf. 30.5 67.2 SUNSYS PCS2 Power Conversion System and Storage from 33 to 200 kVA - Ref.: IOMSUNPCXX04-EN 01...
  • Page 26 • Place the module on the guides and insert it up to the limit. • Insert the connectors and secure them. SUNSYS PCS2 Power Conversion System and Storage from 33 to 200 kVA - Ref.: IOMSUNPCXX04-EN 01...
  • Page 27 • Position the Lexan protection and secure it. • Insert the module completely. • Remove the shelf. SUNSYS PCS2 Power Conversion System and Storage from 33 to 200 kVA - Ref.: IOMSUNPCXX04-EN 01...
  • Page 28 • Tighten the screws to secure the module to the SUNSYS PCS In PCS 132 TL, the unused slots are covered with a panel, do not remove this protection. SUNSYS PCS2 Power Conversion System and Storage from 33 to 200 kVA - Ref.: IOMSUNPCXX04-EN 01...
  • Page 29 • Connect the communication cable. Communication cable SUNSYS PCS2 Power Conversion System and Storage from 33 to 200 kVA - Ref.: IOMSUNPCXX04-EN 01...
  • Page 30 • Close the doors: - Close the left door and hook it with the both upper latch C and lower latch D. - Close the right leaf and close the hook B until the first clack. The door is locked but the lock is not activated. - To lock the door, press the coupling B fully.
  • Page 31: Electrical Installation

    6. ELECTRICAL INSTALLATION NOTE! Before carrying out any operations on the unit read the 'Safety standards' chapter carefully. 6.1 ELECTRICAL REQUIREMENTS The installation and system must comply with national plant regulations. The electrical distribution panel must have a sectioning and protection system installed for AC mains. The tables below show the connection features and the size of the protection devices recommended for correct installation.
  • Page 32 Centralised Fuses (example 100 kW) Distributed Fuses 132 - 200 kW - Centralised fuses is not allowed NOTE: If Socomec also provides the batteries the centralised fuse connection will be used and the fuses will be provided. WARNING: the SUNSYS PCS is designed for transient over-voltages in category II installations for AC terminals.
  • Page 33: Overview

    7. OVERVIEW 7.1 SWITCHES AND INTERFACES SUNSYS PCS 33 TR Communication slots Module A Detail 1 Module A output disconnection switch Detail 2 IEC320 AUX output for assistance IEC320 AUX power input SPD AC SUNSYS PCS output disconnection switch Module A input disconnection switch Detail 1 Detail 2: disconnection switches with fuse RS232/485...
  • Page 34 WIRING DIAGRAM FOR SUNSYS PCS 33 TR Batteries DC +/– X10A Option SPD-IN terminals terminals Option Option SPD-OUT 3Ph+PE AC main network SUNSYS PCS2 Power Conversion System and Storage from 33 to 200 kVA - Ref.: IOMSUNPCXX04-EN 01...
  • Page 35 SUNSYS PCS 66 TR Communication slots Module A Detail 1 Module A output disconnection switch Module B Module B output disconnection switch Detail 2 IEC320 AUX output for assistance IEC320 AUX power input SPD AC SUNSYS PCS output disconnection switch Module B input disconnection switch Module A input disconnection switch Detail 1...
  • Page 36 WIRING DIAGRAM FOR SUNSYS PCS 66 TR Batteries Batteries DC +/– DC +/– Common X10A X10B terminals terminals Option SPD-IN Option Option SPD-OUT 3Ph+PE AC main network SUNSYS PCS2 Power Conversion System and Storage from 33 to 200 kVA - Ref.: IOMSUNPCXX04-EN 01...
  • Page 37 SUNSYS PCS 100 TR Communication slots Detail 1 Q3 Module A output disconnection switch Q3 Module B output disconnection switch Q3 Module C output disconnection switch Q70 SUNSYS PCS output disconnection switch Module A Module B Module C Detail 2 Q1 Module A input disconnection switch IEC320 AUX power input Q1 Module B input disconnection switch...
  • Page 38 WIRING DIAGRAM FOR SUNSYS PCS 100 TR terminals terminals terminals Power supply network Batteries Batteries Batteries DC +/– DC +/– DC +/– X10A Common X10B X10C Option SPD-IN Option SPD-OUT Option 3Ph+PE 3Ph+PE AC main network AC main network SUNSYS PCS2 Power Conversion System and Storage from 33 to 200 kVA - Ref.: IOMSUNPCXX04-EN 01...
  • Page 39 SUNSYS PCS 66 TL Communication slots Detail 1 Module A output disconnection switch Module B Module B output disconnection switch Detail 2 Module C IEC320 AUX output for assistance IEC320 AUX power input Module B input disconnection switch Module A input disconnection switch Detail 1 Detail 2: disconnection switches with fuse RS232/485...
  • Page 40 WIRING DIAGRAM FOR SUNSYS PCS 66 TL Batteries Batteries DC +/– DC +/– Common X10A X10B terminals terminals Option SPD-IN Option 3Ph+PE AC main network SUNSYS PCS2 Power Conversion System and Storage from 33 to 200 kVA - Ref.: IOMSUNPCXX04-EN 01...
  • Page 41 SUNSYS PCS 100 TL Communication slots Module A Detail 1 Module A output disconnection switch Module B Module B output disconnection switch Module C output disconnection switch Detail 2 Module C IEC320 AUX output for assistance IEC320 AUX power input Module C input disconnection switch Module B input disconnection switch Module A input disconnection switch...
  • Page 42 WIRING DIAGRAM FOR SUNSYS PCS 100 TL Batteries Batteries Batteries DC +/– DC +/– DC +/– terminals terminals Common X10A X10B X10C Option SPD-IN Option 3Ph+PE AC main network SUNSYS PCS2 Power Conversion System and Storage from 33 to 200 kVA - Ref.: IOMSUNPCXX04-EN 01...
  • Page 43 SUNSYS PCS 132 - 200 TL Communication slots Module A Module A input disconnec- tion switch RS232/485 Upper Ethernet Network control pnale Module B RS232/Modem Module B input disconnec- tion switch Module A output disconnection switch RS232/485 Lower control Ethernet Network pnale Module C RS232/Modem...
  • Page 44 WIRING DIAGRAM OF SUNSYS PCS 132 - 200 TL terminals terminals Batteries Batteries Option Option SPD-IN SPD-IN Option SPD-OUT AC main network 1. Module A not present in PCS 132 TL 2. Module D not present in PCS 132 TL SUNSYS PCS2 Power Conversion System and Storage from 33 to 200 kVA - Ref.: IOMSUNPCXX04-EN 01...
  • Page 45: Diagram Of Main System Example For Version 100 Tr

    7.2 DIAGRAM OF MAIN SYSTEM EXAMPLE FOR VERSION 100 TR The SUNSYS PCS² system is constructed using power electronics modules. Each power module incorporates circuit protection, sine filter, cooling fans and EMI filtering as shown in the diagram below. • Example for PCS 100kW with transformer 1.
  • Page 46: Connections

    8. CONNECTIONS NOTE! Before carrying out any operations on the unit read the 'Safety standards' chapter carefully. 8.1 INPUT CONNECTION The SUNSYS PCS is connected to the batteries via the DC terminals. The SUNSYS PCS is connected to the AC mains via the AC power terminals. •...
  • Page 47 • Secure the signal cables supplied between the transformer cabinet and the PCS (only for 100 TR). • Use only cables supplied by SOCOMEC for bridging connections between transformer cabinet and PCS (only for 100 TR). • AC neutral is not used in this Power Conversion System.
  • Page 48 SUNSYS PCS 100 TR L1 L3 Signal L– L+ cables Cables supplied L1, L2, L3 Connection terminals for the main AC network Connection terminal for the protective earth wire L+, L- DC connection terminals for the batteries SUNSYS PCS 66 TL L–...
  • Page 49 SUNSYS PCS 100 TL L3 PE L– L+ L1, L2, L3 Connection terminals for the main AC network Connection terminal for the protective earth wire L+, L- DC connection terminals for the batteries SUNSYS PCS 132 - 200 TL L– L+ L–...
  • Page 50 For safety reason, the mounting of the protecting panels is compulsory. SUNSYS PCS range 33 TR - 66 - 100 TR/TL SUNSYS PCS 132 - 200 TL SUNSYS PCS2 Power Conversion System and Storage from 33 to 200 kVA - Ref.: IOMSUNPCXX04-EN 01...
  • Page 51 • Fix both the lateral bases SUNSYS PCS 132 - 200 TL SUNSYS PCS2 Power Conversion System and Storage from 33 to 200 kVA - Ref.: IOMSUNPCXX04-EN 01...
  • Page 52 AUXILIARY CONNECTION The SUNSYS PCS equipment is powered by a special single-phase voltage (refer to 'Technical specifications' chap- ter). The auxiliary voltage must be connected to the relevant socket. WARNING: risk of damage to the system if not observed! SUNSYS PCS 33-66 TR / 66-100 TL Power supply Interface...
  • Page 53: Instructions For Sunsys Pcs Tl Version

    8.2 INSTRUCTIONS FOR SUNSYS PCS TL VERSION The SUNSYS PCS TL versions require the installation of a transformer coupling to the mains, in addition to the AC input protection. Block diagram Mains AC input Transformer protection Grid transformer protection Grid protection 280/xxx V LV grid: MV grid: y/D...
  • Page 54: Control Panel

    9. CONTROL PANEL The control panel displays information regarding operating status, electrical measurements, access to control func- tions and configuration parameters. It includes a colour graphic display and a luminous status bar. Display UP button DOWN button Scrolls up through Scrolls down through the available menus/ the available menus/...
  • Page 55: Exception For Pcs

    9.1 EXCEPTION FOR PCS 132 - 200 TL The PCS 132 - 200 TL has two control panels: - the upper one controls the upper three power modules (Module A, Module B, Module C). - the lower one controls the lower three power modules (Module D, Module E, Module F). So, the first start-up procedure must be applied to both control panels ('First start-up' chapter) and both have to be used to monitor measurements, alarms, etc.
  • Page 56: Converter State Machine

    9.2 CONVERTER STATE MACHINE The SUNSYS PCS² implements the following state-machine concept: INIT SWITCHED-OFF ALARM ON / OFF DC source connected SYSTEM READY CHARGE / DISCHARGE CMD. Grid connected CHARGE / DISCHARGE At system power-on by the auxiliary power supply, the SUNSYS PCS² automatically enters the SWITCHED-OFF state: the Control Panel shows on the display the corresponding message “SWITCHED-OFF”...
  • Page 57: First Start-Up

    10. FIRST START-UP Before carrying out any operations on the unit read the 'Safety standards' chapter carefully. When the SUNSYS PCS is switched on for the first time the commissioning wizard is activated. The commissioning wizard is an interactive procedure that guides the user through the SUNSYS PCS ’s first start-up procedure.
  • Page 58 TRANSFORMER TYPE Set the type of transformer connected to SUNSYS PCS - SOCOMEC: if standard transformer is used. - External: if a custom transformer is provided by the customer. SUNSYS PCS2 Power Conversion System and Storage from 33 to 200 kVA - Ref.: IOMSUNPCXX04-EN 01...
  • Page 59 COUNTRY/GRID CODE SETTING Set the proper country/grid code according to local regulation. Grid code compatibility is always being upgraded, please contact SOCOMEC for grid code compatibility (subject to change without notice). NOTE: Once the country/grid code has been set the SUNSYS PCS will be automatically config- ured in compliance with the local standards.
  • Page 60: Menu

    Commissioning Code not inserted or Scheduled Inspection warning: machine inspection required. Call SOCOMEC support service Key icon: Displayed if the keypad has been locked. USB icon: Displayed if a USB memory stick is inserted. It must be formatted with a FAT32 fi le system.
  • Page 61 SUNSYS PCS Status (grey icon) Battery not present (green icon) SUNSYS PCS normal operation (yellow icon) SUNSYS PCS warning fl agged (red icon) SUNSYS PCS alarm fl agged Battery status SOC ≥ 87.5 % 62.5 % ≤ SOC ≤ 87.5 % 37.5% ≤...
  • Page 62: Menu Tree

    11.2 MENU TREE FIRST LEVEL SECOND LEVEL THIRD LEVEL COUNTERS DAILY TREND STATISTICS DOD DISTRIBUTION PRODUCTION GRAPHS DISCHARGE DURATION BATTERY TEMPERATURE PCS POWER AC MEASURES MEASUREMENTS BATTERY MEASUREMENTS SENSORS ALARMS ALARMS AND WARNINGS WARNINGS HISTORY LOG Start charge/discharge LOCAL PROCEDURE PCS calibration Stop procedure ALARM RESET...
  • Page 63 FIRST LEVEL SECOND LEVEL THIRD LEVEL PCS DESCRIPTION SYSTEM MODULE1 FIRMWARE VERSION MODULE2 SERVICE MODULE3 SERIAL NUMBER COMMISSIONING CODE UPGRADE HMI FIRMWARE UPGRADE FIRMWARE UPGRADE LANGUAGES 1. Password protected. 2. Shown only if Lead-Acid battery type is set. 3. Shown only if generic battery type is set. 4.
  • Page 64: Menu Description

    Step 4 The list of files in the \socomec\wyhi folder in the USB memory stick is shown. Select the file you want to install and follow the instructions displayed. Step 5 At the end of the process select Yes to restart the display.
  • Page 65 This menu contains the System Configuration Parameters, all of them are password protected and it contains param- eters for the PCS and battery configuration. Please contact SOCOMEC for the correct configuration of the PCS according to the specific plant requirements. Please contact SOCOMEC for the correct configuration of the Battery according to the specific battery installed.
  • Page 66: Operating Procedures

    12. OPERATING PROCEDURES NOTE: before carrying out any operations on the unit read the 'Safety standards' chapter care- fully. 12.1 SWITCHING ON SUNSYS PCS2 Power Conversion System and Storage from 33 to 200 kVA - Ref.: IOMSUNPCXX04-EN 01...
  • Page 67: Switching Off

    12.2 SWITCHING OFF Q70 isn't present on PCS 100kW, 132kW and 200kW. If the auxiliary power supply also needs to be cut off, disconnect the cable from the auxiliary power supply input socket or break the fuse connection. This procedure will switch off all the auxiliary SUNSYS PCS equipment, including the system controller and the control panel.
  • Page 68: Operating Mode

    13. OPERATING MODE 13.1 ENERGY SAVER MODE NOTE: The energy saver mode can be used preferably for applications of general Energy Shifting (charging during the day, discharging during the night). WARNING: The energy saver mode is not suitable for Peak Shaving applications, i.e. those that require wide and rapid power variations and very short reaction times.
  • Page 69: Standard Features And Options

    14. STANDARD FEATURES AND OPTIONS Features Type Description Availability This feature provides AC surge protection devices Electrical protection against AC Available as option (SPD AC) overvoltage This feature provides DC surge protection devices Electrical protection against DC Available as option (SPD DC) overvoltage Serial communication interface...
  • Page 70 SUNSYS PCS 132 - 200 TL RS232/485 JBUS RS232 RS232/485 JBUS RS232 RS232/485 C1 pin key RS232 pin key 1 Not connected 1 Reserved 2 RX for RS232 2 RX for RS232 3 TX for RS232 3 TX for RS232 4 Data + 4 Reserved 5 GND...
  • Page 71: Modbus Tcp Interface

    14.2 MODBUS TCP INTERFACE The SUNSYS PCS can be managed from remote stations using MODBUS TCP network protocol. See menu SETTINGS > CONNECTIVITY > PERIPHERALS > NETWORK PARAMETERS to Enable/Disable DHCP setting. Restart the HMI after modifying the parameters. IP Addresses can be changed only if DHCP is disabled. SUNSYS PCS 33 TR - 66-100 TR/TL Control...
  • Page 72: Adc Card

    14.3 ADC CARD This card manages four normally closed or normally open outputs and three digital inputs in configurable mode. • Electrical data. - Permitted rated current and voltage of normally open or normally closed contacts: 2 A 250 Vac depending on the terminal used.
  • Page 73: Serial Communication Interface

    14.4 SERIAL COMMUNICATION INTERFACE Isolated Serial RS232 DB9 and RS485 connectors are available on the card. Isolated Serial RS232 DB9 1 Reserved 6 Reserved 2 RX for RS232 7 Reserved 3 TX for RS232 8 Reserved 4 Reserved 9 Reserved 5 GND for RS232 Isolated RS485 If used in 132, or 200 TL the serial communication interface cards must be n°2.
  • Page 74: Signal Cables Route

    14.5 SIGNAL CABLES ROUTE 132 - 200 TL Cable fi xing points Signal conduct Power terminal area WARNING: Signal cables must not entry inside the power terminal area. SUNSYS PCS2 Power Conversion System and Storage from 33 to 200 kVA - Ref.: IOMSUNPCXX04-EN 01...
  • Page 75: Warnings And Troubleshooting

    15. WARNINGS AND TROUBLESHOOTING The alarm messages offer immediate diagnosis of any faults, malfunctions or breakdowns in the batteries. The following events are indicated: • Warning: non-serious alarm condition that causes the unit stop. This can be reset automatically. • Alarm: serious alarm conditions that cause the unit stop. These alarm conditions require a manual reset. Alarm and warnings are divided into two categories: •...
  • Page 76 System warnings Warning Cause Remedy Module 3 on Alarm Module 3 stopped by alarm. Check Module 3. Unit warnings Warning Cause Remedy The unit is reducing the power Check the other alarms and/or visual Unit in Derating supplied/ drawn by the network. warnings.
  • Page 77: Preventive Maintenance

    NOTE: before carrying out any operations on the unit read the 'Safety standards' chapter care- fully. NOTE: any work carried out on the equipment must be performed by qualified technicians autho- rised by SOCOMEC. Routine maintenance carried out annually is recommended in order to provide optimum operating efficiency and avoid equipment downtime.
  • Page 78: Safeguarding The Environment

    17. SAFEGUARDING THE ENVIRONMENT Do not dispose of electrical appliances with normal waste, use separate collection facilities. Follow local council waste regulations for proper disposal arrangements to reduce the environmental impact of waste electrical and electronic equipment or contact your local government for information regarding the collection arrange- ments available.
  • Page 79: Technical Specifications

    Maximum discharging current 160 + 240 + Maximum recharging current Battery Section Supported in combination with PMS. Lithium, Lead acid, Vanadium Redox, Generic Battery Please contact Socomec for compatibility. AC Section Rated power Maximum power 36.3 72.6 72.6 145.5 Rated apparent power Maximum apparent power 36.3...
  • Page 80 Grid code compatibility is always being upgraded, please contact Grid code SOCOMEC for grid code compatibility. 1. Depending on the specific country setting and regulations. SUNSYS PCS2 Power Conversion System and Storage from 33 to 200 kVA - Ref.: IOMSUNPCXX04-EN 01...
  • Page 84 Socomec: our innovations supporting your energy performance 3,200 independent manufacturer employees % of sales revenue experts worldwide dedicated to R&D dedicated to service provision Your power management expert POWER POWER POWER EXPERT SWITCHING MONITORING CONVERSION SERVICES The specialist for critical applications...

This manual is also suitable for:

Sunsys pcs2 33 trSunsys pcs2 100 tlSunsys pcs2 66 trSunsys pcs2 200 tlSunsys pcs2 132 tlSunsys pcs2 100 tr ... Show all

Table of Contents