Error
E01
E02
E03
E04
E05
E06
E07
E08
E09
E10, E11
E14
E15
E16
E17
E18
E19
E22
Wieland Electric GmbH | BA001133 | 04/2017 (Rev. A)
Cause/description
Cross connection between
OSSD1 and OSSD2
Overload on OSSD1
Overload on OSSD2
High-impedance short cir-
cuit to VCC OSSD1
High-impedance short cir-
cuit to VCC OSSD2
Short circuit against GND
at OSSD1
Short circuit against +24 V
at OSSD1
Short circuit against GND
at OSSD2
Short circuit against +24 V
at OSSD2
OSSD error, source un-
known
Undervoltage (< +15 V)
Overvoltage (> +32 V)
Overvoltage (> +40 V)
Foreign transmitter de-
tected
Ambient temperature too
high
Ambient temperature too
low
Interference detected on
plug pin 3. Signal output:
output signal is not equal
to the signal input read-
back value: it switches si-
multaneously with the
other signal line.
Troubleshooting
Measures
Check the wiring between
OSSD1 and OSSD2.
Check the wiring or exchange
the connected component (re-
ducing the load).
Check the wiring or exchange
the connected component (re-
ducing the load).
Check the wiring. Exchange
the cable, if applicable.
Check the wiring. Exchange
the cable, if applicable.
Check the wiring. Exchange
the cable, if applicable.
Check the wiring. Exchange
the cable, if applicable.
Check the wiring. Exchange
the cable, if applicable.
Check the wiring. Exchange
the cable, if applicable.
Check the wiring. Exchange
the cable and the receiver if
necessary.
Supply the device with the
correct voltage.
Supply the device with the
correct voltage.
Supply the device with the
correct voltage.
Remove foreign transmitters
and increase the distance to
the reflective surfaces. Actu-
ate the start button if avail-
able.
Ensure correct environmental
conditions
Ensure correct environmental
conditions
Check the wiring.
Sensor behav-
ior
Automatic reset
Automatic reset
Automatic reset
Automatic reset
Automatic reset
Automatic reset
Automatic reset
Automatic reset
Automatic reset
Automatic reset
Automatic reset
Automatic reset
Locking
Locking
Automatic reset
Automatic reset
Automatic reset
48

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Slc-4Slc-4prSlc-4stSlc-4trSlc-4sl