3" /80 Mm Only) Flexible Vent System - UTICA BOILERS MAHF-125 Installation, Operation & Maintenance Manual

Condensing gas fired
Hide thumbs Also See for MAHF-125:
Table of Contents

Advertisement

5.10 (3" /80 mm Only) Flexible Vent System

Flexible Pipe Vent Lengths
Boiler Size
Vent Size
Minimum
Exhaust
Natalini
Intake
Exhaust
DuraVent
®
Intake
Exhaust
Centrotherm
Intake
Exhaust
Z-Dens
Intake
Single Wall Elbows - Equivalent Length
45° bend
90° bend
NOTICE
Flexible vent systems shall only be run vertical.
Horizontal runs before adapting to flexible must be
rigid pipe.
• Maximum vent lengths based on equivalent straight
runs only. Include rigid pipe and fittings in overall
equivalent length calculations.
• Flexible venting installations use single wall
polypropylene to pass flue gasses to base of chimney,
then flexible venting to get them to termination at the
top.
• Combustion air is not supplied through masonry
chimney. Combustion air must be from outside using 3"
[80 mm] single wall polypropylene.
• Position boiler to use minimum of rigid single wall
polypropylene venting to the chimney.
• Follow venting manufacturer's instructions on assembly
and clearances to maintain.
• Avoid sharp bends in flexible venting.
5 - COMBUSTION AIR AND VENT PIPING
125/150
3" [80 mm] Diameter Pipe
Minimum
Maximum
6 ft [1.8 m]
75 ft [22.8 m]
6 ft [1.8 m]
50 ft [15.2 m]
6 ft [1.8 m]
82 ft [24.9 m]
6 ft [1.8 m]
50 ft [15.2 m]
6 ft [1.8 m]
52 ft [15.8 m]
6 ft [1.8 m]
50 ft [15.2 m]
NA
NA
3" [80 mm]
0.82 ft [0.25 m]
1.64 ft [0.50 m]
FIGURE 5-24 - (3" / 80 mm Only) Flexible Venting
System CAN BE USED ON ALL SIZES
Flexible Vent
Rigid Vent
Combustion
Air
21
Vent Terminal
240012565 REV A, [05/15/2019]