Ball valves

Advertisement

KTM 2-WAY, 3-WAY AND V-PORT BALL VALVES
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
PRESSURE TEST
• In case of pressure test of the pipe system,
the valve should be in a half-open position
and check the leakage from joint connection
or gland. If the test is performed with the
valve in close position, overload pressure on
the seat could cause seat leakage.
• The ball valve should be operated to either
full open or closed position. Prolonged use
in a half-open position could cause seat
deformation or seat leakage.
OPERATION
Refer to Figure 2
• The closed position of KTM ball valves is
indicated by either the handlever or the
direction of the parallel flats on the top of
the stem (see picture).
• All standard manually operated valves are
'clockwise to close'.
• The valve requires no 'additional tightening'
to shut off, excessive handle operation could
break the lever, injure the operator, or deform
the stopper or stem which may lead to seat
leakage.
FIGURE 3
Tagplate
3
SAITAMA
JAPAN
0062
ASME B16.34
1
2
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product.
Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
KTM is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions, Emerson and
the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be
construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by
our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without
notice.
Emerson.com/FinalControl
MAINTENANCE
Refer to Figure 3
No routine maintenance is required other
than periodic inspection to ensure satisfactory
operation and sealing. Any sign of leakage
from the gland packing should be addressed
immediately by depressurizing the valve and
tightening the gland screws gradually and
evenly. If no further adjustment is possible,
or if seat or joint leakage is suspected, the
valve will require a complete overhaul. This
should be carried out after depressurization
and in accordance with specific maintenance
Instructions. Only original spares should be
used.
4
7
TYPE
EB12
BODY
CF8M
CLASS
300
STEM
SEAT
720
CWP
/
0
@
RATING
5
8
6
9
BALL
CF8M
316
SEAT
E
515
flF
DATE
2001.12
10
11
FIGURE 2
Open position
Closed position
PARTS LIST
Item
Description
1
CE marking
2
Number of notified body
3
Identification and manufacturer
4
Valve type
5
Body material
6
Ball material
7
ASME class
8
Stem material
9
Seat material
10
P/T rating (max/min) of seat
11
Year and date of manufacture