Troubleshooting; Action Table In The Event Of A System Or Component Malfunction - ADB L-861SE Instruction Manual

Clamp band erte incandescent elevated runway threshold/end light, medium-intensity, clamp band
Table of Contents

Advertisement

2.6 Troubleshooting

2.6.1 Action Table in the
Event of a System or
Component Malfunction
Problem
Lamp not energizing
Lamp not turning on at
normal level
Improper color
Short lamp life
© ADB bvba All Rights Reserved
This section contains troubleshooting information. This information covers only the most
common problems that you may encounter. If you cannot solve the problem with the
information given here, contact your local ADB Airfield Solutions' representative for help.
Product ERTE Troubleshooting Guide Table
Table 6:
Possible Cause
Defective lamp
Loose or broken contacts
Power supply failure
Fixture wires pinched
Defective isolation transformer
Isolation transformer secondary current
incorrect or wrong frequency type
Wrong fixture installed
inner lens broken
inner lens not installed or wrong color
Current too high (series circuit
applications)
Cracked lens or base assembly
Component Failure
Corrective Action
Replace the lamp
Replace the lamp or light socket
Replace the power supply
Replace/repair the wire
Replace the transformer
Check for the proper transformer size and replace with
the correct transformer
Replace the fixture
Replace inner lens
Calibrate the CCR
Replace the broken assembly. Clean and reassemble the
light fixture.
Replace the failed component. Check for a cause of the
failure and repair or replace any defective components.