Download Print this page

Carrier 140/E Series Installation, Start--Up, Operating, And Service And Maintenance page 37

Single-stage deluxe, induced-combustion 4-way multipoise gas furnace

Advertisement

multiplier inTable 10for
the correct input rate.
2. Determine
the correct
orifice and manifold
pressure
adjust-
ment. There
are two different
orifice and manifold
adjust-
ment tables. All models
in all positions,
except
Low NOx
models
in downflow
or horizontal
positions,
use Table 13
(22,000
Btuh/Burner).
Low NOx models
in the downflow
or horizontal
positions
must use Table 14 (21,000
Btuh/Burner).
See input
listed
on rating
plate.
a. Obtain average yearly gas heat value (at installed altitude)
from local gas supplier.
b. Obtain average yearly gas specific gravity from local gas
supplier.
c. Find installation
altitude
in Table 13 or 14.
d. Find closest
natural
gas heat value and specific
gravity
in Table 13 or 14.
e. Follow
heat value and specific gravity
lines to point of
intersection
to find orifice size and manifold
pressure set-
tings for proper
operation.
f. Check and verify burner
orifice size in furnace.
NEVER
ASSUME
ORIFICE
SIZE.
ALWAYS
CHECK
AND
VERIFY.
g. Replace
orifice with correct size if required
by Table
10,
12, 13, or 14 Use only factory-supplied
orifices.
See
EXAMPLE
1.
Table
10 - Altitude
Derate Multiplier
for U.S.A.
ALTITUDE
PERCENT
DERATE MULTiPLiER
FT.(M)
OF DERATE
FACTOR*
0-2000
0
1.00
(0- 61O)
2001-3000
8-I2
0.90
(61 O- 914)
3001-4000
12-16
0.86
(914-1219)
4001-5000
16-20
0.82
(1219-1524)
5001-6000
20-24
0.78
1524-1829)
6001-7000
24-28
0.74
(1829-2134)
7001-8000
28-32
0.70
(2134- 2438)
8001-9000
32-36
0.66
(2438-2743)
9001-10,000
36-40
0.62
(2743-3048)
* Derate multiplier factors are based on midpoint altitude for altitude
range.
3. Adjust manifold
pressure
to obtain correct
input rate.
a. Turn gas valve ON/OFF
switch to OFF.
b. Remove
manifold
pressure
tap plug from gas valve. (See
Fig. 47.)
c. Connect
a water column
manometer
or similar
device to
manifold
pressure
tap.
d. Turn gas valve ON/OFF
switch to ON.
e. Manually
close blower
door switch.
f. Set thermostat
to call for heat.
g. Remove
regulator
seal cap and turn regulator
adjusting
screw counterclockwise
(out) to decrease
input
rate of
clockwise
(in) to increase
input rate.
EXAMPLE
1:(0-2000
ft. (0-610
M) altitude)
For 22,000
Btuh per burner
application
use Table 13.
Heating
value = 1000 Btuh/cu
t't.
Specific gravity
= 0.62
Therefore:
Orifice No. 43"
Manifold
pressure:
3.7-In.
W.C.
*Furnace
is shipped
with No. 43 orifices.
In this example
all main burner
orifices
are the correct
size and do not need to be changed
to obtain proper
input rate.
h. Install regulator
seal cap.
i. Leave manometer
or similar device
connected
and pro-
ceed to Step 4.
NOTE:
DO NOT set manifold
pressure
less than 3.2-In.
W.C. or
more than 3.8-In.
W.C. for natural
gas at sea level.
If manifold
pressure
is outside
this range, change
main burner
orifices.
Refer
to Table 13 and 14.
NOTE:
If orifice hole appears
damaged
or it is suspected
to have
been
redrilled,
check
orifice
hole with
a numbered
drill bit of
correct
size.
Never
redrill
an orifice.
A burr-free
and squarely
aligned
orifice
hole is essential
for proper flame characteristics.
4. Verify natural
gas input rate by clocking
meter.
NOTE:
Gas valve regulator
adjustment
cap must be in place for
proper input to be clocked.
a. Turn off all other gas appliances
and pilots served by the
meter.
b. Run furnace
for 3 minutes
in heating
operation.
c. Measure
time (in sec) for gas meter to complete
I revolu-
tion and note reading. The 2 or 5 cubic feet dial provides
a more accurate
measurement
of gas flow.
d. Refer to Table 12 for cubic ft. of gas per hr.
e. Multiply
gas rate (cu ft./hr) by heating
value (Btuh/cu
ft.)
to obtain
input.
If clocked
rate
does
not match
required
input
from
Step
1,
increase
manifold
pressure
to increase
input or decrease
manifold
pressure
to decrease
input. Repeat
steps b through
e until correct
input is achieved.
Reinstall
regulator
seal cap on gas valve.
5. Set temperature
rise. The furnace
must operate
within
the
temperature
rise ranges
specified
on the furnace
rating
plate.
Do not exceed
temperature
rise range
specified
on
unit rating
plate.
Determine
the temperature
rise as fol-
lows:
ELECTRICAL
SHOCK
HAZARD
Failure
to follow
this warning
could result in personal
iniury
or death.
Disconnect
115-v
electrical
power
and install
lockout
tag
before changing
speed tap.
37

Advertisement

loading