Worcester Benchmark Danesmoor Utility 12/14 Installation And Servicing Instructions page 4

Conventional flue and room-sealed bf floor standing oil-fired pressure jet appliances
Table of Contents

Advertisement

12/14 Table 2. Electro Oil Inter B9A Burner (See Fig. 18)
Fuel
Nozzle
28 Sec. Kerosene
0.40 60°ES
28 Sec. Kerosene
0.50 60°ES
15/19 Table 3. Electro Oil Inter B9B Burner (See Fig. 19)
Fuel
Nozzle
28 Sec. Kerosene
0.50 60°ES
28 Sec. Kerosene
0.55 80°EH
28 Sec. Kerosene
0.60 60°ES
35 Sec. Gas Oil*
0.50 80°S
20/25 Table 4. Electro Oil Inter B11C Burner (See Fig. 20)
Fuel
Nozzle
28 Sec. Kerosene
0.60 80°EH
28 Sec. Kerosene
0.75 80°EH
28 Sec. Kerosene
0.75 80°EH
35 Sec. Gas Oil*
0.60 80°S
35 Sec. Gas Oil*
0.60 80°S
26/32 Table 5. Electro Oil Sterling 40 Burner (See Fig. 21)
Fuel
Nozzle
28 Sec. Kerosene
0.85 80°EH
28 Sec. Kerosene
0.85 80°EH
28 Sec. Kerosene
1.00 80°EH
35 Sec. Gas Oil*
0.50 80°H
35 Sec. Gas Oil*
0.55 80°H
35 Sec. Gas Oil*
0.55 80°H
26/32 Table 6. Electro Oil Sterling 40 Burner (See Fig. 21)
Fuel
Nozzle
28 Sec. Kerosene
0.85 80°EH
28 Sec. Kerosene
0.85 80°EH
28 Sec. Kerosene
1.00 80°EH
NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE
Pump
Fuel Flow
Pressure
Rate
(p.s.i.)
Kg/h
l/h
130
1.11
1.41
100
1.30
1.64
NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE
Pump
Fuel Flow
Pressure
Rate
(p.s.i.)
Kg/h
l/h
110
1.40
1.77
115
1.59
2.01
105
1.78
2.25
155
1.80
2.12
NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE
Pump
Fuel Flow
Pressure
Rate
(p.s.i.)
Kg/h
l/h
130
1.87
2.37
105
2.10
2.66
130
2.34
2.96
120
2.13
2.51
150
2.37
2.79
NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE
Pump
Fuel Flow
Pressure
Rate
(p.s.i.)
Kg/h
l/h
110
2.36
2.99
130
2.66
3.37
130
2.95
3.74
260
2.44
2.87
265
2.76
3.25
330
3.06
3.60
NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE
Pump
Fuel Flow
Pressure
Rate
(p.s.i.)
Kg/h
l/h
110
2.36
2.99
130
2.66
3.37
130
2.95
3.74
Flue Gas
Approx.
%CO
Temp.
Air
2
(°C)**
Setting
180
10.0
6.0
195
11.5
7.0
Flue Gas
Approx.
%CO
Temp.
Air
2
(°C)**
Setting
215
10.5
8.5
225
10.5
8.75
235
11.5
9.0
235
11.5
9.0
Flue Gas
Approx.
%CO
Temp.
Air
2
(°C)**
Setting
190
11.0-11.5
5.5
205
11.5-12.0
6.0
220
12.0-12.5
6.5
205
11.5-12.0
6.0
220
12.0-12.5
6.5
Flue Gas
Approx.
%CO
Temp.
Air
2
(°C)**
Setting
225
11.0-11.5
11
240
11.0-11.5
12
245
11.5-12.0
16
220
11.5-12.0
235
11.5-12.0
14
240
12.0-12.5
16
Flue Gas
Approx.
%CO
Temp.
Air
2
(°C)**
Setting
225
11.0-11.5
240
11.0-11.5
245
11.5-12.0
4
Appliance
Input
kW
Btu/hr
13.5
46,000
15.5
53,000
Appliance
Input
kW
Btu/hr
17
58,000
19
65,000
21.5
73,000
21.5
73,000
Appliance
Input
kW
Btu/hr
22.5
77,000
25
86,000
28
96,000
25
86,000
28
96,000
Conventional Flue Appliance (CF/LLD)
Appliance
Input
kW
Btu/hr
28.5
97,000
32
109,000
35.5
121,000
9
28.5
97,000
32
109,000
35.5
121,000
RS Balanced Flue Appliance
Appliance
Input
kW
Btu/hr
10
28.5
97,000
15
32
109,000
20
35.5
121,000
Output
kW
Btu/hr
12
41,000
14
48,000
Output
kW
Btu/hr
15
51,000
17
58,000
19
65,000
19
65,000
Output
kW
Btu/hr
20
68,000
22.5
77,000
25
85,000
22.5
77,000
25
85,000
Output
kW
Btu/hr
26
89,000
29
99,000
32
109,000
26
89,000
29
99,000
32
109,000
Output
kW
Btu/hr
26
89,000
29
99,000
32
109,000