Primary Reactor, Reduced Voltage Starters Catalog S510
Non-Reversing
Mounted in the Medium Voltage Section
Three incoming line connectors.
One drawout 3-pole gang-operated line isolation switch assembly
with isolating shutter, external operating handle interlocked to
prevent opening the medium voltage compartment door until the
isolating switch is open and grounded.
One vertically mounted current limiting power fuse with pop-up
blown fuse indicators.
One magnetic 3-pole vacuum contactor with dc operating coils and
mechanical interlock to prevent opening the isolation switch when
the contactor is closed.
One control power transformer (115-volt secondary).
Two CPT primary current limiting fuses.
One control circuit secondary fuse.
One run-test circuit.
Four electrical interlocks (2NO, 2NC).
Mounted in the Low Voltage Compartment
One control panel with:
– One MP-3000 motor protection relay
– Two interposing relays
One set of control circuit
terminal blocks.
Reduced Voltage Structure
One magnetic 3-pole vacuum run contactor with dc operating coil
and electrical interlocks.
Three current transformers.
One medium-duty starting reactor with 50 – 65 – 80% taps.
Specifications
TABLE 12. STARTER SELECTION INFORMATION — DIMENSIONS IN INCHES (MM)
HORSEPOWER
VOLTS
2200 – 2400 Volts Non-Reversing
700/800
2300
1500/1750
2300
4000 – 4800 Volts Non-Reversing
1250/1500
4600
2500/3000
4600
6600 Volts Non-Reversing
2000/2250
6600
4000/4500
6600
Horsepower based on NEMA standard design B motor at 1800 rpm.
When horizontal bus is added, height becomes 92 inches (2337 mm).
At higher hp rating maximum acceleration time is 3.5 seconds.
At higher hp rating maximum acceleration time is 6 seconds.
Note: See Figure 11 for Starter Arrangement diagram.
Dimensions for estimating purposes only.
22
EATON CORPORATION Cutler-Hammer Chiller Starter (AMPGARD) Technical Data TD02003003E Effective: October 2006
CONTACTOR
STARTER
AMPERE RATING
INTERRUPTING
(ENCLOSED)
RATING (KVA)
200
200,000
400
200,000
200
400,000
400
400,000
200
570,000
400
570,000
Starting Characteristics
TABLE 11. TYPE 502 REACTOR STARTING CHARACTERISTICS
STARTER
% MOTOR
% MOTOR
TYPE
VOLTAGE
CURRENT
80% Tap
80
80
65% Tap
65
65
50% Tap
50
50
Factory set on 65% tap.
M
FIGURE 11. STARTER ARRANGEMENT
DIMENSIONS
HEIGHT
WIDTH
80 (2032)
72 (1829)
80 (2032)
72 (1829)
80 (2032)
72 (1829)
80 (2032)
72 (1829)
80 (2032)
72 (1829)
80 (2032)
72 (1829)
% LINE
CURRENT
% TORQUE
80
64
65
42
50
25
R
Reactor
WEIGHT
DEPTH
LBS. (KG)
30 (762)
2800 (1271)
30 (762)
2800 (1271)
30 (762)
2800 (1271)
30 (762)
2800 (1271)
30 (762)
3300 (1498)
30 (762)
3300 (1498)