Lbs Switch; Starter Fuse Information - Eaton Cutler-Hammer AMPGARD Technical Data Manual

Chiller starter medium voltage
Hide thumbs Also See for Cutler-Hammer AMPGARD:
Table of Contents

Advertisement

LBS Switch

TABLE 7. LBS SWITCH RATINGS
DESCRIPTION
Switch with Internal Fuses
(450E Maximum at 5 kV, 350E Maximum at 7.2 kV)
Switch with 600E and 750E Fuses
(5 kV Maximum)
Switch with 1100E and 1350E Fuses
(5 kV Maximum)
Unfused (7.2 kV Maximum)
1200 ampere rating is for NEMA 1 enclosure with vented covers. NEMA 3/12 rating (without vents) is 1000 amperes.

Starter Fuse Information

TABLE 8. FUSE COORDINATION RECOMMENDATIONS
MINIMUM FLA
MAXIMUM FLA
400 Ampere Contactor
10.0
22.9
23.0
31.1
31.2
41.9
42.0
46.7
46.8
62.9
63.0
74.7
74.8
82.9
83.0
93.5
93.6
123.9
124.0
137.0
137.1
165.9
166.0
187.0
187.1
246.9
247.0
328.9
329.0
360.0
360.1
400.0
800 Ampere Contactor
200.0
250.0
250.1
330.0
330.1
499.0
500.0
650.1
650.1
720.0
Specific motor acceleration time and locked rotor current must be reviewed
to ensure fuse 24R fuse has sufficient capacity for start cycle.
EATON CORPORATION Cutler-Hammer Chiller Starter (AMPGARD) Technical Data TD02003003E
CONTINUOUS
AND BREAK
CURRENT AMPERES
600
1200
1200
1200
FUSE RATING
CT RATIO
70-2R
25:5
70-2R
50:5
100-3R
50:5
100-3R
75:5
130-4R
75:5
150-5R
100:5
170-6R
100:5
170-6R
150:5
200-9R
150:5
200-9R
200:5
230-12R
200:5
230-12R
300:5
390-18R
300:5
450-24R
400:5
450-24R
600:5
450-24R
600:5
450-24R
300:5
450-24R
400:5
650-36R
600:5
800-44R
800:5
800-44R
1000:5
SHORT-TIME
FAULT CLOSE
(2 SECONDS)
(UNFUSED) KA
CURRENT KA
40
25
61
38
61
38
61
38
FUSED
INTERRUPTING RATING
(KA SYMMETRICAL)
50
40
31.5
N/A
Copyright 2006
19