18)
Symptom
Motor stopped. Light in
display, but no fault report.
CAUTION:
Prior to running in Local,
insure all other
equipment associated
with the VLT is ready to
function or has been
isolated
19)
Start the VLT adjustable
frequency drive by
pressing "Start" on the
control panel.
20)
Has the display locked, i.e.
it cannot be changed or is
illegible?
NO
YES
22)
Has the motor been
correctly connected and
are all motor phases in
order?
YES
NO
23)
Attempt to run the VLT in
local.
SEE CAUTION at LEFT
Make the following
parameter settings:
Parameter 003 = Local
Parameter 004 = Fref.
Change by means of
+ and – keys.
Does the motor run?
YES
NO
24)
Verify that the control
signals are connected to
the correct terminals and
the appropriate parameter
settings have been
entered.
20
21)
Replace the Control Card,
see page 31. If this does
not help, the fault might be
electrical noise. Check
whether the following
precautions have been
taken:
• Have shielded cables
been used?
• Are the shields correctly
terminated?
• Is the unit properly
grounded to earth?
Correct the motor wiring
Insure motor overloads are
seset and output contactor
closed.
25)
Replace the Control card,
see page 31.
Does the motor run?
NO
26)
Replace the Interface/ILD
card, see page 31.
Does the motor run?
NO
Consult
factory