Do not permit any vibration approaching it directly. • Go through module specification carefully, ensure inputs, output connections are made with the specifications. Use standard cables for wiring. • Use Product under pollution degree 2 environment. Page 6 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
The modules are equipped with electronic components that may be destroyed by electrostatic discharge. When handling the modules, ensure that the environment (persons, workplace and packing) is well grounded. Avoid touching conductive components, G-BUS Pin. Page 7 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
Signal Description Signal Description Pin No. System Power, 24V System Power, Ground System Power, 24V System Power, Ground Field Power, Ground Field Power, Ground Field Power, 24V Field Power, 24V Page 8 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
Refer to ‘Adapter TCP/IP Special Register (0x1040, 4160)’ at section ‘ 3.3.3’ ** When using in ‘60℃ ~ 70℃’ temperature environment, the power dissipation is limited to 0.8A. Page 9 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
1 Green, Field Power Status 2 LEDs (each RJ45 Connector) 1 Yellow, Link/Active 1 Green, Not used Module Location Starter module left side of G-Series system Field Power Detection About 14Vdc Page 10 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
- Memory error or CPU watchdog error. 2.3.2. Physical Connection LED(LINK) Status To indicate Not Powered or Not Linked Device may not be powered Adapter physical connected Green Adapter Ethernet Controller physically connected Page 11 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
2.3.5 Field Power Status LED Status To indicate No field, System power Not supplied 24Vdc field power, 5Vdc system power. Supplied Green Supplied 24Vdc field power, 5Vdc system power. field, System power Page 12 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
4.1 Total Expansion The number of the module assembly that can be connected is 63 so the maximum length is 426mm Exception GN-9289 is excepted to calculate maximum length because that is double width module. 4.2. Plugging and Removal of the Components.
System and Field power must be supplied separately as the picture above. ※ If the power is supplied to each System and Field power from same power source, it would be vulnerable to power noise. Page 16 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
After setting up the dip switch as 254 or 255, Power off and on in order to start the IAP mode. (254=Fixed IP Address (192.168.0.100) / 255=Last used IP Address) After Login the Web Browser connecting (User ID: beijer, Password: beijer) To update the binary file. Page 19 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
Page 20
GN-9289 User Manual Has been updated. Please reboot the adapter. Page 20 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
IP_DIP bit#7 = ON : Enable DHCP/BOOTP * = ON : Use Lowest IP Address with IP_DIP value * DHCP/BOOTP have to be set in special register (0x1045) (default : BOOTP). Page 21 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
GN-9289 User Manual 6.3 RS232 Port for MODBUS/RTU, Touch Panel or IOGuide Pin# Signal Name Description Reserved ---- RS232 TXD RS232 RXD RS232 GND Page 22 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
20 times every 2sec. If BOOTP/DHCP sever does not response, the Adapter applies its IP Address with EEPROM (Latest saved IP Address). The following is an example of adapter IP-Address setup that can be used with a third party BOOTP/DHCP server. * Beijer BOOTP server Page 23 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
These are examples of adapter IP-Address setup by manual function. Ex) XXX. XXX. XXX. 1 Ex) XXX. XXX. XXX. 2 Ex) XXX. XXX. XXX. 8 Ex) XXX. XXX. XXX. 253 Page 24 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
Page 25
If the adapter is Bootp/DHCP enabled (Dip Pole #9 ON), adapter will send Bootp/DHCP request 20 times every 2sec, after power reset. If Bootp/DHCP server does not response, adapter will use the latest saved IO address in EEPROM. Page 25 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
Page 26
Double click on one of the detected ‘Bootp request message’ and set the IP address. If you wait for more the 40 seconds, you have to restart the GN-9289. Another way to set are, “Add New Device”Click on “Add New Device”, write the Mac Address and then the IP Adress.
Page 27
GN-9289 User Manual Check IP address of the normal. Page 27 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
The data exchange between network adapter and expansion modules is done via an I/O process image data by G-Series protocol. The following figure shows the data flow of process image between network adapter and expansion modules. Page 28 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
* 16. Process output image bits All output registers area are addressable by bit address. 0x1000~ Read/Write 1,5,15 Size of output image bit is size of output image register * 16. Page 29 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
≥ 3.5 char ≥ 3.5 char 1 char 1 char Up to 252 chars 2 chars Function and data field of MODBUS/TCP are identical to function and data field of MODBUS/RTU. Page 32 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
• Length - The length field is a byte count of the following fields, including the Unit Identifier and data fields. • Unit Identifier – This field is used for intra-system routing purpose. Typically MODBUS server must be returned with the same value set by MODBUS client. Page 33 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
Quantity of Outputs Lo 0x0A Response Field name Example Function Code 0x01 Byte Count 0x02 Output Status 0x55 Output Status 0x02 In case of address 0x1015~0x1000 output bit value: 10101010_01010101. Page 34 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
Quantity of Inputs Lo 0x0A Response Field name Example Function Code 0x02 Byte Count 0x02 Input Status 0x80 Input Status 0x00 - In case of address 0x0015~0x0000 input bit value: 00000000_10000000. Page 35 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
Field name Example Function Code 0x05 Output Address Hi 0x10 Output Address Lo 0x01 Output Value Hi 0xFF Output Value Lo 0x00 - Output bit of address 0x1001 turns ON. Page 37 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
0x06 Register Address Hi 0x08 Register Address Lo 0x00 Register Value Hi 0x11 Register Value Lo 0x22 - In case of address 0x0800 output register value: 0x0000 changes to 0x1122. Page 38 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
Echo Request Data Reset with Factory default 1),2) IP Address, Subnet Mask Address, Gateway Address will be the factory defaults value. 2) Mac Address will be the factory default value. Page 39 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
Page 40
(neither a normal response nor an exception response), since its last restart, clear counters operation, or power–up. Sub- Data Field (Request) Data Field (Response) Description function 0x000F(15) 0x0000 Slave No Response Count Page 40 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
0x0F Starting Address Hi 0x10 Starting Address Lo 0x00 Quantity of Outputs Hi 0x00 Quantity of Outputs Lo 0x0A In case of address 0x1015~0x1000 output bit value: 00000000_00000000changes to 00000001_01010101. Page 41 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
Starting Address Lo 0x08 Quantity of Registers Hi 0x00 Quantity of Registers Lo 0x02 .- In case of address 0x0800, 0x0801 output register value: 0x0000, 0x0000 changes to 0x1122, 0x3344. Page 42 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
Read Reg. Value#0 Lo 0x22 Read Reg. Value#1 Hi 0x33 Read Reg. Value#1 Lo 0x44 In case of address 0x0800, 0x0801 output register value: 0x0000, 0x0000 changes to 0x1122, 0x3344. Page 43 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
Gateway Path Unavailable path from the input port to the output port for processing the request. - GN-9289 response exception code 01, 02, 03, 04 and 06. Page 44 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
Read/Write 2word Gateway. If 192.168.123.254,then 0xA8C0, 0xFE7B. Ethernet physical address (MAC-ID). 0x1053(4179) Read 3word If 11-22-33-44-55-66, then 0x2211, 0x4433, 0x6655. * Power off and then power on, this value is applied. Page 46 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
DHCP/Booth enable, Dip SW(0x01), Field Power On = 0x8101 upto Expansion slot’s GT-number including GN 0x110E(4366) Read 33word First 1word is adapter’s number, if GN-9289, then 0x9289 0x1110(4368) Read 1word Number of expansion slot upto Expansion slot Module Id.
Instance Attribute Acces Name Data Type Value s Rule Revision UINT 0001 Max Instance UINT 0001 Maximum ID Number Class Attributes UINT 0000 Maximum ID Number UINT 0000 Instance Attributes Page 52 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
Bit 2: Overflow I/O size Code Bit 3: I/O Configuration failure Bit 4: EEPROM Checksum fault Bit 6: Invalid Module ID Bit 7: Firmware fault Firmware UDINT YYYYMMDD Release Date Page 53 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
09 00 01 00 02 00 04 00 06 Object Class List Array of 00 F4 00 F5 00 F6 00 70 00 UINT 71 00 Number Available UINT Maximum number of connections supported Page 54 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
Input process image data BYTE Data Output (Consumed) Set/G Array Process Image Output process image data BYTE Data 9.5 Connection Manager Object Class Code: 06 9.5.1 Class Attributes, Instance Attribute None Page 55 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
Port Type UINT 0004 , TCP/IP Port 0002 , CIP port number Port Number UINT associate with port UINT Port Object Padde EPATH Port Name Short_String Padded Node Address EPATH Page 56 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
2 – The device shall use the interface configuration values via DHCP upon start-up. 3-15 – Reserved. If TRUE, the device shall resolve host names by querying a DNS server. Reserved 5-31 Page 58 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
Service Name Code Class Instance 0x01 Get_Attribute_All 0x0E Get_Attribute_Single 9.8.2. Class Attributes Instance Attribute Access Name Data Type Value Rule Revision UINT 0002 Max Instance UINT 0001 Num Instances UINT 0001 Page 59 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
Page 60
Bit 2~4 : Auto negotiation 5 : Manual Setting required Reset Bit 6 : Local Hardware Fault Others : 0 Physical ARRAY of 6 USINTs Same as MAC address Address Page 60 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
Output Reset at stop BOOL 0: Disabled(default) 1: Enable *After the system is reset, the new “Set Value” action is applied. If slot location is changed, default value is set automatically. Page 61 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
Page 62
Network Adapter Module External ID = 0x00 External ID for slot position #1 External ID for slot position #2 External ID for slot position #62 External ID for slot position #63 Page 62 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
4 Byte Firmware Revision Structure of USINT USINT *After the system is reset, the new “Set Value” action is applied. If slot location is changed, default value is set automatically. Page 63 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
Page 64
- usually it is used by Analog I/O module. 1 1: Priority 3 (high) S (Status for Profibus Slot Diagnostic) 0: No Status 1: Support Word Input Diagnostic(0x8000 = -32678) Page 64 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
Page 65
1 1: have no Input or Output Data … 1 1 1 1 1 1: 63 Bit/Byte/Word MODBUS Reference MODBUS Reference Documents http://www.modbus.org MODBUS Tools http://www.modbustools.com, MODBUS poll http://www.win-tech.com , MODSCAN32 Page 65 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
- Contact Sales team and send module for repair. - Check main power Cable System Power LED turns - System power is not supplied. - Contact Sales team and send module for repair. Page 66 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
Page 68
Common for 0Vdc 7508 7511 GT-7511 Power Expansion, In 24Vdc, Out 1A/5Vdc 7518 GT-7518 Common for 24Vdc GT-7588 Common for 0Vdc, 24Vdc 7588 GT-7641 Field Power, 5/24/48 Vdc, 110/220 Vac 7641 Page 68 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
Page 69
- Sink : The method of in/output power supply if a device has no power source. - Source : The method of in/output power supply if a device has the power source. Page 69 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
Page 70
GN-9289 User Manual Head office Beijer Electronics AB Box 426 20124 Malmö, Sweden Phone +46 40 358600 www.beijerelectronics.com Page 70 of (70) G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx...
Need help?
Do you have a question about the GN-9289 and is the answer not in the manual?
Questions and answers